F. Electrical Wiring Connections
(Also refer to wiring diagrams in Part X of the installation manual)
1)A
2)Blocked Vent Switch - Locate the two wires marked “8”. Connect these wires to the terminals on the blocked vent switch (it does not matter which of these wires is connected to which terminal on the blocked vent switch). Install the strain relief provided in the hole in the jacket through which these wires pass.
3)Flame
a)Route the wire marked “10” through the bushing located on the left jacket panel and connect it to one side of the flame
b)Route the wire marked “7” through the bushing located on the left jacket panel and connect it to the other side of the flame
4)Standing Pilot Gas Valve (Honeywell VR8200, VR8300 or Robertshaw Model
Note: Boilers equipped with the Robertshaw 7000ERHC are also equipped with a Honeywell Model V8295 gas valve to provide redundancy. This valve should be factory
5)Honeywell Intermittent Ignition System:
a)Mount the S8600 series ignition control to the left side of the jacket just above the gas manifold using the standoff bracket supplied and #10 sheet metal screws.
b)Locate the intermittent ignition harness plugged into the gas valve assembly. This harness has red, blue, and yellow wires and has molex plugs on both ends. Plug the loose end of the harness into the S8600 module.
c)Plug the green burner ground wire numbered “4” to terminal 4 on the S8600. Check that the ground wire has been routed under the burners and that the other end is attached to the pilot assembly under the lower mounting screw.
d)Plug the red wire with the yellow trace, numbered “5”, to terminal 5 on the S8600 module.
e)Plug the black wire with the white trace, numbered “6”, to terminal 6 on the S8600 module.
f)Plug the orange Pilot Ignition Cable, numbered “9”, to terminal 9 on the S8600 module. Verify that this cable has been routed under the burners and that the other end is plugged onto the pilot assembly electrode.
G. Complete Installation
Follow the instructions that start on page 1 of this manual to complete boiler installation.