Vermont Casting DTV38s2 Flue restrictor plate use in straight up installation

Page 24

Chateau™ Direct Vent Gas Fireplace

plicable. When using the unitized 30°, 45° or 90° elbows, apply 1/4” bead of high temperature, 550°F or higher, sealant (milpack or stove cement) to the joint of the inner pipe (flue pipe) and the straight section as it is impossi- ble to be taped. The outer pipe must be taped with 315°F high temperature metal adhesive tape for proper sealing.

For vertically venting either propane or natural gas units, with vertical vent heights of 12’ (3.7 m) or greater, (measured from the top of the flue collar) the flue restrictor plate as supplied with this unit should be used. (Fig. 30) Refer to Figure 29 for flue restrictor plate installation.

X

FP1461

Fig. 30 Flue restrictor plate use in straight up installation.

For LP gas venting straight vertical with 20’ (6 m) or more, adjust the primary air to the burner housing as well as the fresh air to the unit by doing the following:

1.Remove glass, logs, glowing embers (if installed).

2.Remove andirons, fettles and burner housing.

3.Remove the two (2) screws securing the deflector and the rectangular restrictor plate in place. (Fig. 31) Turn the restrictor plate around so the body of the plate will extend down over the air opening.

Rectangular Restrictor Plate

Deflector

Screws

FP1615

Fig. 31 Turn rectangular restrictor plate over to partially cover opening.

24

4.Turn the burner housing upside down. Remove the two (2) screws securing the shutter plate to the bottom of the burner. Turn the shutter plate around so the bottom opening is 1” (25 mm). Replace the screws removed earlier. (Fig. 32)

Shutter

Remove Screws

 

Plate

 

 

Shutter Plate

1“ (25 mm)

FP1616a

Fig. 32 Turn shutter plate over to cover opening.

5.Reinstall burner housing, fettle, andirons, logs and glowing embers in reverse order. (Refer to Page 29 for log installation)

For vertical venting configurations that include a minimum vertical rise of 12’ (3.7 m) and a maximum horizontal offset of 10’ (3 m) the 4¹⁄₂” flue restrictor plate supplied with this unit should be used on LP unit only. (Fig. 33) Refer to Figure 28 for flue restrictor plate installation.

 

FP1462

Fig. 33

Restrictor plate use with horizontal offset.

 

20011957

Image 24
Contents INSTALLER/CONSUMER Safety Information What to do if YOU Smell GASTable of Contents Installation & Operating Instructions Certified ToAnsi Z21.50b-2005 / CSA 2.22b-2005 Vented Gas Fireplace Please Review the Following CarefullyRequirements for the Commonwealth of Massachusetts Clear of ALL ObstructionsGas Equipment Venting System not Provided Locating Your Fireplace Standard FramingClearance to Combustibles MantelsHearth Framing and FinishingFinal Finishing Gas Line Installation Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsControl System Installation Control SystemSpecial Feature for Cold Climates Inside view of wireless wall switchHand-Held Remote Control Transmitter Operating Instructions Key SettingsIntroduction LCD Liquid Crystal DisplayManual Function Thermostat FunctionContinuous Pilot Feature CP Childproof FeatureSetting LOCK-OUT CP Thermostatic Updating Feature Operational NotesGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationCanadian Installations USA InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Horizontal Termination Vertical TerminationSidewall Applications Sidewall Installation StepAlways install horizontal venting on a level plane Zero clearance sleeve is only required for combustible wallsSidewall Installation with Stationary Glass Facing Outside Horizontal length requirementInstallation Procedure Installing the 38S2VDK DoorFlue Restrictor Plate Installation Restrictor Plate InstallationFlue Restrictor Plate Guide Typical ApplicationsFlue restrictor plate use in straight up installation Vertical Through-the-Roof Installation + 2 + 3 + 4 =Min Chimney Components Component Description Model NumberGlass Frame Assembly Removal Glass CleaningCeramic Refractory Installation Clean the glass after the first two weeks of operationLog, Lava Rock and Ember Placement DVT38Sw log identificationLog Pilot Plumbing F50 Overlay is very fragile Log Right Flame Characteristics Trim Installation Lighting & Operating Instructions Lighting InstructionsTurning Off the Gas to the Appliance Troubleshooting American Flame Gas Control SystemOperation Troubleshooting American Flame Gas Control System American Flame Gas Control System Error Codes What to CheckConversion Precautions Conversion ProcedureFuel Conversion Instructions Remove pilot orifice Pilot Flame Adjustment DVT38S2 Injector Orifice Size MatrixValve Minimum Rate Screw Conversion to LPMaintenance Cleaning the Control SystemBurner and Burner Compartment DVT38S2 Units GFYW5Q0 DVT38S2 DVT38S2Fuel Conversion Kits Accessories Back-up Battery KitWall Mountable Wireless Remote Transmitter Limited Lifetime Warranty Product Covered by this WarrantyEfficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %