
23.Turn on the gas supply to the unit and test the gas supply line and union connections by brushing on an approved noncorrosive leak detection solution (Figure 116).
24.Turn on the electrical and the gas supplies to the water heater. Plug in the electric connection from the transformer to the electric outlet (Figure 113).
25.Restart the water heater by following the directions on the “Lighting and Operating Instructions” label located on the front of the water heater .
26.As the burner is heating (view flames through viewport), test the manifold tube connection at the gas control valve/thermostat by brushing on an approved noncorrosive leak detection solution (IMPORTANT: Do Not splash any solution onto any electrical connections) (Figure 120).
27.Upon verifying proper operation of the water heater, replace the manifold cover/outer door.
Figure 120.
IMPORTANT: |
|
|
WHEN BRUSHING ON AN |
| GAS CONTROL |
APPROVED NONCORROSIVE |
| |
LEAK DETECTION SOLUTION, |
| VALVE/THERMOSTAT |
DO NOT SPLASH SOLUTION |
|
|
ONTO ELECTRICAL CON- |
|
|
NECTIONS. |
|
|
|
| PRESSURE |
MANIFOLD TUBE |
| SWITCH/FAN, |
| FV SENSOR | |
POWER SUPPLY | IGNITER/ | CONNECTOR |
| ||
TRANSFORMER | FLAME |
|
CONNECTOR | SENSE | DISPLAY, ANODE |
| CONNECTOR | ROD CONNECTOR |
CHECKING THE GAS SUPPLY PRESSURE
Checking the Gas Supply Pressure
Gas pressure checks are done with flowing gas using a gas pressure gauge capable of reading pressure in inches of water column.
•Supply gas pressure checks are measured before the gas control valve/thermostat and as close to the water heater as possible.
•Manifold (main burner) gas pressure is measured at the pressure tap on the side of the gas control valve/thermostat. Use an allen wrench to remove the plug then attach the gas gauge.
| GAS CONTROL | |
GAS CONTROL | VALVE/ | |
THERMOSTAT | ||
VALVE/ | ||
THERMOSTAT |
| |
USE AN ALLEN |
| |
WRENCH TO REMOVE |
| |
AND REPLACE PLUG. |
| |
MANIFOLD GAS PRESSURE TEST | GAS | |
| PRESSURE | |
CONNECTED AT | GAUGE | |
| ||
PRESSURE TAP |
| |
SUPPLY GAS PRESSURE TEST |
|
NOTE: Desired gas pressures will be noted on | Figure 121 |
the gas valve label located on the gas control |
|
valve/thermostat. |
|
IF . . . |
| . . . THEN |
supply gas pressure is under desired pressure |
| • increase supply gas pressure regulator setting |
requirement |
| and, |
|
| • increase supply gas piping size. |
supply gas pressure is over desired pressure |
| • add gas pressure regulator. |
|
| • reduce setting on existing regulator. |
manifold gas pressure is more than |
| • ensure there is adequate supply gas pressure |
W.C. from values indicated on gas valve |
| • ensure the main burner orifice is the correct size |
|
| |
|
| for the water heater model being tested. |
|
| • if the above tests have been performed and the |
|
| results were correct replace the gas control valve. |
| 52 |
|