New Buck Corporation DV1000 manual Pressure Testing Gas Supply Piping System

Page 20
Pressure Testing Gas Supply Piping System

Pressure Testing Gas Supply Piping System

Note: The appliance and its appliance main valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi. (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi. (3.5 kPa).

Test Pressures In Excess of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping systems. Pressures in excess of 1/2 psig (3.5 kPa) will damage burner system gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas burner system or opening main gas valve located on or near gas meter for natural gas burner system, or using compressed air.

4.Check all joints of gas supply piping system. Apply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect burner system and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve.

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas burner system or opening main gas valve located on or near gas meter for natural gas burner system, or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34, page 17 for propane/LP or Figure 35, page 17 for natural). Apply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.

 

 

CSA/AGA Design-

 

 

Certified Equipment

 

 

Shutoff Valve With

Union

 

1/8" NPT Tap

 

 

 

 

 

 

 

 

 

Gas Control

 

LP

NATURAL

 

PRESSURE:

10.0" W.C.

3.5" W.C.

 

*MIN. INLET

11.0" W.C.

4" W.C.

 

MAX. INLET

13.0" W.C.

10.5" W.C.

OPEN

 

 

EQUIPMENT

 

 

SHUTOFF

 

 

VALVE

 

 

CLOSED

FIGURE 13

EQUIPMENT SHUTOFF VALVE

 

Page 17

Image 20
Contents Approved By DV1000ZERO CLEARANCE DIRECT VENT GAS FIREPLACE Page TABLE OF CONTENTS Page INTRODUCTION AND SAFETY FOR INSTALLATION AND OPERATIONDV1000 FIREBOX COVER DOOR REMOVAL INSTRUCTIONS 1. TOP LOUVER ASSEMBLY 2. BOTTOM LOUVER ASSEMBLYLOUVER ASSEMBLY VER ASSEMBLY CLIP TO SECURE TO STOVE BODYDV1000 SPECIFICATIONS 38-1/8” 36” 33-1/2”16-15/16” 2-1/2” 6” TOP STANDOFFS SIDE STANDOFFS 27-1/8” 13-9/16”MINIMUM FRAMING DIMENSIONS 40-1/8”2-1/2” 36-1/8VENT TERMINAL CLEARANCES PageDETERMINING THE LOCATION FOR DV1000 INSTALLATION INSTRUCTIONS DV1000 DIRECT VENT TERMINATIONPRE-INSTALLATIONINFORMATION PIPE INSTALLATIONOUTER 7” VENT PIPE INNER 4” FLUE PIPE CORNER TERMINATION WITH OPTIONAL REAR VENT FIGURE 8/ OPTIONAL REAR VENT TER9-1/2”WALL MINATION EXAMPLEMINIMUM INSTALLATION MAXIMUM INSTALLATIONINSTALLATIONS VERTICAL TERMINATION CAP ASSEMBLYDV1000 STANDARD VERTICAL CHASE TERMINATION 30FT MAXREMOVABLE INNER BOTTOM PAN ASSEMBLY INSTALLING GAS PIPING TO APPLIANCE Installation Items NeededGAS SUPPLY CONNECTION CHECK GAS TYPEPressure Testing Gas Supply Piping System Test Pressures In Excess of 1/2 PSIG 3.5 kPaDV1000 LOG PLACEMENT ance of the heaterWARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury FOR YOUR SAFETY READ BEFORE LIGHTING WHAT TO DO IF YOU SMELL GASLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE WIRING DIAGRAM SERVICING REPAIR PARTSCLEANING AND MAINTENANCE BURNER PAN ASSEMBLY VENTURA ASSEMBLY Air Shutter Slot OpeningLOGS EMBERSTROUBLESHOOTING OBSERVED PROBLEMPOSSIBLE CAUSE REMEDYDiagram, page Burner does not light after pilot is litTROUBLESHOOTING Maintenance, pageContinued Gas leak. See Warning statementREPLACEMENT PARTS SERVICINGKEY# PART DESCRIPTIONON/OFF/MANUAL PageADDITIONAL REPLACEMENT PARTS WARRANTY WARRANTYPROCEDURE CONDITIONS AND EXCLUSIONSOTHER RIGHTS Page