Burnham V8 Series manual Section Xiii Trouble Shooting, Combustion, OIL Primary Control

Page 80

SECTION XIII: TROUBLE SHOOTING

A.COMBUSTION

1.NOZZLES — Although the nozzle is a relatively inexpensive device, its function is critical to the successful operation of the oil burner. The selection of the nozzle supplied with the V8 boiler is the result of extensive testing to obtain the best flame shape and efficient combustion. Other brands of the same spray angle and spray pattern may be used but

may not perform at the expected level of CO2 and smoke. Nozzles are delicate and should be protected from dirt and abuse. Nozzles are mass-produced and can vary from sample to sample. For all of those reasons a spare nozzle is a desirable item for a serviceman to have.

2.FLAME SHAPE — Looking into the combustion chamber through the observation port, the flame should appear straight with no sparklers rolling up toward the crown of the chamber. If the flame drags to the right or left, sends sparklers upward or makes wet spots on the target wall, the nozzle should be replaced. If the condition persists look for fuel leaks, air leaks, water or dirt in the fuel as described above.

3.FUEL LEAKS — Any fuel leak between the pump and the nozzle will be detrimental to good combustion results. Look for wet surfaces in the air tube, under the ignitor, and around the air inlet. Any such leaks should be repaired as they may cause erratic burning of the fuel and in the extreme case may become a fire hazard.

4.AIR LEAKS — Any such leaks should be repaired, as they may cause erratic burning of the fuel and in extreme cases may become a fire hazard.

5.GASKET LEAKS — If 11.5 to 12.5% CO2 with a #1 smoke cannot be obtained in the breeching, look for air leaks around the burner mounting gasket, observation door, and canopy gasket. Such air leaks

will cause a lower CO2 reading in the breeching. The smaller the firing rate the greater effect an air leak can have on CO2 readings.

6.DIRT — A fuel filter is a good investment. Accidental accumulation of dirt in the fuel system can clog the nozzle or nozzle strainer and produce a poor spray pattern from the nozzle. The smaller the firing rate, the smaller the slots become in the nozzle and the more prone to plugging it becomes with the same amount of dirt.

7.WATER — Water in the fuel in large amounts will stall the fuel pump. Water in the fuel in smaller amounts will cause excessive wear on the pump, but more importantly water doesn’t burn. It chills the flame and causes smoke and unburned fuel to pass out of the combustion chamber and clog the flueways of the boiler.

8.COLD OIL — If the oil temperature approaching the fuel pump is 40°F or lower, poor combustion or delayed ignition may result. Cold oil is harder to atomize at the nozzle. Thus, the spray droplets get larger and the flame shape gets longer. An outside fuel tank that is above grade or has fuel lines in a shallow bury is a good candidate for cold oil. The best solution is to bury the tank and lines deep enough to keep the oil above 40°F.

9.HIGH ALTITUDE INSTALLATIONS — Air openings must be increased at higher altitudes. Use instruments and set for 11.5 to 12.5% CO2.

10.START-UP NOISE — Late ignition is the cause of start-up noises. If it occurs recheck for electrode settings, flame shape, air or water in the fuel lines.

11.SHUT DOWN NOISE — If the flame runs out of air before it runs out of fuel, an after burn with noise may occur. That may be the result of a faulty cut-off valve in the fuel pump, or it may be air trapped in the nozzle line. It may take several firing cycles for that air to be fully vented through the nozzle. Water in the fuel or poor flame shape can also cause shut down noises.

NOTICE

CHECK TEST PROCEDURE. A very good test for isolating fuel side problems is to disconnect the fuel system and with a 24" length of tubing, fire out of an auxiliary five gallon pail of clean, fresh, warm #2 oil from another source. If the burner runs successfully when drawing out of the auxiliary pail then the problem is isolated to the fuel or fuel lines being used on the jobsite.

B. OIL PRIMARY CONTROL

1.Burner (control) will not come on.

a.No power to control.

b.Control is in lockout or restricted mode. Press reset button for one (1) second to exit lockout. If control has recycled three times within the same call for heat, it will enter into restricted mode. To reset from restricted mode, refer to Section X, Paragraph I, No. 2 for details.

c.CAD cell seeing light.

d.CAD assembly defective.

e.Control motor relay is stuck closed (see note below).

2.Burner (control) will light, then shut down after a short time, then restart after one (1) minute.

a.CAD cell is defective.

80

Image 80
Contents V8 Series Important Information Read Carefully USA BoilersPage Table of Contents Dimensional Data see Figures 1A Thru 1D V82 thru V89 Water Boiler without Tankless Heater V83 thru V89 Water Boiler with Front Tankless Heater V83 thru V89 Water Boiler with Rear Tankless Heater V83 thru V89 Steam Boiler with or without Tankless Heater Section I PRE-INSTALLATION Page Do not allow any flueway blockage by gasket Section II Knockdown Boiler AssemblyRemoval of Bare Boiler from Skid Boiler Tapping Locations and Usage Knockdown Boilers Only Knockdown Boiler Jacket Assembly Install Boiler JACKET. See FigureOil Burner Installation Beckett Burner Shown Install Beckett OIL BURNER. See FigureSteam Boilers Only Do not install burner without gasketInstall Carlin 102CRD OIL BURNER. See Figure Combustion Head Adjustment Water Boilers OnlyInstall Carlin Elite EZ OIL BURNER. See Figure Installation/Removal of Drawer Assembly Nozzle Replacement Install probe type Low Water Cut-Off Lwco if so equipped Float-Type Low Water Cut-Off Pressure Limit Installation Aquastat bulb must be fully inserted into the wellInstall Trim and Controls with Carlin 102CRD Burner Burners Supplied by Burnham utilize Install Trim and Controls with Carlin Elite EZ BurnerInstall Trim and Controls with Riello Burner Page Section III Packaged Boiler Assembly Remove CrateRemove Boiler from Skid Do not drop boiler. Do not bump boiler jacket against floorPage Page Steam or Water Boilers Install Safety or Relief Valve in Tapping M Inspect Nozzle and ElectrodesSection IV Water Boiler Piping and Trim Evaluate the Existing Water SystemPage Recommended Water Piping for Circulator Zoned Heating System Page Page Section V Steam Boiler Piping and Trim Evaluate the Existing Steam SystemPage Section VI Tankless and Indirect Water Heater Piping GPM Alliance Water Heater Piping with V8 Boiler Connect Alliance Indirect Water Heater Piping as shown in BDo not exceed maximum allowable air intake length Section VII Venting and AIR Intake PipingGeneral Venting Guidelines Recommended Vent Pipe Arrangement and Chimney Requirements Seal all external joints with weatherproof caulk Section Viii Electrical GeneralBoiler Sequence of Operation with Probe Lwco Page Page Jumper Page Page Boiler Sequence of Operation with Float Lwco Page Page Boiler Sequence of Operation Page Page Boiler Sequence of Operation Page Page Boiler Sequence of Operation Page Page Section IX OIL Piping Single Pipe OIL LinesTWO Pipe OIL Lines SINGLE-STAGE Units 3450 RPM TWO Pipe SystemsFill Heating System with Water Always Inspect Installation Before Starting BurnerSection X System START-UP Adjust OIL Burner Before Starting Beckett BurnersCarlin 102CRD Burners Carlin Elite EZ BurnersStart OIL Burner Adjust OIL Burner While OPERATING. flame presentRiello Burners L1 and V1 Head Electrode Check for Clean CUT OFF of Burner Test ControlsCAD Cell Resistance When Sensing Flame Aquastat Switching Action Within L8124C Control Jumper must be removed after this checkAquastat Switching Action Within L8148A Controls Avoid Breathing Fiber Particulates and Dust Section XI Maintenance and Service Instructions Maintenance of LOW Water CUT- OFF DevicesPage Frequent Water Addition Gal/Month V83 V85 V87 V89 V84 V86 V88 14½Page Section XII Boiler Cleaning Clean the Flueways See FigureClean TOP of Boiler Sections if cleaning from the top Clean the Combustion ChamberCleaning of Boiler Flueways OIL Primary Control Section Xiii Trouble ShootingCombustion Section XIV Repair Parts Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly Bare Boiler Assembly 1BBJacket Assembly Page V83 Thru V89 Steam Boilers Trim and Controls V83 Thru V89 Steam Boilers Trim and Controls V82 Thru V89 Water Boilers Trim and Controls V82 Thru V89 Water Boilers Trim and Controls Beckett AFG Burner Beckett OIL Burner Part NOS. for V8 Series Boilers Beckett OIL Burner Part NOS. for V8 Series Boilers Carlin OIL Burner Part Numbers for V8 Series Boilers Burner Specifications XV. LOW Water CUT OFF Lwco WhenService Record Limited Warranty For Residential Cast Iron Steam Boilers

V8 Series specifications

The Burnham V8 Series is a prestigious line of oil-fired boilers renowned for their efficiency, reliability, and advanced design features. Tailored for residential and light commercial applications, this series exemplifies the perfect blend of tradition and modern technology, ensuring long-term performance and comfort for users.

One of the hallmark features of the Burnham V8 Series is its exceptional cast iron construction, which provides durability and superior heat retention. This robust design allows for an extended lifespan while ensuring that the boiler can withstand the rigors of daily use. The cast iron sections are engineered to facilitate optimal heat transfer and efficiency.

The V8 Series boasts an impressive fuel efficiency rating, often exceeding 85%. This high efficiency is achieved through a combination of advanced combustion technology and the boiler's thoughtful design, which minimizes heat loss. Users benefit not only from lower energy bills but also from a reduced environmental footprint, making the Burnham V8 Series a sustainable choice for heating solutions.

In terms of technology, the Burnham V8 Series features a standing pilot ignition system or an optional intermittent ignition device that enhances safety and efficiency. The advanced burner design allows for smooth operation and excellent fuel utilization, further contributing to the overall economy of the system.

Another notable characteristic is the versatility of the Burnham V8 Series. It can be easily adapted to work with various heating systems, including hot water heating applications. Its compatibility with different fuels, such as natural gas or oil, gives users the flexibility to choose the best energy source for their needs, providing longevity and value.

The installation process is made straightforward with ample connectivity options for plumbing and flue. Its compact design enables easier placement within homes or commercial spaces without compromising performance. Furthermore, the boiler is backed by extensive warranties, ensuring peace of mind for homeowners and businesses alike.

In conclusion, the Burnham V8 Series stands out as a reliable and efficient heating solution, blending robust construction with advanced technology. Its commitment to performance, versatility, and efficiency makes it an excellent choice for meeting the heating demands of various applications while promoting environmental responsibility. Whether for a single-family home or a light commercial building, the Burnham V8 Series remains a trusted leader in the industry.