Santa Fe Pellet Stove

c. Vertical

Rain Cap

Flashing

24 in. (610mm) Minimum

We recommend a minimum of 60 in. (1524mm) vertical, however above the eave is preferred.

Both installations are approved for mobile home installations. Must use 3 or 4 inch (76 to 102mm) “L” or “PL” Listed pellet venting or Listed double wall pipe and Quadra-Fire Outside Air Kit in mobile homes. Single wall pipe is approved for residential instal-

Firestop

Ceiling Support

6in.

(152mm)

Min.

6 in. (152mm) Class A Chimney Connector Adapter

 in. (76mm) Min.

6 in. (152mm) Flue Connector

 in. to 6 in.

(76-152mm) Top Vent Kit

lations only.

Cleanout Cover

Non-combustible Hearth Pad

Figure 14.1

d. Through The Wall & Vertical

Rain Cap

 

Flashing

 

24 in. (610mm) minimum

 

Support Bracket

2 in. (51mm) minimum

every 60 in. (1524mm)

6 in. (152mm)

Wall Thimble

 

minimum

 

 

Tee

 

Cleanout Cover

Non-combustible Hearth Pad

Figure 14.2

Page 14

7001-142D

September 1, 2008

Image 14
Contents Santa FE Pellet Stove Location Back side of left side panel Santa Fe Pellet StoveSerial Number Model Name Table of Contents Listing and Code Approvals Appliance Location Design, Installation & Location Fire Safety ConsiderationsGetting Started Thermostat LocationSanta Fe Pellet Stove Tools And Supplies Needed Inspect Appliance & Components and Pre-Use Check List3Dimensions and Clearances Appliance DimensionsSanta Fe Pellet Stove Clearances to Combustibles UL and ULC Hearth Pad Requirements Exception for Horizontal InstallationsSanta Fe Pellet Stove Hearth Pad Requirements UL and ULC Chimney and Exhaust Connection Venting Termination RequirementsExample of 3 Elbow-Rear Vent Termination Calculaton Pipe Selection ChartSanta Fe Pellet Stove Equivalent Feet of Pipe Venting Systems AlcoveSanta Fe Pellet Stove Through The Wall Straight OutDegree Santa Fe Pellet Stove Vertical Through The Wall & VerticalMasonry Alternate MasonryMobile Home 7Appliance Set-Up Outside Air Kit InstructionsInstalling the Top Vent Adapter Santa Fe Pellet Stove Top Vent Adapter InstallationRear Vent and Rear Vent to Top Vent Adapter Installation Notch Thermocouple Cover Included in Kit 1 Grille Installing the GrilleInstalling the Trim Ring Santa Fe Pellet Stove Thermostat Installation Operating Instructions Fuel Size And Material General Operating InformationFeed Adjustment Control Rod Wing Nut Set Screw Fire CharacteristicsFeed Rate Adjustment Instructions Santa Fe Pellet Stove Before Your First FireFrequently Asked Questions Santa Fe Pellet Stove Iginition CyclesPossible Cause Corrective Action TroubleshootingSymption Page Page Frequency Daily Weekly Monthly Yearly Quick Reference Maintenance ChartMaintaining & Servicing Your Appliance Types of FuelAsh Removal from Firebox Cleaning Firepot with Cleaning Rod & Firepot ScraperCleaning Ash Pan Disposal of Ashes Frequency As neededCleaning Beneath Heat Exchanger Cont’d Cleaning Heat Exchanger Chambers & Drop TubeCleaning Beneath Heat Exchanger Cleaning the Exhaust PathCleaning Convection Blower Requires No Lubrication Cleaning the GlassCleaning Exhaust Blower Requires No Lubrication Door Latch InspectionSanta Fe Pellet Stove High Ash Fuel Content Maintenance Immediate Attention and Cleaning is RequiredConvection Blower Replacement Exhaust Blower ReplacementSnap Disc #2 Replacement Wing NutIgniter Replacement Baffle & Brick Replacement Glass Replacement Reference Materials Snap Disc #1 Convection Blower 110F Vacuum SwitchWiring Harness See .1 below Snap Disc #2 Fuel Delivery Interrupt 250FSanta Fe Pellet Stove Component Locations Santa Fe Pellet Stove Exploded Views Description Part NumberDescription Nbr Santa Fe Pellet Stove Service Parts and Accessories Item # Service Parts Description Part NbrAccessory Description Part Number LVGRL-SF-NLSanta Fe Pellet Stove Service And Maintenance Log Date of Service Performed By Description of ServiceSanta Fe Pellet Stove Warranty Policy CONDITIONS, Exclusions & Limitation of LiabilityHearth & Home Technologies Limited Warranty Cont’d Contact Information Telephone