Ariston 47-116-15 Removing the gas valve, Removing the D.H.W. secondary exchanger

Page 35

Removing the gas valve

1.Disconnect all the cables from the solenoid and modureg;

2.Remove the spark generator (see previous section);

3.Release the top nut “W” (FIG. 1.30);

4.Remove the screws “X” from the bottom of the gas valve pipe (FIG. 1.31);

5.Remove the gas valve (FIG. 1.32).

W

47.eps

FIG. 1.30

X X

48.eps

FIG. 1.31

 

 

38.eps

FIG. 1.32

1.6ACCESS TO THE WATER CIRCUIT

Important! Before any component is removed, the boiler must be drained of all water.

Removing the D.H.W. (secondary) exchanger

1.Remove the screws “Y” (FIG 1.33 + FIG 1.34);

2.Push the exchanger towards the rear of the boiler, and lift upwards and remove out of the front of the boiler

(FIG 1.35);

3.Before replacing the exchanger ensure that the O-rings are in good condition and replace if necessary.

Y

22.eps

FIG. 1.33

Y

21.eps

FIG. 1.34

 

 

68.eps

FIG. 1.35

B063

11

Image 35
Contents Installation Instructions Type C Boilers Table of Contents General Information Overall View Installation Overall Dimensions Supply must be fused at 3 a Domestic Water Kent TN9 1RA Morley RoadTonbridge 80 mm Extension Piping not insulated Piping insulated Restrictor Extension Piping not insulated Piping insulatedSystems Restrictor No RestrictorCalculating the lengths of the pipes, Electrical Diagram Central Heating Return Commissioning Control Panel Initial START-UP Operational Adjustments Status ANTI-FROST Device 16.0 GAS AdjustmentsMethane Liquid Gas Butane G20 Gas G30Maintenance Boiler MiscellaneousProgrammer Manufacturer Merloni TermoSanitari SpA Italy Technical Service Hot Line 01494Technical Information Servicing Instructions Type C Boilers Fault Finding Removing the front panel Servicing InstructionsRemoving the side panels Removing the sealed chamber frontal coverRemoving the electrodes Removing the combustion coverRemoving the burner and jets Removing the main heat exchanger Removing the fan Removing the air pressure switchSetting pressure for soft ignition Setting the gas pressuresSetting the minimum and the maximum power of the boiler Setting the maximum heating circuit powerRegulating the heating power for Propane gas G31 Regulating the heating power for Natural gas G20Regulating the heating power for Butane gas G30 Removing the spark generator Removing the D.H.W. secondary exchanger Removing the gas valveRemoving the automatic air vent Removing the safety valveRemoving the main circuit flow switch Removing the pump Removing the expansion vessel Removing the pressure gaugeRemoving the overheat thermostat Removing the D.H.W. temperature sensor N.T.CRemoving the heating temperature sensor N.T.C Removing the D.H.W. flow switchRemoving the time clock Checking the fusesRemoving the P.C.B Finding diagrams described in this chapter Fault FindingYES YES ∆ P 1.2 mbar YES Electrical Diagrams MicroGENUS 23/27 Mffi MicroGENUS 23/27 Mffi Ariston Page Manufacturer Merloni TermoSanitari SpA Italy Microgenus 27 Mffi Cod Part Code Description 998924 Panel combustion chamber front 571770 Main flow switch top cap