18.0 Fault Finding
I
1.
2.
Check the gas supply pressure: For Natural Gas greater than 10 - 11 mbar
Check and correct if necessary
1.The mechanical set of the gas valve (CO2 values - see instruction)
2.Flame sensing electrode and lead connections
3.Flame sensing electrode position
Flame current should be more than 0.5 μA
YES
Replace PCB
NO
Replace flame sensing electrode
J
1. | Overheat thermostat operated or | NO |
|
| Allow to cool. Continuity | YES |
| ||||
|
|
| Replace safety thermostat | ||||||||
| faulty, i.e. continuity across |
|
|
| across thermostat terminals |
|
| ||||
|
|
| |||||||||
| thermostat terminals |
|
|
| more than 1.5 ohm |
|
|
| |||
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Replace PCB |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
K
| Is there 230V at: |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| YES |
|
|
|
|
1. |
|
|
|
|
|
|
|
|
|
| |
| Motor |
|
|
| Replace motor | ||||||
|
|
| NO | ||||||||
2. |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||
| PCB - X3 connector terminals |
| Replace PCB |
| |||||||
|
|
|
|
| |||||||
|
| 5 | & 6 central heating mode |
|
|
|
|
| |||
|
|
|
|
|
|
| |||||
|
| 5 | & 7 domestic hot water mode |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| YES |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Change pump supply cable |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
L
M
1.
1.
Fan connections correct at fan.
PCB - X401 connector terminals 5,6,7 & 8
Temperature sensors faulty.
Cold resistance approximately
YES
NO
Replace fan
10kΩ @ 25° C (CH sensor) 20kΩ @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)
Replace sensor
2.
If pump is running the heat exchanger could be obstructed
YES
Replace heat exchanger
© Baxi Heating UK Ltd 2008 | 57 |