Pellet Boiler Outdoor Air Reset Operation

When the outdoor sensor is installed, at 20° F. or below OAT (Outdoor Air Temperature), the boiler will operate at the temperature set on the Maximum Temperature knob. The boiler water temperature will decrease by 1 degree for every 1 degree in temperature rise of the Outside Air.

Example 1

OAT

Water Temp

Degree Change

Max set at 185o

65o

140o

-45°

 

Min set at 140o

60o

145o

-40°

 

 

 

55o

150o

-35°

 

 

 

50o

155o

-30°

 

 

 

45o

160o

-25o

 

 

40o

165o

-20o

 

 

35o

170o

-15o

 

 

30o

175o

-10o

 

 

25o

180o

-5o

 

 

20o

185o

0o

 

 

15o

185o

0o

 

 

10o

185o

0o

 

 

5o

185o

 

 

 

0o

185o

 

 

 

Example 2

OAT

Water Temp

Degree Change

 

Max set at 180o

65o

150o

*

 

 

Min set at 150o

60o

150o

*

 

 

 

55o

150o

*

 

 

 

50o

150o

-30o

 

 

45o

155o

-25o

 

 

40o

160o

-20o

 

 

35o

165o

-15o

 

 

30o

170o

-10o

 

 

25o

175o

-5o

 

 

20o

180o

0o

 

 

15o

180o

0o

 

 

10o

180o

0o

 

 

5o

180o

0o

 

 

0o

180o

0o

*No change in boiler temperature after reaching minimum setpoint tempera- ture.

Operation

Image 28
Contents Installation & Operating Manual Bio-Flow BH60 Pellet BoilerPage BH60 Parts Table of Contents Options Bulk Storage HopperPreparation For Installation InstallationBoiler Kit Materials Refer to Minimum non-combustible floor protection area Minimum Clearances To Combustible Materials Venting Requirements for Terminating the VentingVenting Vent PipeVentingti g Venting Into An Existing ChimneyVenting Installation Negative Pressure and Electrical Power Failure Outside AirInstallation-Plumbing Domestic HOT Water ZoneExtremely Important That this Boiler be Existing Controls and Safety Devices areBoiler Example of Piping in Series with AN Existing Operational BoilerExisting Boiler Associated Piping and Controls That shouldInstallingInstallationDuct/Air-PlumbingConditioning Dipswitch #6 must be on Example of a Typical Forced HOT AIR Heating System Installation With a Hot Air System Splice R1 RelayInstallation With a Hot Air System fan only capable R2 RelayWith a 2-wire hot air system Overheat Safety ZoneConnection with a wireless thermostat Blue Violet Draft Test Procedure Low Draft Adjustment Pot High altitude kit #1-00-232059 Test DraftExplanation and Importance of the OverHeat Safety Zone Status light error messagesOperation Control Board Operation Pellet Boiler Outdoor Air Reset Operation Turn Mode Selector to OFF Clean Burnpot with scraperFlip the Igniter Switch up into the Auto position MAX. TempLighting a Fire Manually Type of FuelOperation Maintenance Cleanout coverBurnp ot Fines area Feeder cover FigAsh Removal Inner Refractory LiningOpen The Firebox Door Cleaning Firebox Baffle RemovalCombustion Blower Cleaning Boiler Must be OFF at the circuit breaker,Special Insructions/ Power Failure To Normal Heating DemandHelpful Hints TroubleshootingFuel BTU Input Range= 0, and 9350 to 60,000 SpecificationsElectrical VAC 60 Hz Plug DiagramPIN Warranty ECO-CHOICE Limited WarrantyTesting Label EFEBh105 Bh60 Stocked #11 Feeder Assembly Page Quick Reference Auto-Light Signature of Boxer