Hampton Direct H25-LP1 Horizontal Venting with Two 2 90o Elbows, + H1 With these options, max

Page 15

INSTALLATION

Horizontal Venting with Two (2) 90o Elbows

One 90o elbow = Two 45o elbows.

Option

 

V

H + H1

With these options, maxi-

 

 

 

 

mum total pipe length is 30

A)

2'

Min.

4' Max.

 

 

 

 

feet with minimum of 6 feet

B)

3'

Min.

5' Max.

total vertical and maximum

C)

4'

Min.

6' Max.

8 feet total horizontal.

D)

5'

Min.

7' Max.

Please note minimum 1

E)

6'

Min.

8' Max.

foot between 90o elbows

 

 

 

 

is required.

Lengths do not include elbow indicated

H1

 

Vent restrictor position A (fully open), refer to the

 

"Vent Restrictor Position" section.

 

 

 

V

H

Horizontal Venting with Two (2) 90o Elbows

One 90o elbow = Two 45o elbows.

Option

H

V

H + H1 With these options, max.

A)1' Max. 1' Min. 3' Max. total pipe length is 30 feet with min. of 8 feet total

B)2' Max. 2' Min. 5' Max. vertical and max. 8 feet

C)3' Max. 4' Min. 6' Max. total horizontal.

D)4' Max. 6' Min. 7' Max. Please note min. 1 foot

E)5' Max. 8' Min. 8' Max. between 90o elbows is required.

Lengths do not include elbow indicated

 

Vent restrictor position A (fully open), refer to the "Vent

 

Restrictor Position" section.

H1

 

H

V

Hampton® H25-1 Direct Vent Freestanding Gas Stove

15

Image 15
Contents H25 Direct Vent Gas Fireplace Unit Dimensions HamptonTo the New Owner Table of Contents Copy of Safety Label for H25-NG1 & H25-LP1 Safety LabelMA Code CO Detector RequirementsBefore YOU Start InstallationImportant Message InstructionsThis includes General Safety InformationInstallation Checklist Clearances to CombustiblesFan Kit Contains Optional FAN InstallationLocating Your GAS Stove Manufactured Mobile Home Additional RequirementsInstallation Remove all 4 screws Washers PrecautionsVent Restrictor Position Rotating 45O ElbowExterior Vent Terminal Locations SV4LB6 Rigid Pipe Venting Components ListCaps Rigid Pipe Venting SystemsAlternate HorizontalDura-Vent Snorkel Termination Venting Arrangements+ H1 With these options, max Horizontal Venting with Two 2 90o Elbows+ V1 With these options, max. total Vertical Venting with Two 2 90o ElbowsAlternate Approved Caps Vertical Termination with CO-LINEAR Flex SystemStraight Vertical Terminations DescriptionQty. Description DV Stove Horizontal Vent KITMust be used to ensure that the termination is not Planning Your venting Installation Minimum components for a Horizontal InstallationOptional Components Dura-Vent Basic Horizontal Kit # Planning Your Dura-Vent InstallationDURA-VENT Termination KIT DURA-VENT VentingSnorkel Terminations Below Grade Snorkel InstallationHorizontal Terminations Minimum components for a Dura-Vent Verti- cal TerminationVertical Terminations Offset Chart Converting a Factory Built Metal Chimney Approved for US Installations OnlyGAS Connection Aeration AdjustmentCathedral Ceilings High ElevationGAS Pipe Pressure Testing Valve DescriptionClockwise to open Counter-clockwise to close LPG Conversion Kit Contains Qty Conversion KIT #434-969 from NG to LPGlow on logs Installation of the DC Sparker for the H25-1 Unit Only Are fragile, handle with care do not force into position LOG SET InstallationShut off the gas supply Lift off the Cast Top and remove the Glass Front see manualLogs must be oriented as shown below Rear View Decorative Door Grill Remote ControlWall Thermostat On an interior wallFinal Check Wiring DiagramsFor Propane Units and Units Equipped with DC Spark Boxes Operating Instructions Copy of the Lighting Plate Instructions For Your Safety Read Before LightingMaintenance Maintenance InstructionsNormal Operating Sounds GAS Appliances Replacement 946-327 Glass FAN MaintenanceLOG Replacement Glass ReplacementScrews Installing Valve AssemblyTo remove valve from valve assembly, continue Removing ValveMain Assembly Parts ListBurner & LOG Assembly Conditions WarrantyInstaller Please complete the following information