Bosch Appliances manual D7212G Command Center Terminal Function, Power at Command Centers

Page 50

D7212G

Arming Devices

10.2.2Installation

Consult the command center Operation and Installation Guide for installation and mounting instructions. Command centers connect to the panel in parallel as shown in Table 13.

 

D7212G

Command Center

Terminal

 

Function

Wire Color

Function

32*

 

POWER +

Red

12 VDC

 

 

 

 

 

31

 

DATA BUS A

Yellow

Data-In

 

 

 

 

 

30

 

DATA BUS B

Green

Data-Out

 

 

 

 

 

29

 

COMMON

Black

Common

 

 

 

 

 

*Connect with at least 5 ft. (1.5 m) of 22 AWG wire (14 ft. [4.3 m] of 18 AWG wire).

Table 13: Command Center Connections

Switching the green and yellow wires affects other command centers: Incorrectly connecting the green wire from the command center to Terminal 31 and the yellow wire to Terminal 30 causes other command centers connected to the panel to go blank and/or sound random beep tones.

Devices can be connected to the data bus, Terminals 30 and 31, by parallel wire runs from the panel to each device, wire from device to device, or a combination of the two as long as a maximum of 15000 ft. (4572 m) of 22 AWG wire for all devices connected to the SDI Bus combined is used.

It is recommended, however, that command centers be limited to 2000 ft. (610 m) per run and the D9131A be limited to 1000 ft. (305 m) per run.

Extra power needed for more command centers: The D1255 Command Center draws 104 mA when it is idle. It draws 206 mA with the keys lit and the sounder activated. Review Section 5.0 Power Outputs on page 29 to determine the total power output requirements for the system.

One or more D8132 Battery Charger/Power Supply Modules may need to be added for the number of command centers that will be used. Figure 17 shows the D8132 powering command centers in a stand-alone configuration.

 

 

D8132 or

 

 

External

 

 

Power Supply

To

+12 VDC

 

Panel

DATA

+12 VDC

 

 

COMMON

 

DATA

 

 

 

COMMON

 

Figure 17: Power at Command Centers

For UL certificated accounts, use a UL Listed power supply. The D8132 is not UL Listed as a stand-alone power supply.

Application

Tip

CAUTION

Control/Communicator and D8132 (or other power supply) must share COMMON:

Note that Figure 17 shows the common from the D8132 Module connected to both the command centers' common and the common on the control/communicator. Any stand-alone power supply powering any device connected to the panel must also be connected to a common terminal on the panel.

If you are using the Ground Fault Detect capability on the D7212G Control/Communicator and an external power supply:

Make sure that the external power supply selected isolates its Earth Ground connection from the negative side of the Aux Power output. External power supplies that do not isolate Earth Ground will cause ground fault conditions on the control/communicator.

D7212G Operation and Installation Guide

4998138544C

Page 50

© 2003 Bosch Security Systems

Image 50
Contents Control/Communicator D7212G Operation and Installation Guide D7212GContents 11.2 10.111.1 10.0 11.013.0 Figures D7212G Operation and Installation Guide Organization TablesSection Description IntroductionGuide Organization Appendix DescriptionType Styles Used in the Text Related DocumentationDocumentation Conventions Part FCC RulesTips, Notes, Cautions and Warnings D7212G 9000G Series Panel Differences New Features D9412G D7412G D7212GOverview Specifications SecondaryTelephone Connections Telephone Line Ground Fault Detect Features in D7212GCompatible Accessories IntroductionStandard Features Model Display Application Components and Literature Available by Separate Order Other FeaturesControl/Communicator Assembly Listings Listings and ApprovalsBurglary Before Beginning InstallationBeginning the Installation Enclosure OptionsGround Fault Detect Enable Installing the AssemblyConnecting Earth Ground Locking the Reset PinInstall and Wire Detection Devices Finishing the InstallationCharge the Battery While Finishing Install Modules and RelaysProgramming the Panel Install the Point Chart LabelTesting the System Secondary Power Terminals Power SupplyPrimary Power Terminals Installing the Battery Replacing the BatteryBattery Discharge/Recharge Schedule Battery SupervisionBattery Charging Circuit Float Charge Discharge CycleAction Charging Status and Low Battery LEDsType Color StateAux Power Terminals Continuous Current Draw Power OutputsTotal Available Power Programmable Power Outputs TerminalsFire System Power Formula Relay InstallationAvailable Power Verification/Reset RelayTelephone Connections Phone Line Monitor Operation Monitor LED GreenDialing Format Called Party DisconnectLoop Start Ground StartPhone Monitor Select Jumper Position Ground StartD7212G Point Sensor Loops On-board PointsDescription Terminals Point ParametersBell Off-board Points Point Zonex Bus D7212G TerminalsInstalling the D8125 Popex Module D8125, D8127 and D9127 Popit ModulesLength in ft. m Wiring Data Expansion Loops to Popex ModulesExpansion Loops Combined Popit Sensor LoopsConnecting the D8125 Popex to the D7212G Panel Radxpnts Handler Popit Module Point AssignmentsProgram Record Sheet Popit Labels Installing the OctoPOPITD8128D OctoPOPIT Module DescriptionWiring OctoPOPITs Line TerminationD8128D Address Switches Testing Off-board PointsAddress Assignment Switches OctoPOPIT Sensor LoopsConnecting D8128D OctoPOPITs to the D7212G D7212G D8129 OctoRelay Panel Relay D8129 OctoRelay D8129 OctoRelay Switch NumberOff-board Relays D8129 Connections to the D7212G Address Switch Command Center TerminalsAssigning the command center an address Arming DevicesD7212G Command Center Terminal Function Power at Command Centers10.3 D279A Independent Zone Control KeyswitchKeyswitch Operation Maintained Contact Momentary ContactD7212G SDI Devices InstallationPrinter Switch 11.3 D9131A Parallel Printer Interface ModuleSDI Address Address Settings 11.5.2 D9133TTL-E Network Interface ModuleD7212G Accessory Connector Programmer and Accessory ConnectionsProgrammer Connector Programmer Access ReportsAccessoryProgramming ConnectorConnector Programmer and Accessory ConnectionsFaceplate 13.0 13.1 D7212G FaceplateFaceplate Appendix a System Wiring Diagrams, Issue a D7212G Control/Communicator, 1D7212G System Wiring Diagram, 2 D7212G Control/Communicator, 2D7212G System Wiring Diagram, 3 D7212G Control/Communicator, 3D7212G Appendix B Point Address Chart Zonex 1, Points 9 toD7212G Symbols IndexZonex