CarAlarms.com P90-NG1 manual Pilot Adjustment, High Elevation, GAS Line Installation

Page 24

INSTALLATION

P90-NG1 System Data

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #34

Max. Input Rating

35,000 Btu/h

Min. Input Rating

18,200 Btu/h

 

 

Supply Pressure

min.5.0" w.c.

 

 

Manifold Pressure

 

(High)

3.8"+/- 0.2"w.c.

P90-LP1 System Data

For 0 to 2000 feet altitude

Burner Inlet Orifice Sizes: #51

Max. Input Rating

35,000 Btu/h

Min. Input Rating

17,950 Btu/h

High Altitude: For 2000 to 4500 feet alti- tude

Burner Inlet Orifice Sizes: #52

Max. Input Rating

31,000 Btu/h

Min. Input Rating

15,500 Btu/h

Supply Pressure

min.12.0" w.c.

Manifold Pressure

(High)

11"+/- 0.2" w.c.

 

 

Electrical: 120 V

A.C. System.

When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.

Important:Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

PILOT ADJUSTMENT

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you haveanincorrectflamepattern, contact your Excalibur® dealer for further instructions.

Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.

Themanifoldpressureiscontrolledbyaregulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug, but do not over tighten.

Circulation Fan: variable speed 130

CFM.

Log Set: Ceramic fi bre, 7 per set.

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M91).

GAS LINE

INSTALLATION

The gas line is brought through the right side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve.

The gas line connection may be made of rigid pipe, copper pipe or an approved flex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.

For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.

S.I.T. VALVE DESCRIPTION

1) Gas on/off knob

2) Manual high/low adjustment

3) Pilot Adjustment

4) Thermocouple Connection - option

5) Outlet Pressure Tap

6) Inlet Pressure Tap

7) Pilot Outlet

8) Main Gas Outlet

9) Alternative TC Connection

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

24

Excalibur® P90 Zero Clearance Direct Vent Gas Fireplace

Image 24
Contents P90 Zero Clearance Direct Vent Gas Fireplace 07/17/06Information for MOBILE/MANUFACTURED Homes After First Sale To the New OwnerTable of Contents Safety Label Copy of Safety Decal for P90Requirements For the State of Massachusetts onlyInstallation General Safety InformationInstallation Checklist Important Message Save These InstructionsLocating Your GAS Fireplace Manufactured Mobile Home Additional RequirementsHeatwave Optional Heat Release KITFraming Dimensions Combustible MantelsFraming Finishing Unit Base STAND-OFFSFacing Requirement Facing Over 1 25mm ThickFloor Mounted Fireplaces Raised Fireplaces Unit Assembly Prior to Installation Top Standoff AssemblyVenting Introduction Side Nailing StripsVenting FPI Direct Vent System Flex Horizontal Terminations OnlyExterior Vent Termination Locations Rigid Pipe Venting Components List SV4LB6Rigid Pipe Venting Systems AlternateHorizontal CapsHorizontal & Vertical Terminations for 5 x 8 Venting Rigid Pipe Venting Arrangements Horizontal Terminations 8 outer diameterRigid Pipe Venting Arrangements Vertical Terminations Installation Horizontal Venting with Two 2 90o Elbows Horizontal Venting with Three 3 90o ElbowsOption + H1 Option + V1 H + H1Vertical Venting with Two 2 90o Elbows Vertical Venting with Three 3 90o ElbowsOption Below Grade Installation Diagram Horizontal Terminations This allows for small adjustments Vertical TerminationsInstallation Procedures Offset ChartFor FPI Direct Vent System Flex Pilot Adjustment GAS Line InstallationGAS Pipe Pressure Testing High ElevationConversion KIT #791-969 from NG to LP LPG Conversion Kit Contains Qty DescriptionInstallation of the DC Sparker for the H35-1 Units Only Installation of the DC Sparker For the P90 Units Only Ground Wire from Kit 02-75 02-54 02-52 02-50 02-53 02-51 Bracket2nd Grate Tab 02-5302-5302-51 02-50 02-53Front Brackets Place embers in these 3 locations On the burner trayGlass Door Installation Arch SurroundOptional Screen Door Screw BracketAccent KIT Installation Double & Single Door OptionRemote Control Wall SwitchThermostat Wire Table Wall ThermostatWiring Diagrams Do not cut the ground terminal off under any circumstancesFor Propane Units and Units Equipped with DC Spark Boxes Operating Instructions Copy of the Lighting Plate Instructions Normal Operating Sounds of GAS AppliancesMaintenance FAN Maintenance To Install the FanShut the power off To Remove the FanInstalling Valve Removing ValveHint ImpossibleParts List P90 Main AssemblyDescription Heat Wave Duct KIT P90 Burner Assembly & LOG SET P90 Flush Front Accessories DescriptionExcalibur P90 Zero Clearance Direct Vent Gas Fireplace Excalibur P90 Zero Clearance Direct Vent Gas Fireplace Warranty Warranty Limited LifetimeInstaller Please complete the following information