Hampton Direct H25-LP1, H25-NG1 installation manual GAS Pipe Pressure Testing, Valve Description

Page 27

INSTALLATION

To adjust the aeration: use the allen key to turn the turning gear which will adjust the air shutter. Open the air shutter for a blue fl ame or close it for a more yellow fl ame. This adjustment is per- formed by a qualified installer.The factory setting should be suffi cient for most installations.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air shutter is closed too much.

Note: Any damage due to carboning re- sulting from improperly setting the aeration controls is NOT covered under warranty.

Note: Aeration Adjustment should only be performed by an authorized Hamp- ton® Installeratthetimeofinstallation or service.

GAS PIPE

PRESSURE TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" posi- tion.

2)Loosenthe"IN"and/or"OUT"pressuretap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position. Read manometer.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug, but do not over tighten

Valve Description

1)Gas on/off knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection

5)Main Operator

6)Outlet Pressure Tap (Manifold Pressure)

7)Inlet Pressure Tap (Supply Pressure)

8)Pilot Outlet

9)Main Gas Outlet

10)Flange Securing Screw Holes

11)Alternative TC Connection Point

12)Thermoelectric Unit

13)Additional Valve Mounting Hole

Hampton® H25-1 Direct Vent Freestanding Gas Stove

27

Image 27
Contents H25 Direct Vent Gas Fireplace Unit Dimensions HamptonTo the New Owner Table of Contents Copy of Safety Label for H25-NG1 & H25-LP1 Safety LabelMA Code CO Detector RequirementsBefore YOU Start InstallationImportant Message InstructionsThis includes General Safety InformationInstallation Checklist Clearances to CombustiblesFan Kit Contains Optional FAN InstallationLocating Your GAS Stove Manufactured Mobile Home Additional RequirementsInstallation Remove all 4 screws Washers PrecautionsVent Restrictor Position Rotating 45O ElbowExterior Vent Terminal Locations SV4LB6 Rigid Pipe Venting Components ListCaps Rigid Pipe Venting SystemsAlternate HorizontalDura-Vent Snorkel Termination Venting Arrangements+ H1 With these options, max Horizontal Venting with Two 2 90o Elbows+ V1 With these options, max. total Vertical Venting with Two 2 90o ElbowsAlternate Approved Caps Vertical Termination with CO-LINEAR Flex SystemStraight Vertical Terminations DescriptionQty. Description DV Stove Horizontal Vent KITMust be used to ensure that the termination is not Planning Your venting Installation Minimum components for a Horizontal InstallationOptional Components Dura-Vent Basic Horizontal Kit # Planning Your Dura-Vent InstallationDURA-VENT Termination KIT DURA-VENT VentingSnorkel Terminations Below Grade Snorkel InstallationHorizontal Terminations Minimum components for a Dura-Vent Verti- cal TerminationVertical Terminations Offset Chart Converting a Factory Built Metal Chimney Approved for US Installations OnlyGAS Connection Aeration AdjustmentCathedral Ceilings High ElevationGAS Pipe Pressure Testing Valve DescriptionClockwise to open Counter-clockwise to close LPG Conversion Kit Contains Qty Conversion KIT #434-969 from NG to LPGlow on logs Installation of the DC Sparker for the H25-1 Unit Only Are fragile, handle with care do not force into position LOG SET InstallationShut off the gas supply Lift off the Cast Top and remove the Glass Front see manualLogs must be oriented as shown below Rear View Decorative Door Grill Remote ControlWall Thermostat On an interior wallFinal Check Wiring DiagramsFor Propane Units and Units Equipped with DC Spark Boxes Operating Instructions Copy of the Lighting Plate Instructions For Your Safety Read Before LightingMaintenance Maintenance InstructionsNormal Operating Sounds GAS Appliances Replacement 946-327 Glass FAN MaintenanceLOG Replacement Glass ReplacementScrews Installing Valve AssemblyTo remove valve from valve assembly, continue Removing ValveMain Assembly Parts ListBurner & LOG Assembly Conditions WarrantyInstaller Please complete the following information