Burnham V8 Series manual

Page 11

C.PROVIDE COMBUSTION AND VENTILATION AIR. Local and National Codes may apply and should be referenced.

WARNING

Adequate combustion and ventilation air must be provided to assure proper combustion and to maintain safe ambient air temperatures.

Do not install boiler where gasoline or other flammable vapors or liquids, or sources of hydrocarbons (i.e. bleaches, fabric softeners, etc.) are used or stored.

1.Determine volume of space (boiler room). Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.

Volume(ft3) = Length(ft) x Width(ft) x Height(ft)

2.Determine total input of all appliances in the space.

Add inputs of all appliances in the space and round the result to the nearest 1000 BTU per hour.

3.Determine type of space. Divide Volume by total input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour, then it is considered an unconfined space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a confined space.

4.For boiler located in an unconfined space of a conventionally constructed building, the fresh air infiltration through cracks around windows and doors normally provides adequate air for combustion and ventilation.

5.For boiler located in a confined space or an unconfined space in a building of unusually tight construction, provide outdoor air.

a.Outdoor air for combustion may be provided with an optional Burnham V8 Inlet Air Accessory Kit, Part Number 611280031 (ONLY

AVAILABLE WITH BECKETT BURNER). See Section VII for installation details.

or

b.Outdoor air may be provided with the use of two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top

of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:

i. Direct communication with outdoors. Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.

ii. Vertical ducts. Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

iii. Horizontal ducts. Minimum free area of 1 square inch per 2,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

Alternate method for boiler located within confined space. Use indoor air if two permanent openings communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.

6.Louvers and Grilles of Ventilation Ducts

a.All outside openings should be screened and louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.

b.Free area requirements need to consider the blocking effect of louvers, grilles, or screens protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.

c.Louvers and grilles must be fixed in the open position, or interlocked with the equipment to open automatically during equipment operation.

11

Image 11
Contents V8 Series USA Boilers Important Information Read CarefullyPage Table of Contents Dimensional Data see Figures 1A Thru 1D V82 thru V89 Water Boiler without Tankless Heater V83 thru V89 Water Boiler with Front Tankless Heater V83 thru V89 Water Boiler with Rear Tankless Heater V83 thru V89 Steam Boiler with or without Tankless Heater Section I PRE-INSTALLATION Page Do not allow any flueway blockage by gasket Section II Knockdown Boiler AssemblyRemoval of Bare Boiler from Skid Boiler Tapping Locations and Usage Knockdown Boilers Only Install Boiler JACKET. See Figure Knockdown Boiler Jacket AssemblyInstall Beckett OIL BURNER. See Figure Oil Burner Installation Beckett Burner ShownSteam Boilers Only Do not install burner without gasketInstall Carlin 102CRD OIL BURNER. See Figure Water Boilers Only Combustion Head AdjustmentInstall Carlin Elite EZ OIL BURNER. See Figure Installation/Removal of Drawer Assembly Nozzle Replacement Install probe type Low Water Cut-Off Lwco if so equipped Aquastat bulb must be fully inserted into the well Float-Type Low Water Cut-Off Pressure Limit InstallationInstall Trim and Controls with Carlin 102CRD Burner Burners Supplied by Burnham utilize Install Trim and Controls with Carlin Elite EZ BurnerInstall Trim and Controls with Riello Burner Page Do not drop boiler. Do not bump boiler jacket against floor Section III Packaged Boiler AssemblyRemove Crate Remove Boiler from SkidPage Page Steam or Water Boilers Inspect Nozzle and Electrodes Install Safety or Relief Valve in Tapping MEvaluate the Existing Water System Section IV Water Boiler Piping and TrimPage Recommended Water Piping for Circulator Zoned Heating System Page Page Evaluate the Existing Steam System Section V Steam Boiler Piping and TrimPage Section VI Tankless and Indirect Water Heater Piping GPM Connect Alliance Indirect Water Heater Piping as shown in B Alliance Water Heater Piping with V8 BoilerDo not exceed maximum allowable air intake length Section VII Venting and AIR Intake PipingGeneral Venting Guidelines Recommended Vent Pipe Arrangement and Chimney Requirements Seal all external joints with weatherproof caulk General Section Viii ElectricalBoiler Sequence of Operation with Probe Lwco Page Page Jumper Page Page Boiler Sequence of Operation with Float Lwco Page Page Boiler Sequence of Operation Page Page Boiler Sequence of Operation Page Page Boiler Sequence of Operation Page Page Single Pipe OIL Lines Section IX OIL PipingSINGLE-STAGE Units 3450 RPM TWO Pipe Systems TWO Pipe OIL LinesFill Heating System with Water Always Inspect Installation Before Starting BurnerSection X System START-UP Carlin Elite EZ Burners Adjust OIL Burner Before StartingBeckett Burners Carlin 102CRD BurnersStart OIL Burner Adjust OIL Burner While OPERATING. flame presentRiello Burners L1 and V1 Head Electrode Test Controls Check for Clean CUT OFF of BurnerCAD Cell Resistance When Sensing Flame Jumper must be removed after this check Aquastat Switching Action Within L8124C ControlAquastat Switching Action Within L8148A Controls Avoid Breathing Fiber Particulates and Dust Maintenance of LOW Water CUT- OFF Devices Section XI Maintenance and Service InstructionsPage Gal/Month V83 V85 V87 V89 V84 V86 V88 14½ Frequent Water AdditionPage Clean the Combustion Chamber Section XII Boiler CleaningClean the Flueways See Figure Clean TOP of Boiler Sections if cleaning from the topCleaning of Boiler Flueways OIL Primary Control Section Xiii Trouble ShootingCombustion Section XIV Repair Parts Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly 1BB Bare Boiler AssemblyJacket Assembly Page V83 Thru V89 Steam Boilers Trim and Controls V83 Thru V89 Steam Boilers Trim and Controls V82 Thru V89 Water Boilers Trim and Controls V82 Thru V89 Water Boilers Trim and Controls Beckett AFG Burner Beckett OIL Burner Part NOS. for V8 Series Boilers Beckett OIL Burner Part NOS. for V8 Series Boilers Carlin OIL Burner Part Numbers for V8 Series Boilers Burner Specifications When XV. LOW Water CUT OFF LwcoService Record Limited Warranty For Residential Cast Iron Steam Boilers

V8 Series specifications

The Burnham V8 Series is a prestigious line of oil-fired boilers renowned for their efficiency, reliability, and advanced design features. Tailored for residential and light commercial applications, this series exemplifies the perfect blend of tradition and modern technology, ensuring long-term performance and comfort for users.

One of the hallmark features of the Burnham V8 Series is its exceptional cast iron construction, which provides durability and superior heat retention. This robust design allows for an extended lifespan while ensuring that the boiler can withstand the rigors of daily use. The cast iron sections are engineered to facilitate optimal heat transfer and efficiency.

The V8 Series boasts an impressive fuel efficiency rating, often exceeding 85%. This high efficiency is achieved through a combination of advanced combustion technology and the boiler's thoughtful design, which minimizes heat loss. Users benefit not only from lower energy bills but also from a reduced environmental footprint, making the Burnham V8 Series a sustainable choice for heating solutions.

In terms of technology, the Burnham V8 Series features a standing pilot ignition system or an optional intermittent ignition device that enhances safety and efficiency. The advanced burner design allows for smooth operation and excellent fuel utilization, further contributing to the overall economy of the system.

Another notable characteristic is the versatility of the Burnham V8 Series. It can be easily adapted to work with various heating systems, including hot water heating applications. Its compatibility with different fuels, such as natural gas or oil, gives users the flexibility to choose the best energy source for their needs, providing longevity and value.

The installation process is made straightforward with ample connectivity options for plumbing and flue. Its compact design enables easier placement within homes or commercial spaces without compromising performance. Furthermore, the boiler is backed by extensive warranties, ensuring peace of mind for homeowners and businesses alike.

In conclusion, the Burnham V8 Series stands out as a reliable and efficient heating solution, blending robust construction with advanced technology. Its commitment to performance, versatility, and efficiency makes it an excellent choice for meeting the heating demands of various applications while promoting environmental responsibility. Whether for a single-family home or a light commercial building, the Burnham V8 Series remains a trusted leader in the industry.