Ariston 47-116-15 installation instructions Overall View

Page 4

5 - If called for by point. 3, dismantling and cleaning of the combustion chamber.

6 - If called for by point. 4, dismantling and cleaning of the burner jets.

7 - Visual check of the primary heat exchanger:

-check for overheating in the blade assembly;

-clean the exhaust fan if needed.

8 - Adjustment of the flow rate of the gas: flow rate for lighting, partial load and full load.

9 - Check of the heating safety systems:

-safety device for maximum temperature;

-safety device for maximum pressure.

10- Check of the gas safety systems:

-safety device for lack of gas or flame ionisation (detection electrode);

-safety device for gas cock.

11- Check of the electrical connection (make sure it complies with the instructions in the manual).

12- Check of domestic hot water production efficiency (flow rate and temperature) 13- General check of the combustion by-products of the discharge/ventilation

system.

14- Check of the general performance of the unit.

FIG. 1.0

1.2 OVERALL VIEW

LEGEND:

1. Flue connector

2. Air intake for twin pipe flue systems

3. Fan

4. Combustion chamber hood

5. Main heat exchanger

6. Safety thermostat

7. Combustion chamber

8. Combustion chamber insulation panel

9. Burner

10. Detection electrode

11. Ignition electrodes

12. Motorised diverter valve

13. Main circuit temperature probe

14. Main circuit flow switch

15. Domestic hot water temperature probe

16. Gas valve

17. Spark generator

18. Domestic hot water flow switch

19. Domestic cold water inlet filter

20. Secondary heat exchanger

21. Circulation pump with automatic air release valve

22. Safety valve (3 bar)

23. Expansion vessel

24. Air pressure switch

25. Combustion analysis intakes

IN013A

4

Image 4
Contents Installation Instructions Type C Boilers Table of Contents General Information Overall View Installation Overall Dimensions Supply must be fused at 3 a Domestic Water Tonbridge Morley RoadKent TN9 1RA 80 mm Restrictor Extension Piping not insulated Piping insulated SystemsRestrictor No Restrictor Extension Piping not insulated Piping insulatedCalculating the lengths of the pipes, Electrical Diagram Central Heating Return Commissioning Control Panel Initial START-UP Operational Adjustments Status ANTI-FROST Device GAS Adjustments Methane Liquid Gas ButaneG20 Gas G30 16.0Maintenance Miscellaneous BoilerProgrammer Technical Information Technical Service Hot Line 01494Manufacturer Merloni TermoSanitari SpA Italy Servicing Instructions Type C Boilers Fault Finding Servicing Instructions Removing the front panelRemoving the sealed chamber frontal cover Removing the side panelsRemoving the burner and jets Removing the combustion coverRemoving the electrodes Removing the main heat exchanger Removing the air pressure switch Removing the fanSetting the gas pressures Setting the minimum and the maximum power of the boilerSetting the maximum heating circuit power Setting pressure for soft ignitionRegulating the heating power for Butane gas G30 Regulating the heating power for Natural gas G20Regulating the heating power for Propane gas G31 Removing the spark generator Removing the gas valve Removing the D.H.W. secondary exchangerRemoving the main circuit flow switch Removing the safety valveRemoving the automatic air vent Removing the pump Removing the pressure gauge Removing the expansion vesselRemoving the D.H.W. temperature sensor N.T.C Removing the heating temperature sensor N.T.CRemoving the D.H.W. flow switch Removing the overheat thermostatChecking the fuses Removing the time clockRemoving the P.C.B Fault Finding Finding diagrams described in this chapterYES YES ∆ P 1.2 mbar YES Electrical Diagrams MicroGENUS 23/27 Mffi MicroGENUS 23/27 Mffi Ariston Page Manufacturer Merloni TermoSanitari SpA Italy Microgenus 27 Mffi Cod Part Code Description 998924 Panel combustion chamber front 571770 Main flow switch top cap