Crown Boiler CWI138, CWI172, CWI345, CWI310 Removing an Existing Boiler from a Common Chimney

Page 10

sealed tight.

13)Do not install the vent damper in any portion of the vent system which is used by appliances other than the boiler being installed.

14)Vent damper installation is mandatory on all CWI boiler models except the CWI310-CWI379. Install vent damper (see Figure 9) as follows:

a)Open vent damper carton and remove installation instructions. Read the instructions thoroughly before proceeding. Verify that vent damper is same size as draft diverter outlet. See Figure 1. Unpack vent damper carefully. Do not force closed damper blade. Forcing vent damper closed may result in damaged gear train and void warranty.

b)Vent damper is factory shipped having approximately ¾” diameter hole in the vent damper blade, which must be left open for boilers equipped with standing pilot, and should be plugged on boilers with an intermittent pilot, using the plug supplied with the damper.

Mount the vent damper on the flue collar without modification to either and secure with sheet metal screws. Make sure screws do not interfere with damper blade operation. Vent damper blade position indicator must be visible to users.

c)The damper wire harness is shipped wired into the boiler junction box. Plug the loose end of this harness into the damper and secure the flexible conduit to the damper using a connector nut provided.

d)Install vent connector pipe and vent fittings from vent damper outlet to chimney or gas vent. Secure with sheet metal screws and support as required.

Removing an Existing Boiler from a Common Chimney

In some cases, when an existing boiler is removed from a common chimney, the common venting system may be too large for the remaining appliances. At the time of removal of an existing boiler the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.

a)Seal any unused opening in the common venting system.

b)Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

c)Insofar as practical, close all building doors and windows and all doors between the space in which all the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

d)Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will operate continuously.

e)Test for spillage at the draft hood relief opening after five (5) minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.

f)After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliances to their previous condition of use.

g)Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z223.1.

10

9

Image 10
Contents Models Gas-Fired Natural Draft Water Boilers INSTALLATION INSTRUCTIONSCWI Series These instructions must be affixed on or adjacent to the boilerTable of Contents I Product DescriptionFIGURE 1 CWI BOILERS - GENERALCONFIGURATION II SpecificationsTABLE 1 CWI SPECIFICATIONS III Before Installing IV Locating the BoilerV Air for Combustion and Ventilation ForBuildingsofUnusuallyTightConstruction For Buildings of Other than Unusually Tight ConstructionExample FIGURE 4 ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC FIGURE3BOILERINSTALLEDINCONFINEDSPACE, ALL AIR FROM INSIDEFIGURE 5 ALL AIR FROM OUTDOORS VIA VENTILATED ATTIC FIGURE 6 ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM VI Venting Removing an Existing Boiler from a Common Chimney FIGURE8 CWI BOILERTYPICALVENTSYSTEM INSTALLATION AND COMPONENTS FIGURE 9 VENT DAMPER INSTALLATION DETAILSVII Gas Piping StandardPiping VIII System PipingDANGER 1413 Piping for Special SituationsFIGURE 11 STANDARD BOILER PIPING FIGURE 12 INDIRECT WATER HEATER BOILERSIDEPIPINGFIGURE13 BOILERBYPASSPIPING FIGURE14 ISOLATIONOFBOILERFROMSYSTEMWITHAHEATEXCHANGER FIGURE15 BOILERPIPINGWITHCHILLERIX TANKLESS HEATER PIPING Feel water before showering or bathing A mixing valve does not eliminate the risk of scaldingFIGURE 17TANKLESSHEATERPIPING IX Wiring SingleZoneWiringFIGURE 20 WIRING DIAGRAM, STANDING PILOT WITH TANKLESS HEATER Wiring Variations FIGURE23ZONEWIRINGUSINGHONEYWELLV8043FZONEVALVES FIGURE 22 CIRCULATOR ZONEWIRING USING HONEYWELLR845AsFACTORY BOILER WIRING NOT SHOWN - SEE FIGURES 18 FACTORYWIRING NOT SHOWN - SEE FIGURES 18Sequence of Operation, Standing Pilot, Less Tankless Heater CWI Control System - Sequence of OperationSequence of Operation, Standing Pilot, With Tankless Heater Sequence of Operation, Intermittent Ignition, Less Tankless Heater Sequence of Operation, Intermittent Ignition, With Tankless HeaterXI Start-up and Checkout Safety Control Operation - Standing Pilot and Intermittent Ignition2726 FIGURE 24 STANDING PILOT BURNER FLAMEPage Page TO TURN OFF GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE OPERATINGLIGHTING INSTRUCTIONS LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELLLIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH ROBERTSHAW FOR YOUR SAFETY READ BEFORE LIGHTING7000ERHC SERIES GAS VALVES STANDING PILOT TO TURN OFF GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS VR8204 AND VR8304 SERIES GAS VALVES INTERMITTENT PILOT7000DERHC SERIES GAS VALVES INTERMITTENT PILOT FIGURE 27a GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOT FIGURE 28b GASVALVEDETAIL-ROBERTSHAW 7000DERHC INTERMITTENT IGNITIONXI Service and Maintenance Heat Exchanger Cleaning Procedure XIII Troubleshooting START C1&C2?5&6 on National Fuel Gas CodeSTART L2 ?T&TV? C1&C2?C2 and Standing Pilot Ignition System Troubleshooting Chart Caution Read page 36 before attempting to use this chartIntermittent Ignition System Troubleshooting Chart XIV PARTS Page 1/4 Pilot Tubing Used with Robertshaw Valves These Valves Piped in Series to Provide Redundent Shut-off40mm BURNERS ONLY Page KEY # Page B. BaseAssembly Preparation Appendix A Knockdown Boiler Assembly InstructionsA. Before Installing C. Heat Exchanger and Flue Collector InstallationFIGUREA1 BASE, HEAT EXCHANGER, FLUE COLLECTORASSEMBLY D. Gas Valve Installation E. Control and Trim InstallationFIGURE A2 JACKET INSTALLATION F. Electrical Wiring Connections G. Complete InstallationFIGURE A3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES 3633 I. Street P.O. BoxPhiladelphia