Crown Boiler CWI Series, CWI172, CWI345, CWI310, CWI103, CWI276 2726, Standing Pilot Burner Flame

Page 27
FIGURE 24: STANDING PILOT BURNER FLAME

FIGURE 24: STANDING PILOT BURNER FLAME

FIGURE 25: INTERMITTENT IGNITION PILOT BURNER FLAME

10)Make sure vent damper is in open position when main burners are firing.

11)Inspect the main burner flames visible through the observation port in burner access panel. The flame should be stable and mostly blue (see Figure 26). No yellow tipping should be present; however, intermittent flecks of yellow and orange in the flame are normal.

12)Check entire gas train for leaks using soap and water or other approved leak detection method while boiler is firing. Fix any leaks found immediately.

WARNING

NEVER USE A FLAME TO CHECK FOR GAS LEAKS.

MAKE SURE THAT THE AREA AROUND THE BOILER IS CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS.

DAMPER MUST BE IN OPEN POSITION WHEN APPLIANCE MAIN BURNER IS OPERATING.

13)Run gas valve safety shutdown test:

For standing pilot boiler models, disconnect the thermocouple from gas valve. Both pilot burner and main burners should stop firing.

For intermittent ignition boiler models, with main burners firing, disconnect ignition cable from ignition module. Both pilot burner and main burners should stop firing.

2726

Image 27
Contents These instructions must be affixed on or adjacent to the boiler Gas-Fired Natural Draft Water Boilers INSTALLATION INSTRUCTIONSCWI Series ModelsI Product Description Table of ContentsII Specifications FIGURE 1 CWI BOILERS - GENERALCONFIGURATIONTABLE 1 CWI SPECIFICATIONS IV Locating the Boiler III Before InstallingV Air for Combustion and Ventilation For Buildings of Other than Unusually Tight Construction ForBuildingsofUnusuallyTightConstructionExample FIGURE3BOILERINSTALLEDINCONFINEDSPACE, ALL AIR FROM INSIDE FIGURE 4 ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTICFIGURE 5 ALL AIR FROM OUTDOORS VIA VENTILATED ATTIC FIGURE 6 ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM VI Venting Removing an Existing Boiler from a Common Chimney FIGURE 9 VENT DAMPER INSTALLATION DETAILS FIGURE8 CWI BOILERTYPICALVENTSYSTEM INSTALLATION AND COMPONENTSVII Gas Piping VIII System Piping StandardPipingDANGER Piping for Special Situations 1413BOILERSIDEPIPING FIGURE 11 STANDARD BOILER PIPING FIGURE 12 INDIRECT WATER HEATERFIGURE13 BOILERBYPASSPIPING FIGURE15 BOILERPIPINGWITHCHILLER FIGURE14 ISOLATIONOFBOILERFROMSYSTEMWITHAHEATEXCHANGERIX TANKLESS HEATER PIPING A mixing valve does not eliminate the risk of scalding Feel water before showering or bathingFIGURE 17TANKLESSHEATERPIPING SingleZoneWiring IX WiringFIGURE 20 WIRING DIAGRAM, STANDING PILOT WITH TANKLESS HEATER Wiring Variations FACTORYWIRING NOT SHOWN - SEE FIGURES 18 FIGURE 22 CIRCULATOR ZONEWIRING USING HONEYWELLR845AsFACTORY BOILER WIRING NOT SHOWN - SEE FIGURES 18 FIGURE23ZONEWIRINGUSINGHONEYWELLV8043FZONEVALVESCWI Control System - Sequence of Operation Sequence of Operation, Standing Pilot, Less Tankless HeaterSequence of Operation, Standing Pilot, With Tankless Heater Sequence of Operation, Intermittent Ignition, With Tankless Heater Sequence of Operation, Intermittent Ignition, Less Tankless HeaterSafety Control Operation - Standing Pilot and Intermittent Ignition XI Start-up and CheckoutFIGURE 24 STANDING PILOT BURNER FLAME 2726Page Page LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELL FOR YOUR SAFETY READ BEFORE OPERATINGLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEFOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH ROBERTSHAW7000ERHC SERIES GAS VALVES STANDING PILOT VR8204 AND VR8304 SERIES GAS VALVES INTERMITTENT PILOT FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE7000DERHC SERIES GAS VALVES INTERMITTENT PILOT FIGURE 28b GASVALVEDETAIL-ROBERTSHAW 7000DERHC INTERMITTENT IGNITION FIGURE 27a GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOTXI Service and Maintenance Heat Exchanger Cleaning Procedure XIII Troubleshooting C1&C2? STARTNational Fuel Gas Code 5&6 onL2 ? STARTC1&C2? T&TV?C2 and Caution Read page 36 before attempting to use this chart Standing Pilot Ignition System Troubleshooting ChartIntermittent Ignition System Troubleshooting Chart XIV PARTS Page These Valves Piped in Series to Provide Redundent Shut-off 1/4 Pilot Tubing Used with Robertshaw Valves40mm BURNERS ONLY Page KEY # Page C. Heat Exchanger and Flue Collector Installation Appendix A Knockdown Boiler Assembly InstructionsA. Before Installing B. BaseAssembly PreparationFIGUREA1 BASE, HEAT EXCHANGER, FLUE COLLECTORASSEMBLY E. Control and Trim Installation D. Gas Valve InstallationFIGURE A2 JACKET INSTALLATION G. Complete Installation F. Electrical Wiring ConnectionsFIGURE A3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES P.O. Box 3633 I. StreetPhiladelphia