CarAlarms.com P90-NG1 manual Vertical Terminations, This allows for small adjustments

Page 22
2)
1) Maintain the 1 - 1/2" clearances (air spaces) to combustibleswhenpassing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation. Check the "Rigid Pipe Venting Systems" & "Rigid Pipe Venting Arrangements" sections for themaximumverticalriseof the venting system and the maximum horizontal offset limitations.
Note:
Apply sealant "Mill-
Pac" to inner pipe
andhightemperature
silicone sealant to
outer pipe on every twist-lock joint.
3) A Firestop spacer must be installed in the fl oor or ceiling of every level. To install the Firestop spacer in a fl at ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the fi restop.
Diagram 3
Set the gas appliance in its desired location. Dropaplumbbobdownfromtheceilingtothe position of the appliance fl ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where
the vent will penetrate the
roof.Determine if ceiling joists, roof rafters or other framing will obstruct the ventingsystem. You may wish to relocate the
appliance or to
offset,asshown
in Diagram 2 to avoid cutting
load bearing Diagram 2 members.
Diagram 1

INSTALLATION

Diagram 5

The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

VERTICAL

TERMINATIONS

4)Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.

5)Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles of 1-1/2". Slip the fl ashing under the shingles (shingles should overlap half the fl ashing) as per Diagram 4.

Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.

7)Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble (Part # 620-926) over the vent pipe.

8)Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 6.

Diagram 6

9) Install wall thimble in the center of the 10" square and attach with wood screws (Diagram 7).

Diagram 7

Diagram 4: The upper half of the fl ashing is installed under the roofi ng material and not nailed down until the chimney is installed.

This allows for small adjustments.

6)Continue to assemble pipe lengths.

Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet, to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (Diagram 2).

Galvanizedpipeisdesirableabovetheroofline duetoitshighercorrosionresistance.Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in Diagram 5 or local codes. Note that for steep roof pitches,

Diagram 5

Roof Pitch

Minimum Vent Height

 

Feet

 

Meters

 

 

fl at to 7/12

2

 

0.61

over 7/12 to 8/12

2

 

0.61

over 8/12 to 9/12

2

 

0.61

over 9/12 to 10/12

2.5

 

0.76

over 10/12 to 11/12

3.25

 

0.99

over 11/12 to 12/12

4

 

1.22

over 12/12 to 14/12

5

 

1.52

over 14/12 to 16/12

6

 

1.83

over 16/12 to 18/12

7

 

2.13

over 18/12 to 20/12

7.5

 

2.29

over 20/12 to 21/12

8

 

2.44

 

 

 

 

22

Excalibur® P90 Zero Clearance Direct Vent Gas Fireplace

Image 22
Contents P90 Zero Clearance Direct Vent Gas Fireplace 07/17/06Information for MOBILE/MANUFACTURED Homes After First Sale To the New OwnerTable of Contents Safety Label Copy of Safety Decal for P90Requirements For the State of Massachusetts onlyInstallation Checklist InstallationGeneral Safety Information Important Message Save These InstructionsHeatwave Locating Your GAS FireplaceManufactured Mobile Home Additional Requirements Optional Heat Release KITFraming Finishing Framing DimensionsCombustible Mantels Unit Base STAND-OFFSFacing Over 1 25mm Thick Facing RequirementFloor Mounted Fireplaces Raised Fireplaces Venting Introduction Unit Assembly Prior to InstallationTop Standoff Assembly Side Nailing StripsVenting FPI Direct Vent System Flex Horizontal Terminations OnlyExterior Vent Termination Locations Rigid Pipe Venting Components List SV4LB6Horizontal Rigid Pipe Venting SystemsAlternate CapsHorizontal & Vertical Terminations for 5 x 8 Venting Rigid Pipe Venting Arrangements Horizontal Terminations 8 outer diameterRigid Pipe Venting Arrangements Vertical Terminations Installation Option + H1 Horizontal Venting with Two 2 90o ElbowsHorizontal Venting with Three 3 90o Elbows Option + V1 H + H1Vertical Venting with Three 3 90o Elbows Vertical Venting with Two 2 90o ElbowsOption Diagram Below Grade InstallationHorizontal Terminations This allows for small adjustments Vertical TerminationsOffset Chart Installation ProceduresFor FPI Direct Vent System Flex GAS Pipe Pressure Testing Pilot AdjustmentGAS Line Installation High ElevationConversion KIT #791-969 from NG to LP LPG Conversion Kit Contains Qty DescriptionInstallation of the DC Sparker for the H35-1 Units Only Installation of the DC Sparker For the P90 Units Only Ground Wire from Kit 2nd Grate Tab 02-75 02-54 02-52 02-50 02-53 02-51Bracket 02-53Front Brackets 02-5302-5102-50 02-53 Place embers in these 3 locations On the burner trayOptional Screen Door Glass Door InstallationArch Surround Screw BracketAccent KIT Installation Double & Single Door OptionThermostat Wire Table Remote ControlWall Switch Wall ThermostatWiring Diagrams Do not cut the ground terminal off under any circumstancesFor Propane Units and Units Equipped with DC Spark Boxes Operating Instructions Copy of the Lighting Plate Instructions Normal Operating Sounds of GAS AppliancesMaintenance Shut the power off FAN MaintenanceTo Install the Fan To Remove the FanHint Installing ValveRemoving Valve ImpossibleP90 Main Assembly Parts ListDescription Heat Wave Duct KIT P90 Burner Assembly & LOG SET P90 Flush Front Accessories DescriptionExcalibur P90 Zero Clearance Direct Vent Gas Fireplace Excalibur P90 Zero Clearance Direct Vent Gas Fireplace Warranty Warranty Limited LifetimeInstaller Please complete the following information

P90-NG1 specifications

CarAlarms.com P90-NG1 is a cutting-edge vehicle security system designed to provide maximum protection against theft and unauthorized access. This advanced system combines innovative technology with user-friendly features to ensure that car owners can safeguard their vehicles effectively.

One of the standout features of the P90-NG1 is its two-way communication system. This allows users to receive real-time alerts and notifications directly on their key fob whenever the system detects any suspicious activity. The LCD display on the key fob provides clear information, including the vehicle's status, which enhances the overall user experience. This feature ensures that users are always informed about their vehicle’s security status, whether they are close by or a significant distance away.

The P90-NG1 also employs a state-of-the-art shock sensor, which detects impacts on the vehicle's body. This allows the system to respond swiftly to attempted break-ins or vandalism, triggering an audible alarm to deter potential thieves. The adjustable sensitivity of the shock sensor can be customized to suit different environments, ensuring that users can find an optimal balance between security and everyday usability.

Another notable characteristic of the P90-NG1 is its remote start capability. This feature enables users to start their vehicle from afar, adding convenience, especially in harsh weather conditions. Paired with the optional smartphone app, users can control their vehicle’s security functions from their mobile devices, providing added flexibility and peace of mind.

The installation process of the P90-NG1 is designed to be straightforward and efficient, making it suitable for a wide range of vehicles. The system is compatible with various vehicle models and can be integrated seamlessly with existing systems, providing enhanced functionality without compromising factory features.

In conclusion, CarAlarms.com P90-NG1 stands out in the vehicle security market due to its robust features, advanced technology, and user-centric design. With its reliable two-way communication, effective shock sensor, and convenient remote start capability, it offers vehicle owners a comprehensive solution to protect their assets while ensuring ease of use. This makes the P90-NG1 an ideal choice for those looking to enhance the security of their vehicles.