Mitsubishi Electronics PKA-AFA, PCA-AGA Auto Off Timer, Timer value is visible and appropriate

Page 10

6. Timer

7. After completing steps 3 to 6 above, press the Filter button 4 to lock

Example 2:

 

 

 

in the value.

 

 

 

 

 

 

 

 

 

Start the timer, with OFF time is sooner than ON time

Note:

 

 

 

 

 

 

 

 

 

ON Setting: 5 hours

 

 

 

Your new settings will be cancelled if you press the Mode (Return) button 2

 

OFF Setting: 2 hours

 

 

 

before pressing the Filter

button 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hr

 

 

 

 

8. Press the Mode (Return) button 2 to return to the standard control

 

 

 

 

 

 

 

 

˚F

 

AFTER OFF

 

 

 

At Timer Start

 

 

 

 

˚F

 

 

 

 

 

 

 

 

 

screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

 

Display shows the timer’s OFF setting (hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remaining to OFF).

9. Press the Timer On/Off button 9 to start the timer countdown. When the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

timer is running, the timer value is visible on the display. Be sure that the

 

 

 

 

 

 

 

 

 

At 2 hours after timer start

 

 

 

 

 

 

 

 

 

 

Hr ON

 

 

 

timer value is visible and appropriate.

 

 

 

 

 

 

 

 

 

 

AFTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display changes to show the timer’s ON setting

<Viewing the Current Simple Timer Settings>

 

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

 

(hours remaining to ON).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The time displayed is ON setting (5 hours) –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF setting (2 hours) = 3 hours.

 

§ Timer Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

˚F

 

 

 

 

 

 

At 5 hours after timer start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIMER

 

Hr ON

 

 

 

 

 

 

 

 

˚F

 

 

 

 

 

 

 

The air conditioner comes on, and will continue

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AFTER OFF

 

 

 

¡

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to run until someone turns it off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

6.1.3. Auto Off Timer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Be sure that the simple timer indicator is visible on the screen (at ¡).

This timer begins countdown when the air conditioner starts, and shuts

 

the air conditioner off when the set time has elapsed.

2. Press the Timer Menu button w, so that the “Monitor” appears on the

 

Available settings run from 30 minutes to 4 hours, in 30-minute intervals.

screen (at ).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

• If the ON or OFF simple timer is running, the current timer value will

 

 

 

*1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same time.

appear at §.

 

 

 

 

 

 

 

 

*2. The Auto Off timer will not operate when any of the following conditions is

• If ON and OFF values have both been set, the two values appear

 

in effect.

 

 

 

alternately.

 

 

 

 

 

 

 

 

 

The timer is off; the system is in malfunction state; a test run is in progress;

3. Press the Mode (Return) button 2to close the monitor display and return

 

the remote controller is undergoing self-check or remote controller check;

to the standard control screen.

 

 

 

 

 

 

the user is in the process of selecting a function; the user is in the process

 

 

 

 

 

 

of setting the timer; the system is under central control. (Under these con-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<To Turn Off the Simple Timer...>

 

 

 

 

 

 

ditions, On/Off operation is prohibited.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the Timer On/Off button 9 so that the timer setting no longer ap- pears on the screen (at ).

 

AFTER

OFF

˚F

 

˚F

 

SIMPLE

 

AUTO OFF

TEMP. ON/OFF

<To Turn On the Simple Timer...>

 

 

 

 

 

w

Press the Timer On/Off button 9 so that the timer setting becomes visible

 

MENU

ON/OFF

FILTER

4

 

 

 

 

at .

BACK

MONITOR/SET

DAY

CHECK TEST

 

 

 

 

 

 

 

PAR-21MAA

CLOCK

OPERATION CLEAR

 

 

 

 

Hr ON

AFTER

˚F

˚F

SIMPLE

2 q 9

Examples

 

 

 

 

 

<How to Set the Auto Off Timer>

If ON and OFF times have both been set at the simple timer, operation and

 

 

£ Timer Setting

display are as indicated below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example 1:

 

 

 

 

 

 

 

 

 

 

 

AFTER

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start the timer, with ON time set sooner than OFF time

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON Setting: 3 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUTO OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF Setting: 7 hours

 

 

 

 

 

1. Be sure that you are at a standard control screen, and that the Auto Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hr ON

 

 

 

 

 

 

timer indicator is visible in the display (at ¡).

 

 

 

 

 

 

 

 

 

AFTER

 

 

 

 

 

 

When something other than the Auto Off Timer is displayed, set it to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At Timer Start

AUTO OFF TIMER using the function selection of remote controller (see

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

 

 

 

Display shows the timer’s ON setting (hours

8.[4]–3 (3)) timer function setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remaining to ON).

 

 

 

 

 

 

 

 

 

 

 

 

2. Hold down the Timer Menu button w for 3 seconds, so that the “Set Up”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At 3 hours after timer start

appears on the screen (at ).

 

 

 

 

 

 

 

 

 

Hr

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AFTER OFF

 

 

 

 

 

(Note that each press of the button toggles the display between “Set Up”

 

 

 

 

 

 

 

 

˚F

 

 

 

 

 

 

Display changes to show the timer’s OFF set-

 

 

 

 

˚F

 

 

 

 

SIMPLE

 

 

 

 

ting (hours remaining to OFF).

and “Monitor”.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The time displayed is OFF setting (7 hours) –

3. Press the appropriate Set Time button q as necessary to set the OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON setting (3 hours) = 4 hours.

time (at £).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At 7 hours after timer start

4. Press the Filter button 4 to lock in the setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

 

 

 

The air conditioner goes off, and will remain off

Your entry will be cancelled if you press the Mode (Return) button 2 before

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

until someone restarts it.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressing the Filter button 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5. Press the Mode (Return) button 2to complete the setting procedure and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

return to the standard control screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6. If the air conditioner is already running, the timer starts countdown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

immediately. Be sure to check that the timer setting appears cor-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rectly on the display.

 

 

 

 

 

 

 

10

Image 10
Contents Air-Conditioners Safety Precautions ContentsParts Names PKA-A·FA/PKA-A·FAL Wall Mounted PKA-A·GA/PKA-A·GAL Wall MountedPCA-A·GA Ceiling Suspended Operation Section Wired Remote-ControllerDisplay Section TempBattery installation/replacement Wireless Remote-ControllerOperation Screen ConfigurationSetting the Day of the Week and Time Turning ON/OFFFan speed setting Mode selectTemperature setting Airflow direction settingFor Wired Remote-controller TimerVentillation Simple Timer Timer Off indication is no longer displayedViewing the Current Simple Timer Settings Auto Off TimerTimer value is visible and appropriate Examples How to Set the Auto Off TimerFor wireless remote controller Other FunctionsFunction selection of remote controller Error Codes indicationFunction Selection Function selection flowchart Setting language EnglishDetailed setting Dot display table JapaneseTrouble Shooting Emergency Operation for Wireless Remote-controllerCare and Cleaning When the remote controller cannot be usedSimple , or Auto OFF appears Replace the batteries and press the Reset buttonController High sound Normal rooms Low sound Absorbing rooms LocationDRY CFM SpecificationsFLA MCA Mocp WET CFMPage Medidas de Seguridad ContenidoNombres de las piezas Rejilla Salida de aire PKA-A·GA/PKA-A·GAL Modelo montado en paredFiltro Entrada de aire PKA-A·FA/PKA-A·FAL Modelo montado en paredPara controlador remoto cableado Sección de pantallaSección de control Temp ON/OFFInterior Instalación/sustitución de pilasPara controlador remoto inalámbrico InicialManejo Configuración de la pantallaConfiguración de día de la semana y hora Encendido y apagadoAjuste de la velocidad del ventilador Selección de modoAjuste de la temperatura Ajuste de la dirección del flujo de aireVentilación TemporizadorPara controlador remoto cableado Temporizador simple De que ya no se muestre el indicador Timer OffCómo configurar el temporizador simple Para desactivar el temporizador semanalTemporizador de apagado automático Otras funciones Para controlador remoto inalámbricoSelección de función Indicación de códigos de errorSelección de funciones del controlador remoto Idioma ajustado inglés Ajuste detallado Tabla del indicador de puntos Cuando no puede utilizar el controlador remoto Mantenimiento y limpiezaLocalización de fallos Refrigeración CalefacciónENCENDIDO/APAGADO VOR, EspereEspecificaciones Specifications are subject to change without notice