COMBUSTION AIR AND VENT SYSTEM REQUIREMENTS

• The connector must be firmly attached and

sealed to prevent it from falling out.

• To aid in removing the connector, a thimble or

slip joint may be used.

• The connector must not extend beyond the

inner edge of the chimney as it may restrict

The following figures are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-current edition and the guidelines set forth by prevailing local codes.

the space between it and the opposite wall of

the chimney

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

FT.

 

 

 

 

 

 

 

 

 

 

 

2 FT. Minimum Above Any Object

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Within 10 FT. Horizontally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support Strap

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain

 

 

 

 

 

 

 

Seal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do Not Extend

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Beyond Edge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Of Chimney

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector

 

 

Slope

Up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Per Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 FT.

Minimum

Support Strap

Maintain

Clearance*

Vent

Connector

Slope Up

1/4 Inch

Per Foot

Minimum

2 FT. Minimum Above

Any Object Within

10 FT. Horizontally

Type B Double

Wall Vent Pipe

**Maintain Specified Clearance

Chimney Termination Vent System

Figure 8.

Do not reduce the vent to less than the draft hood outlet diameter. Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent: Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials.

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent. NOTE: The chimney flue or masonry enclosure size may be too large to allow proper venting.

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Venting Gas Vent System With Type B Double Wall Vent Pipe.

Figure 9.

Consult the table found in the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-current edition to determine the minimum height from roof to lowest discharge opening.

Listed Vent Cap

Maintain Manufacturer’s

Specified Minimum Clearance

Support Strap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**Maintain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specified

Maintain

 

 

 

 

 

 

 

 

 

Seal

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance

Clearance*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slope Up

 

 

 

 

 

 

 

 

 

Unused Chimney

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flue Or Masonry

 

 

 

 

 

 

 

 

 

 

 

 

 

Per Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enclosure

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Venting Through Chimney With Type B Double Wall Vent Pipe.

Figure 10.

*Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections.

10

Image 10
Contents Models ALL Technical and Warranty Questions Service Handbook Tools Required for servicing gas modelsFire or Explosion Harzard Breathing Hazard Carbon Monoxide GasTable of Contents Basic Installation & Operation Installation of Residential GAS Water HeaterCombustion AIR and Vent System Requirements Carbon Monoxide WarningReference Vent Connectors Connector must be firmly attached Electronic Control Display Upper Control Know the Water HEATER’S Component PartsGas Control Valve/Thermostat Lower Control Pressure Switch Burner/Manifold Door AssemblyAir Intake Chamber Fan Power Anode Rod HOW the Water HEATER’S Component Parts are ConnectedWater Heater Operation Sequence of OperationFILLING, Draining and Flushing the Water Heater Tank For Your Safety Read Before Operating Lighting InstructionsAdjusting the Temperature on Electronic Control Display Hotter CoolerFault Code Diagnostics Using the Electronic Control DisplayFault Code Retrieval Reviewing Fault Codes FV-Sense Reset SequenceElectronic Control Display Troubleshooting Electronic Control DisplayControl Display Troubleshooting Control Display Status Problem SolutionLDO-SW, OPEN, and Clean Screen Troubleshooting Flowchart YESCleaning the Air Intake Chamber Screen External Inspection and CleaningCleaning the Combustion Chamber and Air Diverter Assembly Installing the Electronic Control Display Electronic Control Display Removal / ReplacementRemoving the Electronic Control Display Powered Anode ROD Removal / Replacement Removing the Powered Anode RodInstalling the Powered Anode Rod Removing the Pressure Switch Pressure Switch Removal / ReplacementInstalling the Pressure Switch Transformer Removal / Replacement Removing the TransformerInstalling the New Transformer AIR Intake Chamber BOX Removal / Replacement Removing the Air Intake Chamber BoxInstalling the Air Intake Chamber Box Installing the Fan in the Air Intake Chamber Box Wiring Harness Removal / Replacement PressureReplacing the Wiring Harness Installing the New Wiring HarnessUndue Pressure or Sudden Force AIR Intake Chamber FAN Removal / Replacement Removing the Fan from the Air Intake ChamberInstalling the Fan in the Air Intake Chamber Box Pressure Tubing Removal / Replacement Installing the Air Intake Chamber Box Inner DOOR/MANIFOLD/BURNER Assembly Removal / Replacement GAS ControlInstallation Caution Must Be Taken TABFlame SENSE/HOT Surface Igniter Removal / Replacement Replacing the Flame Sense/Hot Surface Igniter AssemblyBurner Removal / Replacement Installing New Burner Removing Old BurnerPressure Burner Orifice Removal / Replacement Installing New Burner Orifice Removing Old Burner OrificeReinstalling The Inner Door/Manifold/Burner Assembly GAS Control VALVE/THERMOSTAT Removal / Replacement Removing the Gas Control Valve/ThermostatInstalling the Gas Control Valve/Thermostat Checking the GAS Supply Pressure Checking the Gas Supply PressureGAS Water Heater Sizing Guide Leakage CheckpointsGeneral Information Formulas and ConversionsMM millimeters =Inches X