Vermont Casting DTV38s2 Maintenance, Cleaning the Control System, Burner and Burner Compartment

Page 42

Chateau™ Direct Vent Gas Fireplace

Maintenance

Burner and Burner Compartment

It is important to keep the burner and the burner compartment clean. At least once per year the logs and lava rock/ember material should be removed and the burner compartment vacuumed and wiped out. Remove and refit the logs as per the instructions in this manual.

Always handle the logs with care as they are fragile and may also be hot if the fireplace has been in use.

Cleaning the Control System

The burner and control system consist of:

burner tubes gas orifice

pilot assembly gas valve

Most of these components may require only an occasional checkup and cleaning and some may require adjustment. If repair is necessary, it should be performed by a qualified technician.

1.Turn off main gas shut-off valve.

2.Allow fireplace to cool if it has been operating.

3.Remove window frame assembly. (Refer to Window Frame Assembly Removal section.)

4.Remove logs.

5.Vacuum burner compartment especially around orifice primary air openings.

6.Visually inspect pilot. Brush or blow away any dust or lint accumulation.

7.Reinstall logs.

8.Ignite pilot - Refer to Lighting Instructions.

9.Reinstall window frame assembly.

To obtain proper operation, it is imperative that the pilot and burner’s flame characteristics are steady, not lifting or floating.

Typically, the top 3/8” or 1/2” of the pilot flame sensor should be engulfed in the pilot flame. (Page 38, Fig. 52)

To adjust pilot burner:

1.Locate pilot adjustment screw on the valve next to the black plastic cap. (Refer to Page 35)

2.Adjust pilot screw to provide proper sized flame. Only a small adjustment should be needed.

NOTE: Do not rotate screw excessively. Do not adjust any other screws on the valve.

42

20011957

Image 42
Contents INSTALLER/CONSUMER Safety Information What to do if YOU Smell GASTable of Contents Ansi Z21.50b-2005 / CSA 2.22b-2005 Vented Gas Fireplace Installation & Operating InstructionsCertified To Please Review the Following CarefullyRequirements for the Commonwealth of Massachusetts Clear of ALL ObstructionsGas Equipment Venting System not Provided Locating Your Fireplace Standard FramingClearance to Combustibles MantelsHearth Framing and FinishingFinal Finishing Gas Inlet and Manifold Pressures Gas Line InstallationGas Specifications High ElevationsControl System Installation Control SystemSpecial Feature for Cold Climates Inside view of wireless wall switchIntroduction Hand-Held Remote Control Transmitter Operating InstructionsKey Settings LCD Liquid Crystal DisplayManual Function Thermostat FunctionContinuous Pilot Feature CP Childproof FeatureSetting LOCK-OUT CP Thermostatic Updating Feature Operational NotesGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationCanadian Installations USA InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Horizontal Termination Vertical TerminationSidewall Applications Sidewall Installation StepAlways install horizontal venting on a level plane Zero clearance sleeve is only required for combustible wallsSidewall Installation with Stationary Glass Facing Outside Horizontal length requirementInstallation Procedure Installing the 38S2VDK DoorFlue Restrictor Plate Guide Flue Restrictor Plate InstallationRestrictor Plate Installation Typical ApplicationsFlue restrictor plate use in straight up installation Vertical Through-the-Roof Installation + 2 + 3 + 4 =Min Chimney Components Component Description Model NumberCeramic Refractory Installation Glass Frame Assembly RemovalGlass Cleaning Clean the glass after the first two weeks of operationLog, Lava Rock and Ember Placement DVT38Sw log identificationLog Pilot Plumbing F50 Overlay is very fragile Log Right Flame Characteristics Trim Installation Lighting & Operating Instructions Lighting InstructionsTurning Off the Gas to the Appliance Troubleshooting American Flame Gas Control SystemOperation Troubleshooting American Flame Gas Control System American Flame Gas Control System Error Codes What to CheckConversion Precautions Conversion ProcedureFuel Conversion Instructions Remove pilot orifice Valve Minimum Rate Screw Pilot Flame AdjustmentDVT38S2 Injector Orifice Size Matrix Conversion to LPMaintenance Cleaning the Control SystemBurner and Burner Compartment DVT38S2 Units GFYW5Q0 DVT38S2 DVT38S2Fuel Conversion Kits Accessories Back-up Battery KitWall Mountable Wireless Remote Transmitter Limited Lifetime Warranty Product Covered by this WarrantyEfficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %