Ariston 47-116-15 GAS Adjustments, Methane Liquid Gas Butane, G20 Gas G30, 16.0

Page 20

4.GAS ADJUSTMENTS

CATEGORY II2H3+

 

Methane Gas

Liquid Butane Gas

Liquid Propane Gas

 

 

G20

G30

G31

 

 

 

 

 

Lower Wobbe Index (15°C;1013mbar)

MJ/m3h

45.67

80.58

80.58

Nominal Delivery Pressure

mbar

20

29

37

Minimum Delivery Pressure

mbar

17

20

25

23 MFFI

 

 

 

 

Main Burner: n. 13 jets (ø )

mm

1.30

0.77

0.77

Consumption (15°C; 1013mbar)

mc/h

2.72

----

----

Consumption (15°C; 1013mbar)

Kg/h

----

2.02

2.02

Gas Cock Outlet Pressure

 

 

 

 

max - min

mbar

11.0 - 2.0

(*) - 6.0

(*) - 6.0

27 MFFI

 

 

 

 

Main Burner: n. 15 jets (ø )

 

1.30

0.77

0.77

Consumption (15°C; 1013mbar)

mc/h

3.15

----

----

Consumption (15°C; 1013mbar)

Kg/h

----

2.34

2.31

Gas Cock Outlet Pressure:

 

 

 

 

max - min

mbar

11.0 - 1.6

(*) - 4.6

(*) - 6.0

 

 

 

 

 

[1 mbar = 10,197 mmc.a.]

4.1CHANGING THE TYPE OF GAS

The outlet pressure of the gas cock is obtained by completely loosening the screw on the solenoid. The maximum pressure of the gas to the burner will be equal to the nominal delivery pressure minus the head loss within the gas valve.

The boiler can be converted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an Authorised Service Centre.

The operations that must be performed are the following:

1.Replace the jets on the main burner (see table in section 4);

2.Adjust the maximum and minimum thermal capacity values for the boiler (see table in section 4);

3.Replace the gas rating plate;

4.Adjust the maximum thermal power setting;

5.Adjust the soft-light feature;

6.Adjust the ignition delay feature for the heating system (can be set from 0 to 2 mins.).

CATEGORY II2H3+

Methane

Liquid

Liquid

 

Gas

Butane

Propane

 

G20

Gas

Gas

 

 

G30

G31

Recommended Soft-

 

 

 

light Pressure

8.0

16.0

16.0

(mbar)

 

 

 

 

 

 

 

20

Image 20
Contents Installation Instructions Type C Boilers Table of Contents General Information Overall View Installation Overall Dimensions Supply must be fused at 3 a Domestic Water Kent TN9 1RA Morley RoadTonbridge 80 mm Restrictor Extension Piping not insulated Piping insulated SystemsRestrictor No Restrictor Extension Piping not insulated Piping insulatedCalculating the lengths of the pipes, Electrical Diagram Central Heating Return Commissioning Control Panel Initial START-UP Operational Adjustments Status ANTI-FROST Device GAS Adjustments Methane Liquid Gas ButaneG20 Gas G30 16.0Maintenance Miscellaneous BoilerProgrammer Manufacturer Merloni TermoSanitari SpA Italy Technical Service Hot Line 01494Technical Information Servicing Instructions Type C Boilers Fault Finding Servicing Instructions Removing the front panelRemoving the sealed chamber frontal cover Removing the side panelsRemoving the electrodes Removing the combustion coverRemoving the burner and jets Removing the main heat exchanger Removing the air pressure switch Removing the fanSetting the gas pressures Setting the minimum and the maximum power of the boilerSetting the maximum heating circuit power Setting pressure for soft ignitionRegulating the heating power for Propane gas G31 Regulating the heating power for Natural gas G20Regulating the heating power for Butane gas G30 Removing the spark generator Removing the gas valve Removing the D.H.W. secondary exchangerRemoving the automatic air vent Removing the safety valveRemoving the main circuit flow switch Removing the pump Removing the pressure gauge Removing the expansion vesselRemoving the D.H.W. temperature sensor N.T.C Removing the heating temperature sensor N.T.CRemoving the D.H.W. flow switch Removing the overheat thermostatChecking the fuses Removing the time clockRemoving the P.C.B Fault Finding Finding diagrams described in this chapterYES YES ∆ P 1.2 mbar YES Electrical Diagrams MicroGENUS 23/27 Mffi MicroGENUS 23/27 Mffi Ariston Page Manufacturer Merloni TermoSanitari SpA Italy Microgenus 27 Mffi Cod Part Code Description 998924 Panel combustion chamber front 571770 Main flow switch top cap