1. Top Vent - Horizontal Termination - (continued)
Two Elbows
Note: Use SLP Series components only.
Note: There MUST be a 25% re- duction in total H when using flex vent except when using the sim- ple up and out installation (see Figure 7.3).
V1 Minimum** | H1 + H2 Maximum | ||
90 Elbow Only** | 1/2 ft. | 152 mm | |
|
|
|
|
1/2 ft.** | 152 mm | 1 ft. | 305 mm |
457 mm | 2 ft. | 610 mm | |
762 mm | 4 ft. | 1.2 m | |
|
|
|
|
1.1 m | 6 ft. | 1.8 m | |
|
|
|
|
1.4 m | 14 ft. | 4.3 m |
H1 + H2 MAX. =14 ft. (4.3 m)
V1 + H1 + H2 MAX. = 40 ft. (12.2 m)
**See Warning Below.
H2
INSTALLED
HORIZONTALLY
WARNING**
Fire Risk.
•When using
•When using
H1
V1
Figure 7.5
Hearth & Home Technologies • DV3732SBI, DV3732SBIL • | 25 |