Ariston 47-116-15 installation instructions ∆ P 1.2 mbar

Page 45

C

 

 

 

 

IS THE

NO

 

 

 

AIR PRESSURE SWITCH

 

 

 

ACTIVATED?

 

 

 

 

YES

CHECK

P

1.2 mbar 1 - Check A.P. switch cable

P ON TEST

 

PRESSURE

 

 

2 - Check/replace A.P. switch

 

 

 

3 - Check/replace P.C.B.

 

INTAKE

 

 

 

 

 

 

 

 

 

1 - Check exhaust discharge

 

P 1.2 mbar

 

2 - Check venturi & pipes

 

 

 

 

 

 

 

 

3 - Check fan efficiency

 

 

 

 

1 - Check/replace ignition

IS FLUE

 

 

 

electrode

NO

 

 

2 - Check ignition cable

DISCHARGE

 

 

 

 

3 - Check spark generator

NORMAL?

 

 

 

 

 

 

4 - Check ignition electrode

 

 

 

 

 

 

 

 

cable

YES

 

 

 

5 - Check/replace P.C.B.

 

 

 

 

 

 

 

 

1 - Check power supply of

 

 

 

 

gas valve

IS THE BURNER

NO

 

 

2 - Check/replace P.C.B.

 

 

3 - Check efficiency of

ALIGHT?

 

 

 

 

 

 

 

gas valve

YES

 

 

 

4 - Replace gas valve

 

 

 

 

HAS THE

 

 

 

1 - Check if flame strikes

 

 

 

detection electrode

BOILER SAFETY

YES

 

 

2 - Check soft-light gas

SHUTDOWN BEEN

 

 

pressure

ACTIVATED?

 

 

 

3 - Check/replace detection

 

 

 

 

electrode

NO

 

 

 

4 - Check/replace P.C.B.

 

 

 

 

D

 

 

 

HAS THE

 

NO

BOILER SAFETY

 

SHUTDOWN BEEN

 

 

 

 

ACTIVATED?

 

 

 

 

YES

 

 

 

 

Shutdown L.E.D. off

 

 

 

 

fan restarts

 

 

 

 

FC004Ad

B063

 

 

 

21

Image 45
Contents Installation Instructions Type C Boilers Table of Contents General Information Overall View Installation Overall Dimensions Supply must be fused at 3 a Domestic Water Morley Road TonbridgeKent TN9 1RA 80 mm Systems Restrictor Extension Piping not insulated Piping insulatedRestrictor No Restrictor Extension Piping not insulated Piping insulatedCalculating the lengths of the pipes, Electrical Diagram Central Heating Return Commissioning Control Panel Initial START-UP Operational Adjustments Status ANTI-FROST Device Methane Liquid Gas Butane GAS AdjustmentsG20 Gas G30 16.0Maintenance Boiler MiscellaneousProgrammer Technical Service Hot Line 01494 Technical InformationManufacturer Merloni TermoSanitari SpA Italy Servicing Instructions Type C Boilers Fault Finding Removing the front panel Servicing InstructionsRemoving the side panels Removing the sealed chamber frontal coverRemoving the combustion cover Removing the burner and jetsRemoving the electrodes Removing the main heat exchanger Removing the fan Removing the air pressure switchSetting the minimum and the maximum power of the boiler Setting the gas pressuresSetting the maximum heating circuit power Setting pressure for soft ignitionRegulating the heating power for Natural gas G20 Regulating the heating power for Butane gas G30Regulating the heating power for Propane gas G31 Removing the spark generator Removing the D.H.W. secondary exchanger Removing the gas valveRemoving the safety valve Removing the main circuit flow switchRemoving the automatic air vent Removing the pump Removing the expansion vessel Removing the pressure gaugeRemoving the heating temperature sensor N.T.C Removing the D.H.W. temperature sensor N.T.CRemoving the D.H.W. flow switch Removing the overheat thermostatRemoving the time clock Checking the fusesRemoving the P.C.B Finding diagrams described in this chapter Fault FindingYES YES ∆ P 1.2 mbar YES Electrical Diagrams MicroGENUS 23/27 Mffi MicroGENUS 23/27 Mffi Ariston Page Manufacturer Merloni TermoSanitari SpA Italy Microgenus 27 Mffi Cod Part Code Description 998924 Panel combustion chamber front 571770 Main flow switch top cap