Hearth and Home Technologies CD4842MLR, CD4842MR Troubleshooting, Standing Pilot Ignition System

Page 58

15 Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service technician in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician. Con- tact your dealer to arrange a service call by a qualified service technician.

A. Standing Pilot Ignition System

Symptom

Possible Causes

Corrective Action

1. After repeated triggering

A. No gas or low gas pressure.

Check the remote shut-off valves from the appliance. Usually, there

of the red or black piezo

 

is a valve near the gas main. There can be more than one valve

ignitor button, the spark

 

between the appliance and the main.

ignitor will not light the

B. No lp in tank.

Check the LP (propane) tank. You may be out of fuel.

pilot. Check for spark.

C. Ignitor.

Check the spark at the electrode and pilot. If no spark and electrode

 

 

 

wire is properly connected, replace the ignitor. Verify that there is

 

 

no short in electrode wire.

 

D. Pilot or misaligned electrode

Using match, light the pilot. If the pilot lights, turn off the pilot and

 

(spark at electrode).

trigger the piezo ignitor button again. If the pilot lights, an improper

 

 

gas/air mixture caused the bad lighting and a longer purge period

 

 

is recommended. If the pilot will not light, ensure the gap at the

 

 

electrode and pilot is one-eighth inch to have a strong spark. If the

 

 

gap is OK, replace the pilot.

 

 

 

2. The pilot will not stay lit

A. Thermocouple.

Check that the pilot flame impinges on the thermocouple. Adjust the

after carefully following the

 

pilot for proper flame impingement.

lighting instructions.

 

 

 

Ensure that the thermocouple connection at the gas valve is fully

 

 

 

 

inserted and tight (hand tighten plus 1/4 turn).

 

 

Verify proper voltage output from the thermocouple to the valve.

 

 

Place one millivolt meter lead wire on the thermocouple copper

 

 

lead. Place the second lead wire on the solder button on the back

 

 

of the valve (blue wire). Start the pilot and hold the valve knob in.

 

 

The millivolt reading should read 8-16 millivolts. If millivolt reading

 

 

is less than 8 millivolts, replace thermocouple.

 

 

 

 

B. Improper gas inlet pressure.

Natural gas should be 5-14 in. w.c. LP should be 10-14 in. w.c.

 

 

Verify pressure with manometer.

 

C. Control valve.

If the thermocouple is producing 8-16 millivolts, replace control

 

 

valve.

3. The pilot is burning, there

A. On/off switch or wires

Check the ON/OFF switch and wires for proper connections. Place

is no burner flame, the

defective.

the jumper wires across the terminals at the switch. If the burner

valve knob is in the ON

 

comes on, replace the defective switch. If the switch is OK, place

position, and the ON/OFF

 

the jumper wires across the switch wires at the gas valve. If the

switch is in the ON

 

burner comes on, the wires are faulty or connections are bad.

position.

 

 

 

 

 

 

B. Thermopile may not be

Check that the pilot flame impinges thermopile properly.

 

generating sufficient

Be sure the wire connections from the thermopile at the gas valve

 

millivoltage.

 

terminals are tight and that the thermopile is fully inserted into the

 

 

 

 

pilot bracket.

 

 

Check the thermopile with a millivolt meter. Take the reading at

 

 

TH-TP&TP terminals of the gas valve. The meter should read 350

 

 

millivolts minimum, while holding the valve knob depressed in the

 

 

pilot position, with the pilot lit, and the ON/OFF switch in the OFF

 

 

position. Replace the thermopile if the reading is below the specified

 

 

minimum.

 

 

 

 

 

With the pilot in the ON position, disconnect the thermopile leads

 

 

from the valve. Take a reading at the thermopile leads. The reading

 

 

should be 350 millivolts minimum. Replace the thermopile if the

 

 

reading is below the minimum.

 

 

 

58

Heatilator • Caliber Mesh CD Series-SIT Valve • 4040-849 Rev J • 06/08

Image 58
Contents Direct Vent Gas Appliance Installation and OperationModels CD4236MR CD4842MR What to do if you smell gasCongratulations Homeowner Reference InformationInstaller Guide Table of ContentsUser Guide Troubleshooting Appliance SetupReference Materials Gas Appliance Fireplace Limited Lifetime Warranty Limited Lifetime WarrantyListing and Code Approvals Requirements for the Commonwealth of Massachusetts Operating Instructions Gas Fireplace SafetyYour Fireplace Fan Kit optional Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceFor Your Safety Read Before Lighting Lighting Instructions IPIStanding LightingPilot Frequently Asked Questions After Fireplace is LitRemote Control Maintenance and ServiceMaintenance Tasks-Homeowner Doors, Surrounds, FrontsMaintenance Tasks-Qualified Service Technician Getting Started Typical Appliance SystemTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Select Appliance Location Framing and ClearancesModel # Construct the Appliance Chase ClearancesMantels Mantel and Wall ProjectionsMantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesMinimum Clearances for Termination Vent Table Key Vent Information and DiagramsApproved Pipe Use of ElbowsTop Vent Horizontal Termination Vent DiagramsOne Elbow Two 45 Elbows replacing One 90 Elbow Two ElbowsInstalled Vertically Three ElbowsTop Vent Vertical Termination No Elbow12 ft 3.66 m min 60 ft 18.29 m max Rear Vent Horizontal Termination One 45 ElbowTwo Elbows Rear Vent Vertical Termination Min Ft 1.83 m max 12 ft 3.66 m min 60 ft 18.29 m max Install Vertical Termination Baffle 17 Flat BaffleWall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Combustible Wall PenetrationInstall the Ceiling Firestop Installing Ceiling FirestopFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Appliance Preparation Convert from Top Vent to Rear VentOuter Collar, Remove Four Screws 11 Place Outer Collar on Rear of Appliance 16 Cover Plate-Replace Secure and Level the Appliance 20 Proper Positioning, Leveling And Securing Of AnAssemble Pipe Sections DVP Only Install Vent PipeAttach Pipe to the Firebox Assembly Assemble Pipe SectionsAssemble Vent Sections SLP Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 SLP-FSInstall Decorative Wall Components SLP only Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination Install Horizontal Termination Cap InteriorGas Pressure Gas InformationFuel Conversion Gas ConnectionIntellifire Ignition System Wiring Wiring RequirementsStanding Pilot Ignition System Wiring Optional Accessories RequirementsElectrical Service and Repair WSK-MLT-HTLJunction Box Installation Wall Switch Installation for Fan OptionalFacing Material FinishingCombustible Appliance Setup Removing Fixed Glass Assembly Install the Log AssemblyReplacing Fixed Glass Assembly Install Hood Install TrimInstall Clean Face Components Install Top Latch CoverInstall Bottom Latch Cover Air Shutter SettingInstall Firescreen Assembly Troubleshooting Standing Pilot Ignition SystemSymptom Possible Cause Corrective Action Intellifire Ignition System Will not ignite. If the pilot Appliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP Vent ComponentsBEK DVP-BEK2 DVP-TVHW DVP-TRAP DVP-HRC-SS Effective SL-2DVP Adapter#22 Log/Grate Assembly ServiceParts CD4842M Series Parts Service CD4842M SeriesOptional Components Model # Description Contact Information