A.O. Smith Guide to Using the Electronic Control Display of GAHH-50 Water Heater

Page 19

USING THE ELECTRONIC CONTROL DISPLAY

Reviewing Fault Codes:

1.Press the red up arrow button one time.

2.The display will show either E0 or E1.

3.If E0 is shown, there are no faults. By pressing the up arrow button again the display will exit the Field Service mode, or the control will exit automatically after no button is pressed for five (5) seconds.

4.If E1 is shown, the control will flash the icons of the most recent fault.

5.Pressing the red up arrow button again will shown how many days ago the fault occurred and continue to flash the corresponding fault icons.

6.Interpreting the day of the fault occurrence is as follows...00 would be today, 01 would be yesterday, up to 14 which would be 14 or more days ago.

7.Continuing to press the up arrow button will scroll through all of the eight (8) most recent faults, if they exist, and its days ago of occurrence.

8.After the last fault is reached the display will return to the first fault (E1) to allow for the faults to be reviewed again.

Exiting Field Service Mode:

• There are three (3) methods to exit the Field Service Mode, Manual, Manual and Clear, and Timed Exit.

1.Manual exit is accomplished by pressing both the red up arrow and the blue down arrow buttons for one (1) second, but less than five (5) seconds while in the Field Service Mode, or by pressing the red up arrow button one (1) time after the “E0” is displayed during fault review while in the Field Service Mode. These methods will return the control to the standard operating mode and retain any fault codes stored in memory.

2.Manual exit and fault clear is accomplished by pressing the red up arrow and the blue down arrow buttons for five (5) seconds while in the Field Service Mode. This method will return the control to the standard operating mode and at the end of the five (5) seconds clear all faults stored in memory and initiate a software reset indicated by all the LCD segments coming on for five (5) seconds. The temperature setting and scale, etc. will not be altered using this method of exit.

3.Timed exit will occur while in the Field Service Mode if the control detects no button presses for a period exceeding five (5) minutes. The control will automatically return to the normal operating mode and keep all fault data retained in memory.

FV-Sense Reset Sequence:

Flammable liquids (such as gasoline, solvents, adhesives, LP gases, etc.) and other substances emit flammable vapors which can be ignited by a gas water heater’s hot surface igniter or main burner. The resulting flashback and fire can cause serious burns to anyone in the area. This water heater is equipped with a FV sensor for detecting the presence of flammable vapors. When the sensor detects those vapors, the unit will shut down and not operate. Even though this water heater is a flammable vapors ignition resistant water heater and designed to reduce the chances of flammable vapors being ignited, gasoline and other flammable substances should never be stored or used in the same vicinity or area containing a gas water heater or other open flame or spark producing appliance.

Figure 23.

FV Sensor

Should the FV-Sensor of this water heater detect the presence of flammable vapors the following FV-Sense Reset Sequence must be entered into the Electronic Control Display. NOTE: BEFORE RESETTING THE

FVIR SENSE IN THE ELECTRONIC CONTROL DISPLAY, THOROUGHLY INSPECT THE AREA AND REMOVE THE SOURCE OF THE FLAMMABLE VAPORS”.

1.Manual reset is accomplished by first turning off the power to the water heater for at least 10 seconds.

2.Then, while pressing the two temperature adjustment buttons on the display, turn the switch on the gas control valve/thermostat to the on position. All the display icons will start to flash. Temporarily release both temperature adjust buttons and within 2 seconds, press both temperatures adjust buttons again until all the display icons are on steady. Release the two temperature adjust buttons. The system will clear the fault, perform a reset, and normal operation will be restored.

19

Image 19
Contents Models ALL Technical and Warranty Questions Tools Required for servicing gas models Service HandbookBreathing Hazard Carbon Monoxide Gas Fire or Explosion HarzardTable of Contents Installation of Residential GAS Water Heater Basic Installation & OperationCarbon Monoxide Warning Combustion AIR and Vent System RequirementsReference Vent Connectors Connector must be firmly attached Electronic Control Display Upper Control Know the Water HEATER’S Component PartsGas Control Valve/Thermostat Lower Control Pressure Switch Burner/Manifold Door AssemblyAir Intake Chamber Fan HOW the Water HEATER’S Component Parts are Connected Power Anode RodSequence of Operation Water Heater OperationFILLING, Draining and Flushing the Water Heater Tank Lighting Instructions For Your Safety Read Before OperatingHotter Cooler Adjusting the Temperature on Electronic Control DisplayFault Code Diagnostics Using the Electronic Control DisplayFault Code Retrieval FV-Sense Reset Sequence Reviewing Fault CodesElectronic Control Display Electronic Control Display TroubleshootingControl Display Status Problem Solution Control Display TroubleshootingLDO-SW, OPEN, and Clean Screen YES Troubleshooting FlowchartCleaning the Air Intake Chamber Screen External Inspection and CleaningCleaning the Combustion Chamber and Air Diverter Assembly Installing the Electronic Control Display Electronic Control Display Removal / ReplacementRemoving the Electronic Control Display Removing the Powered Anode Rod Powered Anode ROD Removal / ReplacementInstalling the Powered Anode Rod Removing the Pressure Switch Pressure Switch Removal / ReplacementInstalling the Pressure Switch Removing the Transformer Transformer Removal / ReplacementInstalling the New Transformer Removing the Air Intake Chamber Box AIR Intake Chamber BOX Removal / ReplacementInstalling the Air Intake Chamber Box Installing the Fan in the Air Intake Chamber Box Pressure Wiring Harness Removal / ReplacementInstalling the New Wiring Harness Replacing the Wiring HarnessUndue Pressure or Sudden Force Removing the Fan from the Air Intake Chamber AIR Intake Chamber FAN Removal / ReplacementInstalling the Fan in the Air Intake Chamber Box Pressure Tubing Removal / Replacement Installing the Air Intake Chamber Box GAS Control Inner DOOR/MANIFOLD/BURNER Assembly Removal / ReplacementTAB Installation Caution Must Be TakenReplacing the Flame Sense/Hot Surface Igniter Assembly Flame SENSE/HOT Surface Igniter Removal / ReplacementBurner Removal / Replacement Removing Old Burner Installing New BurnerPressure Burner Orifice Removal / Replacement Removing Old Burner Orifice Installing New Burner OrificeReinstalling The Inner Door/Manifold/Burner Assembly Removing the Gas Control Valve/Thermostat GAS Control VALVE/THERMOSTAT Removal / ReplacementInstalling the Gas Control Valve/Thermostat Checking the Gas Supply Pressure Checking the GAS Supply PressureLeakage Checkpoints GAS Water Heater Sizing GuideFormulas and Conversions General InformationMM millimeters =Inches X