Carlin Elite EZ Burners
a.Carlin
4.READJUST THE TURBULATOR SETTING only if necessary.
Riello Burners
a.V82 through V89
Move the turbulator setting forward or back one position at a time to optimize the smoke and CO2 readings.
b.Turn “OFF” burner and remove Riello Combination Pressure Gauge and Bleeder Valve Assembly. Install pressure port/bleeder plug and tighten. Start burner again.
5.TURN “OFF” BURNER and remove pressure gauge. Install gauge port/bleeder plug and tighten. Start burner again.
WARNING
Do not loosen or remove any oil line fittings while burner is operating.
6.FLAME FAILURE
The V8 boiler controls operate the burner automatically. If for unknown reasons the burner ceases to fire and the reset button on the primary control has tripped, the burner has experienced ignition failure.
WARNING
Do not attempt to start the burner when excess oil has accumulated, when the unit is full of vapor, or when the combustion chamber is very hot.
H.CHECK FOR CLEAN CUT OFF OF BURNER.
1.AIR IN THE OIL LINE between fuel unit and nozzle will compress when burner is on and will expand when burner stops, causing oil to squirt from nozzle at low pressure as burner slows down and causing nozzle to drip after burner stops. Usually cycling the burner operation about 5 to 10 times will rid oil line of this air.
2.IF NOZZLE CONTINUES TO DRIP, repeat Paragraph I, No. 1. If this does not stop the dripping, remove
I.TEST CONTROLS.
1.Check thermostat operation. Raise and lower thermostat setting as required to start and stop burner.
WARNING
Before installation of the boiler is considered complete, the operation of all boiler controls must be checked, particularly the primary control and high limit control.
2.VERIFY PRIMARY CONTROL FEATURES using procedures outlined in Instructions furnished with control or instructions as follows:
a. FEATURES AND CONTROLS
i.The R7184 is a
Figure 28: R7184 Terminals, LED and Reset Button
ii.Pump Priming Cycle: To facilitate purging air from the oil lines and filters, the R7184 can be placed in a purge routine by pressing and releasing the reset button during the safety check, delayed
iii.Limited Recycle: This feature limits the number of recycle trials (for each call for heat) to a maximum of three trials. If the flame is lost three times and does not successfully satisfy a call for heat, the R7184 locks out.
iv.Limited Reset (Restricted Mode): In order to limit the accumulation of unburned oil in the combustion area, the control can only be reset three times. The reset count returns to zero each time a call for heat is successfully completed.
•To reset from Restricted Mode: Press and hold the reset button for 30 seconds. When the LED flashes twice, the device has reset.
69