FIGURE26a: MAINBURNERFLAME-1”BURNERS

FIGURE26b:MAINBURNERFLAME-40mm

(“HIGH ALTITUDE”) BURNERS

WARNING

FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT IN OVER-FIRING OF THE BOILER AND A CARBON MONOXIDE HAZARD.

15)Check the manifold pressure and adjust if necessary. To do this, use the following procedure:

a)Connect a manometer to the inlet pressure tap on the gas valve (see Figures 27 and 28).

b)Check the inlet pressure with all gas appliances on and off. The inlet pressure at the boiler must be within the following limits regardless of what combination of appliances is firing:

Inlet Press (inches w.c.)

Natural Gas

LPGas

Min.

5.0

11.0

Max.

14.0

13.0

If the inlet pressure falls outside of these limits, find and correct the cause of the problem before proceeding further.

c)Connect a manometer to the manifold (outlet) pressure tap on the gas valve (see Figures 27 and 28).

d)Read the manifold pressure. It should be set at:

 

Natural Gas

LPGas

Manifold Press. (inches w.c.)

3.5

10.0

e)If a manifold pressure adjustment is needed, make the adjustment by turning the pressure regulator (see Figures 27 and 28) screw clockwise to raise the pressure and counter clockwise to reduce the pressure. If a manifold pressure adjustment is made, recheck the line pressure to be certain that it is still within acceptable limits. Replace the cover screw on the regulator.

28

27

Image 28
Contents Gas-Fired Natural Draft Water Boilers INSTALLATION INSTRUCTIONS CWI SeriesModels These instructions must be affixed on or adjacent to the boilerTable of Contents I Product DescriptionFIGURE 1 CWI BOILERS - GENERALCONFIGURATION II SpecificationsTABLE 1 CWI SPECIFICATIONS III Before Installing IV Locating the BoilerV Air for Combustion and Ventilation ForBuildingsofUnusuallyTightConstruction For Buildings of Other than Unusually Tight ConstructionExample FIGURE 4 ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC FIGURE3BOILERINSTALLEDINCONFINEDSPACE, ALL AIR FROM INSIDEFIGURE 5 ALL AIR FROM OUTDOORS VIA VENTILATED ATTIC FIGURE 6 ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM VI Venting Removing an Existing Boiler from a Common Chimney FIGURE8 CWI BOILERTYPICALVENTSYSTEM INSTALLATION AND COMPONENTS FIGURE 9 VENT DAMPER INSTALLATION DETAILSVII Gas Piping StandardPiping VIII System PipingDANGER 1413 Piping for Special SituationsFIGURE 11 STANDARD BOILER PIPING FIGURE 12 INDIRECT WATER HEATER BOILERSIDEPIPINGFIGURE13 BOILERBYPASSPIPING FIGURE14 ISOLATIONOFBOILERFROMSYSTEMWITHAHEATEXCHANGER FIGURE15 BOILERPIPINGWITHCHILLERIX TANKLESS HEATER PIPING Feel water before showering or bathing A mixing valve does not eliminate the risk of scaldingFIGURE 17TANKLESSHEATERPIPING IX Wiring SingleZoneWiringFIGURE 20 WIRING DIAGRAM, STANDING PILOT WITH TANKLESS HEATER Wiring Variations FIGURE 22 CIRCULATOR ZONEWIRING USING HONEYWELLR845As FACTORY BOILER WIRING NOT SHOWN - SEE FIGURES 18FIGURE23ZONEWIRINGUSINGHONEYWELLV8043FZONEVALVES FACTORYWIRING NOT SHOWN - SEE FIGURES 18Sequence of Operation, Standing Pilot, Less Tankless Heater CWI Control System - Sequence of OperationSequence of Operation, Standing Pilot, With Tankless Heater Sequence of Operation, Intermittent Ignition, Less Tankless Heater Sequence of Operation, Intermittent Ignition, With Tankless HeaterXI Start-up and Checkout Safety Control Operation - Standing Pilot and Intermittent Ignition2726 FIGURE 24 STANDING PILOT BURNER FLAMEPage Page FOR YOUR SAFETY READ BEFORE OPERATING LIGHTING INSTRUCTIONSTO TURN OFF GAS TO APPLIANCE LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELLLIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH ROBERTSHAW FOR YOUR SAFETY READ BEFORE LIGHTING7000ERHC SERIES GAS VALVES STANDING PILOT FOR YOUR SAFETY READ BEFORE LIGHTING OPERATING INSTRUCTIONSTO TURN OFF GAS TO APPLIANCE VR8204 AND VR8304 SERIES GAS VALVES INTERMITTENT PILOT7000DERHC SERIES GAS VALVES INTERMITTENT PILOT FIGURE 27a GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOT FIGURE 28b GASVALVEDETAIL-ROBERTSHAW 7000DERHC INTERMITTENT IGNITIONXI Service and Maintenance Heat Exchanger Cleaning Procedure XIII Troubleshooting START C1&C2?5&6 on National Fuel Gas CodeSTART L2 ?T&TV? C1&C2?C2 and Standing Pilot Ignition System Troubleshooting Chart Caution Read page 36 before attempting to use this chartIntermittent Ignition System Troubleshooting Chart XIV PARTS Page 1/4 Pilot Tubing Used with Robertshaw Valves These Valves Piped in Series to Provide Redundent Shut-off40mm BURNERS ONLY Page KEY # Page Appendix A Knockdown Boiler Assembly Instructions A. Before InstallingB. BaseAssembly Preparation C. Heat Exchanger and Flue Collector InstallationFIGUREA1 BASE, HEAT EXCHANGER, FLUE COLLECTORASSEMBLY D. Gas Valve Installation E. Control and Trim InstallationFIGURE A2 JACKET INSTALLATION F. Electrical Wiring Connections G. Complete InstallationFIGURE A3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES 3633 I. Street P.O. BoxPhiladelphia