Crown Boiler CWI310, CWI172, CWI345, CWI103, CWI276 CWI Control System - Sequence of Operation

Page 24

CWI Control System – Sequence of Operation

(Refer to Figures 18 - 21 for ladder and connection diagrams)

Sequence of Operation, Standing Pilot, Less Tankless Heater

1)When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damper. Assuming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close.

2)A call for heat from the thermostat energizes relay coil 1R (the relay on the L8148E), causing contacts 1R1 and 1R2 to make. Contact 1R1 starts the circulator. Contact 1R2 sends power to the high limit.

3)Assuming that the high limit is made, current will flow to pin terminal #2 (orange) at the vent damper and the damper will open.

4)Once the vent damper is fully open, an end switch inside the damper will make, energizing pin #3 (red) at the damper. This pin is connected through the damper harness to terminal “B1” on the L8148E. At this point in the operating sequence, 24 volts is present across “B1” and “B2”.

5)Under normal conditions, the flame roll-out switch and blocked vent switch are made. Voltage will therefore immediately appear across the combination gas control (“gas valve”) terminals “TH” and “TR”.

6)When the boiler is first placed into operation, the pilot must be lit. The pilot heats a thermocouple which generates a small amount of electricity sufficient to hold open the safety shut-off valve in the combination gas control. The circuit connecting the thermocouple and the safety shut-off valve is self contained and completely independent of all other wiring on the boiler. This safety shut-off valve is upstream of the 24 volt valves in the gas control which open in response to a call for heat. If the pilot is not lit, the safety shut-off valve will remain closed and gas will not reach the 24 volt valves.

7)Assuming that the pilot is established and proven by the thermocouple, the application of 24 volts across the combination gas valve terminals energizes the redundant 24 volt solenoid valves in the combination gas control, resulting in gas flow through the control and burner operation.

Sequence of Operation, Standing Pilot, With Tankless Heater

1)When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damper. Assuming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close.

2)If the boiler water temperature is less than the low limit setting minus the differential setting, terminals “R” and “B” in the L8124E are made through the low limit switch. The low limit switching action is SPDT with “R” being common. “R” and “W” are therefore open whenever “R” and “B” are made. This means that while “R” and “B” are made relay coil R1 is deenergized, regardless of whether or not there is a call for heat. The circulator will therefore not operate if the boiler water temperature is too low to generate domestic hot water.

3)Assuming that the high limit is made, current will flow to terminal “B1” on the L8124E and then to terminal “2” (orange) at the vent damper and the damper will open.

4)Once the vent damper is fully open, an end switch inside the damper will make, energizing pin #3 (red) at the damper. The red wire from this pin runs to the flame rollout switch.

5)Under normal conditions, the flame roll-out switch and blocked vent switch are made. Voltage will therefore immediately appear across the combination gas control (“gas valve”) terminals “TH” and “TR”.

6)When the boiler is first placed into operation, the pilot must be lit. The pilot heats a thermocouple which generates a small amount of electricity sufficient to hold open the safety shut-off valve in the combination gas control. The circuit connecting the thermocouple and the safety shut-off valve is self contained and completely independent of all other wiring on the boiler. This safety shut-off valve is upstream of the 24 volt valves in the gas control which open in response to a call for heat. If the pilot is not lit, the safety shut-off valve will remain closed and gas will not reach the 24 volt valves.

7)Assuming that the pilot is established and proven by the thermocouple, the application of 24 volts across the combination gas valve terminals energizes the redundant 24 volt solenoid valves in the combination gas control, resulting in gas flow through the control and burner operation.

8)The boiler will fire until the boiler water temperature is approximately equal to the low limit setting. Once the water temperature reaches this point, “R” and “B” open and “R” and “W” make. At this point, a call for heat will energize 1R, making contacts 1R1 and 1R2. Contacts 1R1 energize the circulator. Contacts 1R2 switch current from the “hot” side of the transformer second- ary to the high limit switch. If the high limit is made, current flows to terminal “B1” and the ignition sequence is then the same as it is for a call for burner operation from the low limit (see (3) above).

24

23

Image 24
Contents Gas-Fired Natural Draft Water Boilers INSTALLATION INSTRUCTIONS CWI SeriesModels These instructions must be affixed on or adjacent to the boilerTable of Contents I Product DescriptionII Specifications FIGURE 1 CWI BOILERS - GENERALCONFIGURATIONTABLE 1 CWI SPECIFICATIONS III Before Installing IV Locating the BoilerV Air for Combustion and Ventilation For Buildings of Other than Unusually Tight Construction ForBuildingsofUnusuallyTightConstructionExample FIGURE3BOILERINSTALLEDINCONFINEDSPACE, ALL AIR FROM INSIDE FIGURE 4 ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTICFIGURE 5 ALL AIR FROM OUTDOORS VIA VENTILATED ATTIC FIGURE 6 ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM VI Venting Removing an Existing Boiler from a Common Chimney FIGURE8 CWI BOILERTYPICALVENTSYSTEM INSTALLATION AND COMPONENTS FIGURE 9 VENT DAMPER INSTALLATION DETAILSVII Gas Piping VIII System Piping StandardPipingDANGER 1413 Piping for Special SituationsFIGURE 11 STANDARD BOILER PIPING FIGURE 12 INDIRECT WATER HEATER BOILERSIDEPIPINGFIGURE13 BOILERBYPASSPIPING FIGURE14 ISOLATIONOFBOILERFROMSYSTEMWITHAHEATEXCHANGER FIGURE15 BOILERPIPINGWITHCHILLERIX TANKLESS HEATER PIPING A mixing valve does not eliminate the risk of scalding Feel water before showering or bathingFIGURE 17TANKLESSHEATERPIPING IX Wiring SingleZoneWiringFIGURE 20 WIRING DIAGRAM, STANDING PILOT WITH TANKLESS HEATER Wiring Variations FIGURE 22 CIRCULATOR ZONEWIRING USING HONEYWELLR845As FACTORY BOILER WIRING NOT SHOWN - SEE FIGURES 18FIGURE23ZONEWIRINGUSINGHONEYWELLV8043FZONEVALVES FACTORYWIRING NOT SHOWN - SEE FIGURES 18CWI Control System - Sequence of Operation Sequence of Operation, Standing Pilot, Less Tankless HeaterSequence of Operation, Standing Pilot, With Tankless Heater Sequence of Operation, Intermittent Ignition, Less Tankless Heater Sequence of Operation, Intermittent Ignition, With Tankless HeaterXI Start-up and Checkout Safety Control Operation - Standing Pilot and Intermittent Ignition2726 FIGURE 24 STANDING PILOT BURNER FLAMEPage Page FOR YOUR SAFETY READ BEFORE OPERATING LIGHTING INSTRUCTIONSTO TURN OFF GAS TO APPLIANCE LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELLFOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH ROBERTSHAW7000ERHC SERIES GAS VALVES STANDING PILOT FOR YOUR SAFETY READ BEFORE LIGHTING OPERATING INSTRUCTIONSTO TURN OFF GAS TO APPLIANCE VR8204 AND VR8304 SERIES GAS VALVES INTERMITTENT PILOT7000DERHC SERIES GAS VALVES INTERMITTENT PILOT FIGURE 27a GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOT FIGURE 28b GASVALVEDETAIL-ROBERTSHAW 7000DERHC INTERMITTENT IGNITIONXI Service and Maintenance Heat Exchanger Cleaning Procedure XIII Troubleshooting START C1&C2?5&6 on National Fuel Gas CodeSTART L2 ?C1&C2? T&TV?C2 and Standing Pilot Ignition System Troubleshooting Chart Caution Read page 36 before attempting to use this chartIntermittent Ignition System Troubleshooting Chart XIV PARTS Page These Valves Piped in Series to Provide Redundent Shut-off 1/4 Pilot Tubing Used with Robertshaw Valves40mm BURNERS ONLY Page KEY # Page Appendix A Knockdown Boiler Assembly Instructions A. Before InstallingB. BaseAssembly Preparation C. Heat Exchanger and Flue Collector InstallationFIGUREA1 BASE, HEAT EXCHANGER, FLUE COLLECTORASSEMBLY D. Gas Valve Installation E. Control and Trim InstallationFIGURE A2 JACKET INSTALLATION F. Electrical Wiring Connections G. Complete InstallationFIGURE A3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES P.O. Box 3633 I. StreetPhiladelphia