Heat & Glo LifeStyle CERONA-36 Gas Information, Fuel Conversions Gas Connection, Gas Pressures

Page 29

9 Gas Information

A. Fuel Conversions

C. Gas Connection

Before making gas connections ensure that appliance be- ing installed is compatible with the available gas type.

Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a qualified technician using Hearth & Home Technologies specified and approved parts.

Note: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI

223.1.Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

B. Gas Pressures

Proper input pressures are required for optimum appli- ance performance. Gas line sizing requirements need to be made following NFPA51.

WARNING

Fire Risk. Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

WARNING

Verify inlet pressures.

• High pressure may cause overfire condition.

• Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Note: A listed (and Commonwealth of Massachusetts ap- proved) 1/2 inch (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

Refer to Reference Section 16 for location of gas line access in appliance.

Note: Gas line may be run from either side of the appliance provided the hole in the outer wrap does NOT exceed 2-1/2 inches in diameter and does not penetrate the firebox.

WARNING

Gas Leak Risk

Support control when attaching pipe to prevent bending gas line.

Note: The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Pressure requirements for appliance are shown in the table below. Minimum pressures must be met when other household gas appliances are operating.

Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 inches

11.0 inches

w.c.

w.c.

 

Maximum inlet gas pressure

14.0 inches

14.0 inches

w.c.

w.c.

 

Manifold pressure

3.5 inches

10.0 inches

w.c.

w.c.

 

Heat & Glo • Cerona-36, Cerona-422106-900 Rev. F • 04/08

29

Image 29 Contents
What to do if you smell gas ModelsModel Number Serial Number Homeowner Reference InformationTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsGetting Started Installation to ensure maximum safety and benefitTools and Supplies Needed Read all of the instructions before starting the instaSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance Chase724 425 406 279 Mantel ProjectionsHearth Extension Hearth Extension DimensionsVent Termination Minimum Clearances Termination LocationsMinimum Clearances for Termination Alcove ApplicationsContinue Adding Vent Components Install Support BracketsTo Install the Heat Shield Vent Table Key Vent Information and DiagramsUse of Elbows Measuring StandardsTwo Elbows Vent DiagramsTop Vent Horizontal Termination One Elbow Top Vent Vertical Termination Straight up Vertical Venting Top Vent Horizontal Termination Three ElbowsV1 = 50 ft. Max .2 m 152 mm 914 mm 305 mm 610 mm 10 ft305 mm 610 mm 914 mm 10 ft Top Vent Horizontal Termination Two ElbowsPipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationVertical Penetration Framing Installing the Ceiling FirestopInstalling Attic Shield Appliance Preparation Removing Non-combustible Facing Mate- rial AssemblyProvided to secure the appliance to the framing members Diagram shows .2 the location of the nailing tabsSecuring and Leveling the Appliance Complete Installation of Non-combustible Facing Material Installing Flue RestrictorsAssembly of Vent Sections Installing Vent PipeAttaching Vent to the Firebox Assembly Assembling Pipe SectionsAssembling DVP-12A Slip Sections Assembling Minimum Installations MI Sections Securing the Vent Sections Disassembly of Vent Sections Vertical Sections Horizontal SectionsInstalling the Horizontal Termination Cap Installing Heat Shield and Horizontal Termination CapHeat Shield Requirements for Horizontal Termination Heat shield DVP-HSM-B must be usedflue of the pipe see Figure Installing Roof Flashing and Vertical Ter- mination Cap18 Assembling the Storm Collar Around the Pipe Assembling and Installing Storm CollarGas Pressures Gas InformationFuel Conversions Gas Connection High Altitude Installations Intellifire Ignition System Wiring Recommendation for WireConnecting to the Appliance Optional Accessories RequirementsProperly grounded Not operate unlessJunction Box Detail Junction Box InstallationStep Finishing Non-combustible Facing Material Facing MaterialFinishing Material Thickness from 3/4 in. to 1-1/4 Finishing Material OptionsFinishing Material Thickness greater than 1-1/4 inch Mounting stone eye brow ATRIMSTONE-36, ATRIMSTONE-4210 Fireplace sitting on combustible surface Clean the Appliance Appliance SetupAccessories Ember PlacementPositioning the Logs Model Cerona-36 Log Assembly LOGS-Cerona36Heat & Glo Cerona-36, Cerona-42 2106-900 Rev. F 04/08 Model Cerona-42 Step Grilles and Trim Glass AssemblyAir Shutter Setting This appliance has an Intellifire ignition system Operating InstructionsBefore Lighting Appliance Final inspection by Lighting Appliance IPI IgnitionAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Sympton Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Symptom Possible Cause Corrective Action Maintaining and Servicing Appliance Maintenance TasksDoors, Surrounds Inspect Maintenance TasksModel Cerona-36 Model Cerona-42 Appliance Dimension DiagramReference Materials DVP vent components Vent Components DiagramsDVP-TRAP COOL-ADD Not for use with these models Part number list on following Log Set AssemblyService Parts At Depot Service Parts ListStocked IPI Valve AssemblyCERONA-42 Fan Kit GFK-160A Junction Box 4021-013 Box Paint Kit CERONA-42IPI Valve Assembly Limited Lifetime Warranty Heat & GLO GAS Appliance Products Limited Lifetime WarrantyContact Information
Related manuals
Manual 62 pages 22.54 Kb Manual 1 pages 2.44 Kb