Vermont Casting DTV38s2 Requirements for the Commonwealth of Massachusetts

Page 4

Chateau™ Direct Vent Gas Fireplace

Installation & Operating Instructions

Requirements for the Commonwealth of Massachusetts

All gas fitting and installation of this heater shall only be done by a licensed gas fitter or licensed plumber.

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW, KEEP

CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

4

20011957

Image 4
Contents INSTALLER/CONSUMER Safety Information What to do if YOU Smell GASTable of Contents Installation & Operating Instructions Certified ToAnsi Z21.50b-2005 / CSA 2.22b-2005 Vented Gas Fireplace Please Review the Following CarefullyClear of ALL Obstructions Requirements for the Commonwealth of MassachusettsGas Equipment Venting System not Provided Locating Your Fireplace Standard FramingClearance to Combustibles MantelsFraming and Finishing HearthFinal Finishing Gas Line Installation Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsControl System Installation Control SystemSpecial Feature for Cold Climates Inside view of wireless wall switchHand-Held Remote Control Transmitter Operating Instructions Key SettingsIntroduction LCD Liquid Crystal DisplayManual Function Thermostat FunctionCP Childproof Feature Continuous Pilot FeatureSetting LOCK-OUT CP Thermostatic Updating Feature Operational NotesGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationUSA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Vertical Termination Horizontal TerminationSidewall Applications Sidewall Installation StepAlways install horizontal venting on a level plane Zero clearance sleeve is only required for combustible wallsSidewall Installation with Stationary Glass Facing Outside Horizontal length requirementInstallation Procedure Installing the 38S2VDK DoorFlue Restrictor Plate Installation Restrictor Plate InstallationFlue Restrictor Plate Guide Typical ApplicationsFlue restrictor plate use in straight up installation Vertical Through-the-Roof Installation + 2 + 3 + 4 =Min Chimney Components Component Description Model NumberGlass Frame Assembly Removal Glass CleaningCeramic Refractory Installation Clean the glass after the first two weeks of operationLog, Lava Rock and Ember Placement DVT38Sw log identificationLog Pilot Plumbing F50 Overlay is very fragile Log Right Flame Characteristics Trim Installation Lighting Instructions Lighting & Operating InstructionsTurning Off the Gas to the Appliance American Flame Gas Control System TroubleshootingOperation Troubleshooting American Flame Gas Control System American Flame Gas Control System Error Codes What to CheckConversion Procedure Conversion PrecautionsFuel Conversion Instructions Remove pilot orifice Pilot Flame Adjustment DVT38S2 Injector Orifice Size MatrixValve Minimum Rate Screw Conversion to LPCleaning the Control System MaintenanceBurner and Burner Compartment DVT38S2 Units GFYW5Q0 DVT38S2 DVT38S2Fuel Conversion Kits Back-up Battery Kit AccessoriesWall Mountable Wireless Remote Transmitter Limited Lifetime Warranty Product Covered by this WarrantyEfficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %