Vermont Casting DTV38s2 installation instructions Sidewall Installation, Step

Page 19

When the vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must be flush with the siding.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length of vent pipe from the flue collar of the fire- place to the face of the outer wall.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

 

20’ (6m)

 

 

 

Unitized Elbow

 

 

 

(SK890)

 

 

 

 

 

Pipe

 

 

 

Straps

(4.3m)

 

 

Every 3’

Pipe Straps

(914mm)

 

Every 3’

 

 

14’

 

 

(914mm)

Firestop/Zero

 

 

Minimum 2’

Clearance Sleeve

 

 

 

 

(610mm) Section

 

NOTE: Apply high temperature sealant or UL approved high temperature metal adhesive tape as directed on Page

16.

FP1453

Fig. 15 Support straps for horizontal runs.

The maximum number of 90° elbows per side wall installation is three (3), but must not have two (2) consecutive elbows in the horizontal plane.

A minimum of 2’ (610 mm) vertical section off the top of the unit is required, an elbow and a 1’ (305 mm) maximum horizontal run to get through a wall. (Fig. 16)

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run. (Fig. 16)

3'

(914mm)

Chateau™ Direct Vent Gas Fireplace

 

A

10'

B

 

(3m)

 

 

A + B = 17' (5.2m)

FP1238b

Fig. 17 Maximum vent run with elbows.

For each 90° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 36” (914 mm).

The maximum number of elbow degrees in a system is 270°. (Fig. 17)

Example:

 

 

 

 

 

 

 

 

 

 

Elbow 1

=

 

90°

 

 

 

 

 

Elbow 2

=

 

45°

4

 

Elbow 3

=

 

45°

 

 

 

 

 

Elbow 4

=

 

90°

 

 

 

 

Total angular variation =

270°

 

 

 

 

 

 

 

 

1

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1455

Fig. 18 Maximum number of elbow degrees.

2'

(610mm)

C Wall Opening

L

6'9���"

Sidewall Installation

STEP 1

Locate vent opening on the wall. It may be necessary

(2080mm)

FP1454

Fig. 16 Minimum vertical run / maximum horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (45 cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 19)

For combustible walls first frame in opening.

Combustible Walls: Cut a 16¹⁄”H x 16¹⁄” W (413 x 413 mm) hole through the exterior wall and frame as shown.

Noncombustible Walls: Hole opening must be 11¹⁄” (286 mm) in diameter.

20011957

19

Image 19
Contents What to do if YOU Smell GAS INSTALLER/CONSUMER Safety InformationTable of Contents Please Review the Following Carefully Installation & Operating InstructionsCertified To Ansi Z21.50b-2005 / CSA 2.22b-2005 Vented Gas FireplaceClear of ALL Obstructions Requirements for the Commonwealth of MassachusettsGas Equipment Venting System not Provided Standard Framing Locating Your FireplaceMantels Clearance to CombustiblesFraming and Finishing HearthFinal Finishing High Elevations Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresControl System Control System InstallationInside view of wireless wall switch Special Feature for Cold ClimatesLCD Liquid Crystal Display Hand-Held Remote Control Transmitter Operating InstructionsKey Settings IntroductionThermostat Function Manual FunctionCP Childproof Feature Continuous Pilot FeatureSetting LOCK-OUT CP Operational Notes Thermostatic Updating FeatureLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Vertical Termination Horizontal TerminationSidewall Applications Step Sidewall InstallationZero clearance sleeve is only required for combustible walls Always install horizontal venting on a level planeHorizontal length requirement Sidewall Installation with Stationary Glass Facing OutsideInstalling the 38S2VDK Door Installation ProcedureTypical Applications Flue Restrictor Plate InstallationRestrictor Plate Installation Flue Restrictor Plate GuideFlue restrictor plate use in straight up installation + 2 + 3 + 4 = Vertical Through-the-Roof InstallationMin Component Description Model Number Chimney ComponentsClean the glass after the first two weeks of operation Glass Frame Assembly RemovalGlass Cleaning Ceramic Refractory InstallationDVT38Sw log identification Log, Lava Rock and Ember PlacementLog Pilot Plumbing F50 Overlay is very fragile Log Right Flame Characteristics Trim Installation Lighting Instructions Lighting & Operating InstructionsTurning Off the Gas to the Appliance American Flame Gas Control System TroubleshootingOperation Troubleshooting American Flame Gas Control System What to Check American Flame Gas Control System Error CodesConversion Procedure Conversion PrecautionsFuel Conversion Instructions Remove pilot orifice Conversion to LP Pilot Flame AdjustmentDVT38S2 Injector Orifice Size Matrix Valve Minimum Rate ScrewCleaning the Control System MaintenanceBurner and Burner Compartment DVT38S2 Units GFYW5Q0 DVT38S2 DVT38S2Fuel Conversion Kits Back-up Battery Kit AccessoriesWall Mountable Wireless Remote Transmitter Product Covered by this Warranty Limited Lifetime WarrantyModel EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings