New Buck Corporation DV1000 manual Troubleshooting, Observed Problem, Possible Cause, Remedy

Page 30
TROUBLESHOOTING

TROUBLESHOOTING

Note: All troubleshooting items are listed in order of operation.

 

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

 

 

 

 

 

When ignitor button is pressed, there is no

1.

Ignitor electrode not connected to

1.

Reconnect ignitor cable

 

 

spark at pilot

 

ignitor cable

 

 

 

 

 

2.

Ignitor cable pinched or wet

2.

Free ignitor cable if pinched by any

 

 

 

 

 

 

metal or tubing. Keep ignitor cable

 

 

 

3.

Piezo ignitor nut is loose

 

dry

 

 

 

3.

Tighten nut holding piezo ignitor.

 

 

 

 

 

 

Nut is located behind the mounting

 

 

 

4.

Broken ignitor cable

 

bracket

 

 

 

4.

Replace ignitor cable

 

 

 

5.

Bad piezo ignitor

5.

Replace piezo ignitor

 

 

 

6.

Ignitor electrode broken

6.

Replace pilot assembly

 

 

 

7.

Ignitor electrode positioned wrong

7.

Replace pilot assembly

 

 

 

 

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or equipment

1.

Turn on gas supply or open

 

 

spark at pilot but no ignition

 

shutoff valve closed

 

equipment shutoff valve

 

 

 

2.

Gas control knob not in PILOT

2.

Turn gas control knob to PILOT

 

 

 

 

position

 

position

 

 

 

3.

Gas control knob not pressed in

3.

Press in gas control knob while in

 

 

 

 

while in PILOT position

 

PILOT position

 

 

 

4.

Air in gas lines when installed

4.

Continue holding down gas control

 

 

 

 

 

 

knob. Repeat igniting operation until

 

 

 

5.

Depleted gas supply (propane/LP

 

air is removed

 

 

 

5.

Contact local propane/LP gas

 

 

 

 

models only)

 

company

 

 

 

6.

Pilot is clogged

6.

Clean pilot (see Cleaning and

 

 

 

 

 

 

Maintenance, page 25 or replace

 

 

 

7.

Gas regulator setting is not correct

 

pilot assembly

 

 

 

7.

Replace gas control

 

 

 

 

 

 

 

 

 

Pilot lights but flame goes out when

1.

Gas control knob not fully pressed in

1.

Press in gas control knob fully

 

 

control knob is released

2.

Gas control knob not pressed in long

2.

After pilot lights, keep gas control

 

 

 

 

enough

 

knob pressed in 30 seconds

 

 

 

3.

Equipment shutoff valve not fully

3.

Fully open equipment shutoff valve

 

 

 

 

open

 

 

 

 

 

4.

Pilot flame not touching

4.

A) Contact local gas company

 

 

 

 

thermocouple, which allows

 

 

 

 

 

 

thermocouple to cool, causing pilot

 

 

 

 

 

 

flame to go out. This problem could

 

 

 

 

 

 

be caused by one or both of the

 

B) Clean pilot (see Cleaning and

 

 

 

 

following:

 

Maintenance, page 25) or replace

 

 

 

 

A. Low gas pressure

 

pilot assembly

 

 

 

 

B. Dirty or partially clogged pilot

 

 

 

 

 

5.

Thermocouple connection loose at

5.

Hand tighten until snug, then tighten

 

 

 

 

control valve

 

1/4 turn more

 

 

 

6.

Thermocouple damaged

6.

Replace thermocouple

 

 

 

7.

Control valve damaged

7.

Replace control valve

 

 

 

 

24

 

 

 

Page 27

Image 30
Contents DV1000 ZERO CLEARANCE DIRECT VENT GAS FIREPLACEApproved By Page TABLE OF CONTENTS Page INTRODUCTION AND SAFETY FOR INSTALLATION AND OPERATIONDV1000 FIREBOX COVER DOOR REMOVAL INSTRUCTIONS LOUVER ASSEMBLY 1. TOP LOUVER ASSEMBLY2. BOTTOM LOUVER ASSEMBLY VER ASSEMBLY CLIP TO SECURE TO STOVE BODY16-15/16” 2-1/2” 6” DV1000 SPECIFICATIONS38-1/8” 36” 33-1/2” TOP STANDOFFS SIDE STANDOFFS 27-1/8” 13-9/16”2-1/2” MINIMUM FRAMING DIMENSIONS40-1/8” 36-1/8VENT TERMINAL CLEARANCES PageDETERMINING THE LOCATION FOR DV1000 INSTALLATION INSTRUCTIONS DV1000 DIRECT VENT TERMINATIONPRE-INSTALLATIONINFORMATION PIPE INSTALLATIONOUTER 7” VENT PIPE INNER 4” FLUE PIPE 9-1/2”WALL CORNER TERMINATION WITH OPTIONAL REAR VENTFIGURE 8/ OPTIONAL REAR VENT TER MINATION EXAMPLEMINIMUM INSTALLATION MAXIMUM INSTALLATIONDV1000 STANDARD VERTICAL CHASE TERMINATION INSTALLATIONSVERTICAL TERMINATION CAP ASSEMBLY 30FT MAXREMOVABLE INNER BOTTOM PAN ASSEMBLY GAS SUPPLY CONNECTION INSTALLING GAS PIPING TO APPLIANCEInstallation Items Needed CHECK GAS TYPEPressure Testing Gas Supply Piping System Test Pressures In Excess of 1/2 PSIG 3.5 kPaDV1000 LOG PLACEMENT ance of the heaterWARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury FOR YOUR SAFETY READ BEFORE LIGHTING WHAT TO DO IF YOU SMELL GASLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE WIRING DIAGRAM SERVICING REPAIR PARTSCLEANING AND MAINTENANCE LOGS BURNER PAN ASSEMBLYVENTURA ASSEMBLY Air Shutter Slot Opening EMBERSPOSSIBLE CAUSE TROUBLESHOOTINGOBSERVED PROBLEM REMEDYDiagram, page Burner does not light after pilot is litContinued TROUBLESHOOTINGMaintenance, page Gas leak. See Warning statementKEY# REPLACEMENT PARTSSERVICING PART DESCRIPTIONON/OFF/MANUAL PageADDITIONAL REPLACEMENT PARTS PROCEDURE WARRANTYWARRANTY CONDITIONS AND EXCLUSIONSOTHER RIGHTS Page