8 Installing Vent Pipe and Appliance

A. Vent Limits

The abbreviations listed in this vent table key are used in the vent diagrams.

B. Venting Components

CAUTION! Risk of Cuts/Abrasions/Flying Debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp.

Description

Minimum Vertical Run Length 10 ft.

Maximum Vertical Run Length 50 ft.

Horizontal venting is NOT allowed.

Vertical terminations are measured to top of chimney.

This appliance is listed for use with LINK-DV systems and components only. It is permissible to extend venting above existing chimney (within specified maximum verti- cal limits) using SL-D series or Dura Vent GS series 4 in. x 6-5/8 in. gas direct-vent pipe. Connection is made us- ing DV-46DVA-GK. The vent must be terminated with the cap supplied with the LINK-series vent kit.

WARNING! Risk of Fire/Explosion/Asphyxiation! Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance.

May impair safe operation of this appliance or other appliances connected to the flue.

Vent this appliance directly outside.

Use separate vent system for this appliance.

CAUTION! ALL vent specifications MUST be followed. This product is tested and listed to these specifications. Appliance performance will suffer if specifications are not followed.

The vertical vent termination system installed on this model includes:

Flexible vent pipe for exhaust air (included with vent kit).

One length of 3-inch flexible vent pipe for combustion air (included with vent kit).

One pipe-to-cap adaptor (included with vent kit).

One vertical termination cap (included with vent kit).

C. Connecting Vent Pipe

Reference instructions in the termination kit.

Install the 3-inch flexible vent pipe(s) down through the chimney.

Secure the exhaust flexible vent pipe to the exhaust starting collar on top of the appliance with three screws and seal with stove cement rated for continuous exposure to 1200ºF or higher. See Figure 8.1.

Use 3 screws to attach the section of inlet air vent to the inlet collar on the collar slide plate and seal with stove cement rated for continuous exposure to 1200ºF or higher. See Figure 8.1. NOTE: The collar slide plate may be removed from appliance to aid installation.

TERMINATION

 

CAP

 

ADAPTER

 

INLET

 

COLLAR

 

EXHAUST

 

COLLAR

 

 

INLET AIR STARTING COLLAR

EXHAUST

LOCKING TAB

AIR

 

VENT PIPE

 

V = 10 FT. MINIMUM

 

50 FT. MAXIMUM

 

 

STARTING COLLAR BRACKET

HANDLE

 

 

EXHAUST STARTING COLLAR

INLET AIR

 

VENT PIPE

 

INLET AIR STARTING COLLAR

 

 

NOTE: TO ACHIEVE OPTIMUM PERFOR-

 

MANCE OF INSERT, MINIMIZE OR AVOID

STARTING COLLAR BRACKET

BENDS IN EXHAUST VENT PIPE.

 

EXHAUST STARTING COLLAR

 

Figure 8.1

22

Heat & Glo • Grand-I35, Grand-I35-SP, Supreme-I30, Supreme-I30-SP2206-900 Rev. K • 6/11

Image 22
Contents What to do if you smell gas ModelsDo Discardnot Congratulations Homeowner Reference InformationTable of Contents User GuideLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Operating Instructions User Guide Gas Fireplace SafetyYour Fireplace IPI Battery Tray/Battery Installation Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear Space Nine Hour Safety Shutdown Feature Module ResetBefore Lighting Fireplace Lighting Instructions IPI Final inspection byLighting Instructions Standing Pilot Ignition Do not Connect 110 VAC to the Control ValveFrequently Asked Questions After Appliance is LitMaintenance and Service Logs Maintenance Tasks-Service TechnicianGasket Seal and Glass Assembly Inspection FireboxBurner Ignition and Operation Standing Pilot Flame PatternsGetting Started Typical Appliance SystemTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Minimum Fireplace Opening Fireplace Size RequirementsTOP View Front View Side View Mantel and Wall Projections Side View TOP ViewTermination Locations Vent Termination Minimum ClearancesInstallation Preparation Vent Limits Installing Vent Pipe and ApplianceConnecting Vent Pipe Venting ComponentsStanding Pilot Models Placing, Securing and Leveling the ApplianceIPI Models Masonry Factory Built Installing Adaptor and Termination CapDamper Flashing Kit Optional Gas Pressure Gas InformationFuel Conversion Gas ConnectionIntelliFire Plus Ignition System Wiring Wiring RequirementsStanding Pilot Ignition System Wiring Electrical InformationOptional Wall Switch Rocker Thermostat or Remote ThermocoupleOptional Accessories Requirements FAN BladesFan Wiring with Remote See .H for control module operation instructionsFinishing Clearances to Mantels or other Combustibles above ApplianceAppliance Setup Install the Log Assembly Log Set Assembly LOGS-I35 Models GRAND-I35, GRAND-I35-SPLOG Support Pilot Grate Tines Bracket Grate BAR END of LOG Rests On Flat Spot Flat Spot for LOG Groove Flat Spot for Grate BARLOG #6 LOG #6 Resting on Flat Spots LOG #7 Resting on Flat Spots Log #6LOG Support LOG Rests on Grate Tine  G. Install the Log AssemblySlot Flat Spots Points of LOG Rest on Corner LOG Flush With Pilot BracketFor LOG #5 For LOG #6Air Shutter Setting Air Shutter SettingsSymptom Possible Causes Corrective Action TroubleshootingStanding Pilot Ignition System Troubleshooting Symptom Possible Cause Corrective ActionShorts in the wiring IntelliFire Plus Ignition SystemAppliance Dimension Diagram Reference MaterialsVent Kits Components Direct Vent Flex Liner KitsStocked Service PartsLog Set Assembly At DepotService Parts SUPREME-I30, SUPREME-I30-SP Metal Insert, IPIGRAND-I35 #19 IPI Valve AssemblySUPREME-I30 Service Parts GRAND-I35-SP, SUPREME-I30-SP #19 Standing Pilot Valve AssemblyStanding Pilot Conversion Kits Service Parts ListIPI Conversion Kits Contact Information