Figure 20: Wiring Diagram, Steam, McDonnell & Miller PS-801 Probe LWCO for Beckett Burners
BOILER SEQUENCE OF OPERATION WITH PROBE LWCO
When the thermostat calls for heat, it energizes the cad cell primary control, bringing on the burner. The burner will operate in the following sequence: Prepurge for the first 10 seconds; fire until the thermostat is satisfied or the limit setting on the high limit is reached;
The probe low water
The probe low water
On burner start, if the cad cell does not see flame within approximately 15 seconds, primary control will shut burner down and enter into a recycle mode, after 60 seconds burner will restart and repeat trial for ignition. If after three
(3)trials for ignition, flame is not detected, control will enter into restricted mode and must be reset manually before burner can be restarted.
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected set- ting for proper operation of the domestic water heater, if equipped with optional tankless heater.
McDonnell & Miller
Terminals May Be Lettered or
Numbered as Follows:
Wire | Numbered | Lettered |
Color | Terminals | Terminals |
|
|
|
RD | 5 | B |
|
|
|
BK | 1 | H |
|
|
|
WH | 2 | N |
|
|
|
Jumper | ||
|
|
|
48