Safety Control Operation - Standing Pilot and Intermittent Ignition
High Limit - Interrupts main burner operation when the supply water temperature exceeds set point. Maximum allowable tempera- ture is 250°F. If the high limit opens, the vent damper will close if the damper switch is in the “automatic” position. The circulator will continue to operate as long as there is a call for heat, regardless of the status of the high limit (if the boiler is equipped with a tankless coil, the low limit switch will prevent the circulator from operating if the boiler water temperature is too low). Burner operation automatically resumes when the supply water temperature falls below set point.
Blocked Vent (“Spill”) Switch - Automatically interrupts main burner operation in the event that flue gas spills from the draft diverter opening. This switch is equipped with a reset button which must be pressed to restore normal burner operation. An open blocked vent switch is indicative of a problem with the vent system. If the blocked vent switch opens, the cause of the venting problem must be found and corrected by a qualified gas service technician before the blocked vent switch is reset.
Flame
XI Start-up and Checkout
NOTE
SAFE LIGHTING AND OTHER PERFORMANCE CRITERIA WERE MET WITH THE GAS MANIFOLD AND CONTROL ASSEMBLY PROVIDED ON THE BOILER WHEN THE BOILER UNDERWENT THE TESTS SPECIFIED IN Z21.13.
Use the following procedure for initial
1)Make sure that the boiler and system are filled with water.
2)Check all new gas piping for leaks and purge piping sections that are filled with air. See Part 4 of the National Fuel Gas Code for additional information on testing and purging gas lines.
3)Verify that vent system is complete and free of obstructions before attempting to fire boiler.
4)Inspect all wiring for loose or uninsulated connections.
5)Make sure the main burners are seated properly in the rear of burner tray and on orifices.
6)Adjust thermostat to the highest setting.
7)Start the boiler using the appropriate lighting instructions for the gas valve on the boiler on pages
8)Upon initial
9)Observe pilot burner flame:
•See Figure 24 for standing pilot. Pilot burner should produce single steady medium blue flame covering around 3/8” to ½” of thermocouple tip.
•See Figure 25 for intermittent ignition. Pilot burner produces three flames. The center one should be a steady medium blue flame covering around 3/8” to ½” of spark electrode/flame rod.
26
25