New Buck Corporation manual DV1000 DIRECT VENT TERMINATION, Installation Instructions

Page 12
DV1000

DV1000

DIRECT VENT TERMINATION

INSTALLATION INSTRUCTIONS

(MAGNAFLEX)

Read the instructions in this manual completely before installing the DV1000 appliance with the Magnaflex vent system. Magnaflex Venting systems are packaged with installation instruc- tions, the instructions must be followed exactly for your safety and to prevent voiding the war- ranty of your appliance and venting system.

The DV1000 will operate safely when installed in accordance with this instruction manual. Read all instructions before starting installation, then follow these instructions carefully to maximize fireplace performance and safety. Report damaged parts to your dealer.

Any common venting of the gas appliance using DV vent kit with other gas appliances is not allowed. Do not connect this appliance to a chimney flue serving a separate solid fuel-burning appliance.

WARNING: Always maintain minimum clearances around vent systems. The minimum clearance to combustibles for horizontal vent pipe is 3 inches at the top and 1 inch at the bottom of the vent system until the flue penetrates the nearest vertical wall.

FOR WALL FIRESTOPS AND VERTICAL RUNS ONLY, maintain a 1 inch minimum clearance from all sides of the vent. Do not pack the open air spaces around the fireplace or flue with insulation or other materials. Any horizontal run must have a 1/4” rise for every one (1) foot of run towards the vent termination. Never install the vent level or downward.

WARNING: Contact your Local Building and Fire Officials about restrictions and in- stallation inspections in your area.

IMPORTANT SAFETY INFORMATION

The termination cap MUST be vented directly to the outside. The termination kit MUST NEVER be connected to a chimney flue(s) servicing a separate solid-fuel burning appliance or any other appliance.

Termination cap MUST NOT be recessed into a wall or siding.

The flexible vent pipe cannot be intermingled with any of the rigid vent pipe section. DO NOT connect two sections of flexible vent pipe together to achieve a longer length without approved connectors.

Horizontal runs must be supported every 3 feet using wall straps. Vertical runs must be sup- ported every 8 feet using wall straps. Slip wall straps loosely on to pipe. Attach straps to framing members using nails or screws. Tighten nut/bolt to secure pipe.

The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service person. Inspect external vent cap on a regular basis to make sure that no debris is interfering with the airflow. Inspect entire venting system to ensure proper function.

Vent connections should overlap a minimum of 1” for proper sealing.

Always stretch and secure venting with metal strapping secured with nails (nails and strap- ping not supplied) to ensure that the horizontal runs remain true.

Page 9

Image 12
Contents DV1000 ZERO CLEARANCE DIRECT VENT GAS FIREPLACEApproved By Page TABLE OF CONTENTS Page INTRODUCTION AND SAFETY FOR INSTALLATION AND OPERATIONDV1000 FIREBOX COVER DOOR REMOVAL INSTRUCTIONS 1. TOP LOUVER ASSEMBLY 2. BOTTOM LOUVER ASSEMBLYLOUVER ASSEMBLY VER ASSEMBLY CLIP TO SECURE TO STOVE BODYDV1000 SPECIFICATIONS 38-1/8” 36” 33-1/2”16-15/16” 2-1/2” 6” TOP STANDOFFS SIDE STANDOFFS 27-1/8” 13-9/16”MINIMUM FRAMING DIMENSIONS 40-1/8”2-1/2” 36-1/8VENT TERMINAL CLEARANCES PageDETERMINING THE LOCATION FOR DV1000 INSTALLATION INSTRUCTIONS DV1000 DIRECT VENT TERMINATIONPRE-INSTALLATIONINFORMATION PIPE INSTALLATIONOUTER 7” VENT PIPE INNER 4” FLUE PIPE CORNER TERMINATION WITH OPTIONAL REAR VENT FIGURE 8/ OPTIONAL REAR VENT TER9-1/2”WALL MINATION EXAMPLEMINIMUM INSTALLATION MAXIMUM INSTALLATIONINSTALLATIONS VERTICAL TERMINATION CAP ASSEMBLYDV1000 STANDARD VERTICAL CHASE TERMINATION 30FT MAXREMOVABLE INNER BOTTOM PAN ASSEMBLY INSTALLING GAS PIPING TO APPLIANCE Installation Items NeededGAS SUPPLY CONNECTION CHECK GAS TYPEPressure Testing Gas Supply Piping System Test Pressures In Excess of 1/2 PSIG 3.5 kPaDV1000 LOG PLACEMENT ance of the heaterWARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury FOR YOUR SAFETY READ BEFORE LIGHTING WHAT TO DO IF YOU SMELL GASLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE WIRING DIAGRAM SERVICING REPAIR PARTSCLEANING AND MAINTENANCE BURNER PAN ASSEMBLY VENTURA ASSEMBLY Air Shutter Slot OpeningLOGS EMBERSTROUBLESHOOTING OBSERVED PROBLEMPOSSIBLE CAUSE REMEDYDiagram, page Burner does not light after pilot is litTROUBLESHOOTING Maintenance, pageContinued Gas leak. See Warning statementREPLACEMENT PARTS SERVICINGKEY# PART DESCRIPTIONON/OFF/MANUAL PageADDITIONAL REPLACEMENT PARTS WARRANTY WARRANTYPROCEDURE CONDITIONS AND EXCLUSIONSOTHER RIGHTS Page