Burnham V8 Series manual Section Viii Electrical, General

Page 44

SECTION VIII: ELECTRICAL

DANGER

Positively assure all electrical connections are unpowered before attempting installation or service of electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock once power is turned off.

WARNING

Failure to properly wire electrical connections to the boiler may result in serious physical harm.

Electrical power may be from more than one source. Make sure all power is off before attempting any electrical work.

Each boiler must be protected with a properly siz ed fused disconnect.

Never jump out or make inoperative any safety or operating controls.

WARNING

The primary control may be damaged or may not function properly if 120 volt power supply is NOT wired into control as follows:

The 120V interrupted hot (black) wire must be connected to the primary control black wire, the 120V neutral (white) wire must be connected to the primary control white wire and the 120V constant hot (red) wire must be connected to the primary control red wire.

A. GENERAL

1.Install wiring and electrically ground boiler in accordance with requirements of the authority having jurisdiction, or in absence of such requirements the National Electrical Code, ANSI/ NFPA 70, and/or the CSA C22.1 Electric Code.

2.Refer to National Electric Code or Local Electric Codes for proper size and type of wire required. Follow Code.

3.A separate electrical circuit must be run from the main electrical service with an over-current device/disconnect in the circuit. A service switch is recommended and may be required by some local jurisdictions.

4.Use anti-short bushings on all wiring passing through boiler jacket, junction boxes and/or control boxes.

5.Use armored cable (BX) over all exposed line voltage wiring.

6.If an Alliance™ indirect water heater is used, use priority zoning. Do not use priority zoning for Hydro-Air Systems.

7.If boiler is installed in Canada, a blocked vent safety switch must be installed. Refer to Blocked Vent Safety Switch Instruction Supplement provided with boiler (Canada only).

8.Wiring should conform to Figures 19 through 23F.

B.INSTALL A ROOM THERMOSTAT on an inside wall about four feet above floor. Never install thermostat on an outside wall or where it will be influenced by drafts, hot or cold water pipes, lighting fixtures, television, rays of the sun or near a fireplace. Keep large furniture away from thermostat so there will be free movement of room air around this control.

Heat Anticipator in Thermostat should be set to match the requirements of the control to which it is connected. See Figures 19 thru 23F for desired system and heat anticipator setting. If system tends to overheat above the thermostat's temperature setting, reduce heat anticipator setting by .1 or .2 amps. If system tends to short cycle without reaching desired room temperature, increase heat anticipator setting by .1 or .2 amps.

44

Image 44
Contents V8 Series Important Information Read Carefully USA BoilersPage Table of Contents Dimensional Data see Figures 1A Thru 1D V82 thru V89 Water Boiler without Tankless Heater V83 thru V89 Water Boiler with Front Tankless Heater V83 thru V89 Water Boiler with Rear Tankless Heater V83 thru V89 Steam Boiler with or without Tankless Heater Section I PRE-INSTALLATION Page Do not allow any flueway blockage by gasket Section II Knockdown Boiler AssemblyRemoval of Bare Boiler from Skid Boiler Tapping Locations and Usage Knockdown Boilers Only Knockdown Boiler Jacket Assembly Install Boiler JACKET. See FigureOil Burner Installation Beckett Burner Shown Install Beckett OIL BURNER. See FigureSteam Boilers Only Do not install burner without gasketInstall Carlin 102CRD OIL BURNER. See Figure Combustion Head Adjustment Water Boilers OnlyInstall Carlin Elite EZ OIL BURNER. See Figure Installation/Removal of Drawer Assembly Nozzle Replacement Install probe type Low Water Cut-Off Lwco if so equipped Float-Type Low Water Cut-Off Pressure Limit Installation Aquastat bulb must be fully inserted into the wellInstall Trim and Controls with Carlin 102CRD Burner Burners Supplied by Burnham utilize Install Trim and Controls with Carlin Elite EZ BurnerInstall Trim and Controls with Riello Burner Page Section III Packaged Boiler Assembly Remove CrateRemove Boiler from Skid Do not drop boiler. Do not bump boiler jacket against floorPage Page Steam or Water Boilers Install Safety or Relief Valve in Tapping M Inspect Nozzle and ElectrodesSection IV Water Boiler Piping and Trim Evaluate the Existing Water SystemPage Recommended Water Piping for Circulator Zoned Heating System Page Page Section V Steam Boiler Piping and Trim Evaluate the Existing Steam SystemPage Section VI Tankless and Indirect Water Heater Piping GPM Alliance Water Heater Piping with V8 Boiler Connect Alliance Indirect Water Heater Piping as shown in BDo not exceed maximum allowable air intake length Section VII Venting and AIR Intake PipingGeneral Venting Guidelines Recommended Vent Pipe Arrangement and Chimney Requirements Seal all external joints with weatherproof caulk Section Viii Electrical GeneralBoiler Sequence of Operation with Probe Lwco Page Page Jumper Page Page Boiler Sequence of Operation with Float Lwco Page Page Boiler Sequence of Operation Page Page Boiler Sequence of Operation Page Page Boiler Sequence of Operation Page Page Section IX OIL Piping Single Pipe OIL LinesTWO Pipe OIL Lines SINGLE-STAGE Units 3450 RPM TWO Pipe SystemsFill Heating System with Water Always Inspect Installation Before Starting BurnerSection X System START-UP Adjust OIL Burner Before Starting Beckett BurnersCarlin 102CRD Burners Carlin Elite EZ BurnersStart OIL Burner Adjust OIL Burner While OPERATING. flame presentRiello Burners L1 and V1 Head Electrode Check for Clean CUT OFF of Burner Test ControlsCAD Cell Resistance When Sensing Flame Aquastat Switching Action Within L8124C Control Jumper must be removed after this checkAquastat Switching Action Within L8148A Controls Avoid Breathing Fiber Particulates and Dust Section XI Maintenance and Service Instructions Maintenance of LOW Water CUT- OFF DevicesPage Frequent Water Addition Gal/Month V83 V85 V87 V89 V84 V86 V88 14½Page Section XII Boiler Cleaning Clean the Flueways See FigureClean TOP of Boiler Sections if cleaning from the top Clean the Combustion ChamberCleaning of Boiler Flueways OIL Primary Control Section Xiii Trouble ShootingCombustion Section XIV Repair Parts Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly 1BBJacket Assembly Page V83 Thru V89 Steam Boilers Trim and Controls V83 Thru V89 Steam Boilers Trim and Controls V82 Thru V89 Water Boilers Trim and Controls V82 Thru V89 Water Boilers Trim and Controls Beckett AFG Burner Beckett OIL Burner Part NOS. for V8 Series Boilers Beckett OIL Burner Part NOS. for V8 Series Boilers Carlin OIL Burner Part Numbers for V8 Series Boilers Burner Specifications XV. LOW Water CUT OFF Lwco WhenService Record Limited Warranty For Residential Cast Iron Steam Boilers

V8 Series specifications

The Burnham V8 Series is a prestigious line of oil-fired boilers renowned for their efficiency, reliability, and advanced design features. Tailored for residential and light commercial applications, this series exemplifies the perfect blend of tradition and modern technology, ensuring long-term performance and comfort for users.

One of the hallmark features of the Burnham V8 Series is its exceptional cast iron construction, which provides durability and superior heat retention. This robust design allows for an extended lifespan while ensuring that the boiler can withstand the rigors of daily use. The cast iron sections are engineered to facilitate optimal heat transfer and efficiency.

The V8 Series boasts an impressive fuel efficiency rating, often exceeding 85%. This high efficiency is achieved through a combination of advanced combustion technology and the boiler's thoughtful design, which minimizes heat loss. Users benefit not only from lower energy bills but also from a reduced environmental footprint, making the Burnham V8 Series a sustainable choice for heating solutions.

In terms of technology, the Burnham V8 Series features a standing pilot ignition system or an optional intermittent ignition device that enhances safety and efficiency. The advanced burner design allows for smooth operation and excellent fuel utilization, further contributing to the overall economy of the system.

Another notable characteristic is the versatility of the Burnham V8 Series. It can be easily adapted to work with various heating systems, including hot water heating applications. Its compatibility with different fuels, such as natural gas or oil, gives users the flexibility to choose the best energy source for their needs, providing longevity and value.

The installation process is made straightforward with ample connectivity options for plumbing and flue. Its compact design enables easier placement within homes or commercial spaces without compromising performance. Furthermore, the boiler is backed by extensive warranties, ensuring peace of mind for homeowners and businesses alike.

In conclusion, the Burnham V8 Series stands out as a reliable and efficient heating solution, blending robust construction with advanced technology. Its commitment to performance, versatility, and efficiency makes it an excellent choice for meeting the heating demands of various applications while promoting environmental responsibility. Whether for a single-family home or a light commercial building, the Burnham V8 Series remains a trusted leader in the industry.