Sequence Of Operation Flow Chart
If tank temperature drops below Operating Set Point minus
Differential setting a heating cycle is activated
| Control System performs diagnostic checks |
|
|
|
|
|
| Control System Locks Out | ||||
Normal State of all pressure switches and ECO are checked |
|
|
|
|
| |||||||
| NO |
|
| |||||||||
| Blower Prover pressure switch verified open |
|
|
|
|
| Displays Fault Msg | |||||
|
|
|
|
|
|
| ||||||
All other pressure switches and ECO are verified closed |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Combustion Blower is energized |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Control System Locks Out |
|
| Blower Prover switch contacts confirmed |
|
|
|
|
|
|
| |||
|
|
| NO |
|
|
|
| “Blower Prover Open” | ||||
|
| closed by control system |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| Fault Msg is displayed | |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Igniter is energized for warm up period |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Does Control System sense minimum |
|
| |
| NO | ||
Igniter amps? |
| ||
|
| ||
|
|
|
|
|
|
|
|
24 Volt Gas Valve is energized gas flows to Main Burner
Is flame sensed at the Main Burner?
(control system monitors the flame sensor)
YESNO
Control System Locks Out “Low Igniter Current” Fault Msg is displayed
2.0 minimum AC amps
Water is heated to
set point
24 Volt Gas Valve
30second
Water heater goes into standby mode
24 Volt Gas Valve
30second
Retries up to two more times
Control System
Locks Out
“Ignition Failure”
Fault Msg is
displayed
Figure 57
55