Weil-McLain 80 manual Freeze protection when used, Check boiler for gas-tight seal

Page 33

• Installation • Start-Up • Maintenance • Parts

16 Make final adjustments (continued)

Figure 35 Flue damper assembly, typical

Skim steam boilers:

Determine if water treatment is needed (water boilers only):

Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to system components can result, causing substantial property damage.

Continual make-up water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron and causing section failure.

For unusually hard water areas or low pH conditions (less than 7.0) consult local water treatment company.

Freeze protection (when used):

1.Use antifreeze especially made for hydronic systems. Inhibited propylene glycol is recommended.

Do not use automotive, ethylene glycol or undiluted antifreeze. Severe personal injury or death can result.

2.50% solution provides protection to about -30°F.

3.Local codes may require back-flow preventer or actual disconnect from city water supply.

Clean all newly installed steam boilers to remove oil. Failure to properly clean can result in violent water level fluctuations, water passing into steam mains, or high maintenance costs on strainers, traps and vents. Skim boiler only. Do not clean old piping or leaks can occur.

Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to system components can result, causing substantial property damage.

1.Remove 1½" plug from skim tapping tapping “A” – Figure 28, page 29). Provide 1½" skim piping from tapping to floor drain (pipe to side of boiler).

2.Raise waterline to midpoint of skim piping.

3.Fire burner to maintain temperature below steaming rate during skimming process.

4.Feed in water to maintain water level. Cycle burner to prevent rise in steam pressure.

5.Continue skimming until discharge is clear. This may take several hours.

6.Drain boiler. While boiler is warm but not hot, flush all interior surfaces under full pressure until drain water runs clear.

7.Remove skim piping. Re-insert plug at boiler skim tapping.

8.Close drain cock. Fill with fresh water to normal water line. Start burner and steam for 15 minutes to remove dissolved gases. Stop burner.

9.Check traps and air vents for proper operation.

4.Determine quantity according to system water content. Boiler water content is listed on page 34. Percent of solution will affect sizing of heat distribution units, circulator and expansion tank.

5.Follow antifreeze manufacturer's instructions.

Check boiler for gas-tight seal:

Boiler must be sealed gas-tight to prevent possible flue gas leakage and carbon monoxide emissions, resulting in severe personal injury or death.

1. Remove boiler jacket side and top panels.

The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 38 of this manual. Failure to comply could result in severe personal injury.

2.Start burner. Observe all sealing points and chalk mark any not gas-tight.

3.To seal all chalk-marked areas:

a.use silicone sealant on section flueways.

b.check gaskets and sealing rope placement.

4.Reinstall all jacket panels.

Part No. 550-141-935/0602

33

Image 33
Contents Boiler Manual Contents Installation must comply with Before installing boilerBefore selecting boiler location Lay a foundation, if neededProvide combustion and ventilation air openings Using crane attach free end of cables to eye of crane For block assemblySet boiler in place For packaged boilerAssemble block Install back refractory blanketPrepare back section Place a block under pipe to hold section uprightInstall intermediate sections If using tankless heater TI sectionsPrepare remaining sections Prepare boiler and test Perform hydrostatic pressure testComplete block assembly Install burner mounting plate on front sectionInstall cleanout plates Flue collector assembly Install flue collectorInstall collector hold-down bolts Prepare flue collector hood assemblyInstall flue collector After installing flue collector, ALL Boilers Before installing flue collectorRear flue boilers only Top flue boilers onlyInstall flue collector Install piping Connect water boiler pipingGeneral water piping information Size secondary boiler pump GPM based on following formulas Piping for multiple boilers see FigureGeneral steam piping information Connect steam boiler pipingConnect steam boiler piping Condensate piping to boiler Condensate receiver capacity Multiple Steam Boiler Piping Gravity Condensate Return Before installing jacket Install jacketInstall support brackets and rails Install jacket front and rear panelsInstall jacket Install jacket side panels Install jacket top panelsInstall jacket trim Jacket side panel placement Models 380, 480, 580 Jacket side panel placement Models 780, 880 Jacket side panel placement Models 1080, 1180, Jacket top panel placement Pipe tankless heaters To pipe tankless heatersSize piping no smaller than heater inlet and outlet Install controls Install water boiler controlsInstall controls where shown in and Figure Install steam boiler controlsWater level control locations see Table Connect breeching and venting systems General venting information Construct metal breechingSelect type of venting system Install burner Wiring and fuel pipingMake final adjustments Check boiler for gas-tight seal Freeze protection when usedDimensions and ratings Dimensions and ratings Parts Parts Eye Irrigate immediately Breathing Fresh air Handling ceramic fiber and fiberglass materialsPropane boilers propane gas odorant All Residential & Commercial Cast Iron Boilers