Termination to an internal soil and
Boiler
vent pipe
| 50mm | per |
|
|
|
|
| metre | |||
|
|
| of | ||
|
|
|
|
| pipe |
2.5° | Minimum |
|
| run | |
|
|
| |||
|
|
|
| ||
|
| fall |
|
|
|
|
|
|
|
|
|
Fig. 13 | 450mm min |
|
External termination via internal discharge
Boilerbranch
e.g sink waste - downstream
7.0Site Requirements
7.7Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run.
1.The condensate outlet will accept 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
2.Ensure the discharge of condensate complies with any national or local regulations in force.
BS 6798:2000 & Part H1 of the Building Regulations give further guidance.
Sink
Fig. 14
50mm | per |
|
| metre |
|
| of | |
|
| pipe |
2.5° | Minimum | run |
| ||
|
| |
| fall |
|
Pipe must terminate above water level but below surrounding surface
3. | The discharge pipe should be run in a proprietary drain pipe |
material e.g. PVC, | |
4. | Metal pipework is NOT suitable for use in condensate |
discharge systems. | |
5. | The pipe should be a minimum of 21.5mm diameter and |
must be supported using suitably spaced clips to prevent | |
sagging. | |
6. | It is advisable to keep the condensate pipe internal. |
7. | External runs greater than 3 metres or runs in cold areas |
should use 32mm waste pipe. |
Termination to a drain or gully
Boiler
Pipe must terminate above water level but below surrounding surface
50mm | per |
| |
|
| metre |
|
|
| of |
|
|
| pipe | |
2.5° | Minimum | run | |
| |||
|
|
| |
|
| fall |
|
Fig. 15
Termination to a purpose made soak-
away
8. If the boiler is fitted in an unheated location the entire |
condensate discharge pipe should be treated as an external |
run. |
9. In all cases discharge pipe must be installed to aid disposal |
of the condensate. To reduce the risk of condensate being |
trapped, as few bends and fittings as possible should be used. |
10. When discharging condensate into a soil stack or waste |
pipe the effects of existing plumbing must be considered. If soil |
pipes or waste pipes are subjected to internal pressure |
fluctuations when WC's are flushed or sinks emptied then |
cause appliance lockout. |
Examples are shown of the following methods of termination:-
i) to an internal soil & vent pipe - Fig. 13 |
Boiler
50mm | per |
| |
|
| metre |
|
|
| of |
|
|
| pipe | |
2.5° | Minimum | run | |
| |||
|
|
| |
|
| fall |
|
500mm min
Holes in the
ii) via an internal discharge branch (e.g. sink waste) - Fig. 14 |
iii) to a drain or gully - Fig. 15 |
iv) to a purpose made soakaway - Fig. 16 |
Fig. 16
© Baxi Heating UK Ltd 2008 | 17 |