INSTALLATION
You will require the following components with your new Direct Vent Freestanding Gas Stove. Please review your product to make sure you have everything you need. In the event that you are missing any part, contact your dealer.
Note: These are the minimum pieces re- quired. Other parts may be required for your particular installation. See above for a list of vent parts.
If installing termination on a siding covered wall, a vinyl siding standoff or furring strips can be used in order to ensure that the termination is not recessed into siding.
The vinyl siding standoff is required for walls with vinyl siding.
Minimum components for a
A)
B)Wall Thimble (required for combustible walls)
Minimum components for a Dura-Vent Verti- cal Termination:
D)
HORIZONTAL
TERMINATIONS
1)Set the unit in its desired location. Check to determine if wall studs are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit.
2)Assemble the desired combination of pipe and elbow to the appliance adapter with pipe seams oriented down. Offset the pipe seams as double seams in one place will cause the outer pipe to take an oval shape. Kit comes complete with 18" of straight vent -
3)With the pipe attached to the stove, slide the stove into its correct location, and mark the wall for a
Diagram 1
Note:
a)The horizontal run of vent should have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high tempera- tures and may present the possibility of a fi re.
b)Thelocationofthehorizontalventtermination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. Refer to the "Exterior Vent Terminal Locations" section.
c)Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building,
*Diagram 2a: As specifi ed in CGA B149 Instal- lation Code. Local codes or regulations may require different clearances.
Diagram 2a
Diagram 2b
NOTE: For Snorkel terminations in ABOVE grade installations, follow national or local code requirements.
Below Grade Snorkel Installation
If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent waterfromenteringtheSnorkelTermination. Refer to
4)Install wall penetration heat shield in the center of the
5)If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding. Diagram 3.
6)Take the Riser Vent terminal and separate the Backing Plate from the Riser Vent Front by removing 8 screws as shown in diagram 4.
Diagram 3
22 | Hampton® |