Ariston 47-116-15 installation instructions Initial START-UP Operational Adjustments

Page 17

3.4.INITIAL START-UP

3.5OPERATIONAL ADJUSTMENTS

THE CHECKS TO BE RUN BEFORE INITIAL START-UP ARE AS FOLLOWS:

1.Make sure that:

-the screw on the automatic air valve has been loosened when the system is full;

-If the water pressure in the system is below 1 bar, bring it up to the appropriate level;

-Check to see whether the gas cock is closed;

-Make sure that the electrical connection has been made properly and that the earth wire is connected to an efficient earthing system;

-Supply power to the boiler by turning the On/Off switch “A” (see FIG.3.1) - the L.E.D. “D” will illuminate - turn the selector knob “C” to the winter /central heating position. This will start the circulation pump. After 7 seconds, the boiler will signal a shutdown due to ignition failure. Leave the boiler as it is until all of the air has been bled from the lines.

-Loosen the cap on the head of the pump to eliminate any air pockets;

-Repeat the procedure for bleeding the radiators of air;

-Open the taps for a brief period;

-Check the system pressure and, if it has dropped, open the filling loop again to bring the pressure back up to 1 bar.

2.Check the exhaust flue for the fumes produced by combustion.

3.Make sure that all gate valves are open;

4.Turn on the gas cock and check the seals on the connections, including the one for the burner, making sure that the meter does not signal the passage of gas. Check the connections with a soap solution and eliminate any leaks.

5.Press the reset button “A” for the lighting system; the spark will light the main burner. If the burner does not light the first time, repeat the procedure.

6.Check the minimum and maximum pressure values for the gas going to the burner; adjust it if needed using the values indicated in the table in section 4 (See the relative section for burner pressure adjustment within the servicing manual).

(See section 3.2 for references) it is possible to:

-Set the temperature of the heating system by adjusting the knob “C”

-Set the temperature of the domestic hot water by turning knob “B”

-The selector knob “G” allows the user to choose the economy mode (position “E”) or the comfort mode (position “C”).

The economy mode is the normal state for the operation of the boiler, since the domestic water is heated up only when a tap is turned on.

The comfort mode is a special operating state, because the water contained in the secondary exchanger and in the primary exchanger is kept in a preheated condition, thereby allowing a quicker delivery of domestic water when required. The latter is therefore the more

convenient choice.

To access the areas in which adjustments are made, it is necessary to open the control panel, as indicated in section 3.3, then remove the rear inspection cover by unscrewing the two screws. Access is thereby provided to the P.C.B. and to the following components:

1.the power supply cable connector;

2.the fuses;

3.the soft-light potentiometer the setting for which can range from the minimum thermal power to the maximum;

4.the maximum thermal heating power potentiometer adjustable by the minimum to maximum power (already calibrated in the factory to 70% of the maximum thermal power);

5.the potentiometer for adjusting the ignition delay (anti-cycling) feature, which can be set from 0 to 2 minutes (set in the factory at one minute);

6.the time clock connector.

17

Image 17
Contents Installation Instructions Type C Boilers Table of Contents General Information Overall View Installation Overall Dimensions Supply must be fused at 3 a Domestic Water Kent TN9 1RA Morley RoadTonbridge 80 mm Systems Restrictor Extension Piping not insulated Piping insulatedRestrictor No Restrictor Extension Piping not insulated Piping insulatedCalculating the lengths of the pipes, Electrical Diagram Central Heating Return Commissioning Control Panel Initial START-UP Operational Adjustments Status ANTI-FROST Device Methane Liquid Gas Butane GAS AdjustmentsG20 Gas G30 16.0Maintenance Boiler MiscellaneousProgrammer Manufacturer Merloni TermoSanitari SpA Italy Technical Service Hot Line 01494Technical Information Servicing Instructions Type C Boilers Fault Finding Removing the front panel Servicing InstructionsRemoving the side panels Removing the sealed chamber frontal coverRemoving the electrodes Removing the combustion coverRemoving the burner and jets Removing the main heat exchanger Removing the fan Removing the air pressure switchSetting the minimum and the maximum power of the boiler Setting the gas pressuresSetting the maximum heating circuit power Setting pressure for soft ignitionRegulating the heating power for Propane gas G31 Regulating the heating power for Natural gas G20Regulating the heating power for Butane gas G30 Removing the spark generator Removing the D.H.W. secondary exchanger Removing the gas valveRemoving the automatic air vent Removing the safety valveRemoving the main circuit flow switch Removing the pump Removing the expansion vessel Removing the pressure gaugeRemoving the heating temperature sensor N.T.C Removing the D.H.W. temperature sensor N.T.CRemoving the D.H.W. flow switch Removing the overheat thermostatRemoving the time clock Checking the fusesRemoving the P.C.B Finding diagrams described in this chapter Fault FindingYES YES ∆ P 1.2 mbar YES Electrical Diagrams MicroGENUS 23/27 Mffi MicroGENUS 23/27 Mffi Ariston Page Manufacturer Merloni TermoSanitari SpA Italy Microgenus 27 Mffi Cod Part Code Description 998924 Panel combustion chamber front 571770 Main flow switch top cap