11 Gas Information
A. Gas Pressure Requirements | B. Gas Connection |
Pressure requirements for
Two taps are provided on the right hand side of the gas control for a test gauge connection to measure the inlet and outlet pressures.
The fireplace and its individual
If the fireplace must be isolated from the gas supply pip- ing system by closing an individual
WARNING
Fire Risk
Explosion Risk
High pressure will damage valve.
•Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 60 mbar.
•Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 60 mbar.
| ON/OFF/REMOTE |
GAS VALVE | SWITCH |
|
CONTROL | DC ADAPTER | BATTERY |
MODULE | PACK |
Figure 11.1. Valve Components
Note: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality.
Note: Before the first firing of the appliance, the gas supply line should be purged of any trapped air.
Note: Consult local building regulations to properly size the gas supply line leading to the (Rp 1/2 in.)
Incoming gas line should be piped into the valve compart- ment and connected to the ISO
Leak test all gas line points and the gas control valve prior to and after starting the gas appliance.
WARNING
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
•Check all fittings and connections.
•Do not use open flame.
•After the gas line installation is complete, all connections must be tightened and checked for leaks with a
Fittings and connections may have loosened during shipping and handling.
C. Access Through the Valve Assembly
Refer to Section 16.C.
| Natural Gas | Propane | Propane | Butane | Butane | Natural Gas | ||||||
| (G20) | (G31) | (G31) | (G30) | (G30) | (G25) | ||||||
CAT | I2H, I2E, I2E+ | I3P |
| I3P |
| I3B/P |
| I3B/P |
| I2E+ |
| |
Inlet Pressure | 20 mbar | 37 mbar | 50 mbar | 30 mbar | 50 mbar | 25 mbar | ||||||
Burner Pressure | 8.7 mbar | 25 mbar | 25 mbar | 25 mbar | 25 mbar | 8.7 mbar | ||||||
Gas Rate | .405 m3/ | h | .134 m3/ | h | .134 m3/ | h | .111 m3/ | h | .111 m3/ | h | .40 m3/ | h |
Heat Input (Net) | 7.32 kW | 6.74 kW | 6.74 kW | 6.44 kW | 6.44 kW | 7.32 kW | ||||||
|
|
|
|
|
|
| ||||||
Burner Injector | DMS 42 | DMS .057 | DMS .057 | DMS 55 | DMS 55 | DMS 42 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Pilot Injector | 51 |
| 30 |
| 30 |
| 30 |
| 30 |
| 51 |
|
Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum inlet pressure of 37 mbar. For pressures over 37 mbar, an in line pressure regulator must be installed upstream from the gas control valve.
Heat & Glo • | 41 |