Heatiator BH60 manual Requirements for Terminating the Venting

Page 9

Venting

Requirements for Terminating the Venting

WARNING: Venting terminals must not be recessed into a wall or siding.

NOTE: Only PL vent pipe wall pass-throughs and fire stops should be used when venting through com- bustible materials.

NOTE: Always take into consideration the effect the prevailing wind direction or other wind currents will cause with flyash and /or smoke when placing the termination.

In addition, the following must be observed: A. The clearance above grade must be a minimum of 18”.1

B. The clearance to a window or door that may be opened must be a minimum of 48” to the side, 48” below the window/door, and 12” above the window/ door.1

C. A 12” clearance to a permanently closed window is recommended to prevent condensation on the window. D. The vertical clearance to a ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of the terminal must be a minimum of 18”.

E. The clearance to an unventilated soffit must be a minimum of 12”.

F. The clearance to an outside corner is 11” from center of pipe.

G. The clearance to an inside corner is 12”. If you see deposits developing on the wall, you may need to extend this distance to accomodate your installation conditions.

H. A vent must not be installed within 3 feet (90 cm) above a gas meter/regulator assembly when measured from the horizontal center-line of the regulator.1

I. The clearance to service regulator vent outlet must be a minimum of 6 feet.1

J. The clearance to a non-mechanical air supply inlet to the building or the combustion air inlet to any other appliance must be a minimum of 48”.1

K. The clearance to a mechanical air supply inlet must be a minimum of 10 feet.1

L. The clearance above a paved sidewalk or a paved driveway located on public property must be a minimum of 7 feet.1,2

M. The clearance under a veranda, porch, deck or balcony must be a minimum of 12 inches.1,3 (See B. also)

NOTE: The clearance to vegetation and other exte- rior combustibles such as mulch is 36” as measured from the center of the outlet or cap. This 36” radius continues to grade or a minimum of 7 feet below the outlet.

1Certain Canadian and or Local codes or regulations may require different clearances.

2A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single  family dwellings and serves both dwellings.

3Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor.

NOTE: Where passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365. (if in Canada)

= Vent terminal

= Air supply inlet

= Area where terminal is not permitted

Fig. 2

9

Image 9
Contents Bio-Flow BH60 Pellet Boiler Installation & Operating ManualPage BH60 Parts Table of Contents Bulk Storage Hopper OptionsInstallation Preparation For InstallationBoiler Kit Materials Refer to Minimum non-combustible floor protection area Minimum Clearances To Combustible Materials Requirements for Terminating the Venting VentingVent Pipe VentingVenting Into An Existing Chimney Ventingti gVenting Installation Outside Air Negative Pressure and Electrical Power FailureDomestic HOT Water Zone Installation-PlumbingExisting Controls and Safety Devices are Extremely Important That this Boiler beBoiler AN Existing Operational Boiler Example of Piping in Series withExisting Boiler Associated Piping and Controls That shouldInstallingInstallationDuct/Air-PlumbingConditioning Dipswitch #6 must be on Example of a Typical Forced HOT AIR Heating System Installation With a Hot Air System R1 Relay SpliceR2 Relay Installation With a Hot Air System fan only capableOverheat Safety Zone With a 2-wire hot air systemBlue Violet Connection with a wireless thermostatLow Draft Adjustment Pot High altitude kit #1-00-232059 Draft Test ProcedureTest DraftStatus light error messages Explanation and Importance of the OverHeat Safety ZoneOperation Control Board Operation Pellet Boiler Outdoor Air Reset Operation Clean Burnpot with scraper Turn Mode Selector to OFFMAX. Temp Flip the Igniter Switch up into the Auto positionType of Fuel Lighting a Fire ManuallyOperation Cleanout cover MaintenanceBurnp ot Fines area Feeder cover FigInner Refractory Lining Ash RemovalOpen The Firebox Door Firebox Baffle Removal CleaningBoiler Must be OFF at the circuit breaker, Combustion Blower CleaningTo Normal Heating Demand Special Insructions/ Power FailureTroubleshooting Helpful HintsFuel Specifications BTU Input Range= 0, and 9350 to 60,000Electrical VAC 60 Hz Diagram PlugPIN ECO-CHOICE Limited Warranty WarrantyEFE Testing LabelBh105 Bh60 Stocked #11 Feeder Assembly Page Quick Reference Auto-Light Signature of Boxer

BH60 specifications

The Heatiator BH60 is an innovative heating solution designed to enhance indoor comfort while maximizing energy efficiency. This state-of-the-art heater combines advanced technology with user-friendly features, making it an ideal choice for both residential and commercial applications.

One of the standout features of the Heatiator BH60 is its powerful heating capability. The unit can produce an impressive amount of heat, making it suitable for larger spaces. With an adjustable thermostat, users can easily set their desired temperature, ensuring a cozy environment regardless of the season. Additionally, the unit employs a rapid heating technology that allows it to warm up spaces quickly, reducing the wait time for comfort.

The Heatiator BH60 is equipped with energy-saving technologies to minimize power consumption while maximizing output. The unit utilizes a smart energy management system that monitors usage patterns and adjusts heating levels accordingly. This not only helps in reducing energy bills but also contributes to a more sustainable environment. The heater is also designed to operate quietly, making it perfect for use in bedrooms, living rooms, and offices without disturbing daily activities.

Another significant characteristic of the Heatiator BH60 is its safety features. The heater is built with overheat protection, which automatically shuts off the unit if it reaches unsafe temperature levels. Additionally, the unit is constructed with flame-resistant materials, adding an extra layer of safety. It also comes with a tip-over switch that automatically turns off the heater if it is knocked over, making it a safe option for households with pets and children.

The design of the Heatiator BH60 is both sleek and modern, allowing it to blend seamlessly into various interior styles. Its compact size ensures it does not take up much space, making it easy to place it in different locations according to needs. Users appreciate the straightforward controls, which provide a hassle-free experience when adjusting settings.

In conclusion, the Heatiator BH60 stands out as an effective and efficient heating solution. With its robust heating capabilities, energy-efficient technologies, and a focus on safety, it is an excellent choice for anyone looking to improve their indoor climate. Whether in a home or office, the Heatiator BH60 promises to deliver comfort and warmth in a reliable manner.