Emerson VH Setup Operation, Setup functions and factory default values, Function Default Range

Page 16

Advanced Microprocessor Controls Setup

Setup Operation

The Setup Operation permits the review and/or adjustment of the unit configuration. The menu may include:

Cold Start: This feature, also referred to as Positive Start or Winter Start Kit, allows for the low- pressure switch to be ignored for the programmed time during a cold start of the compressors, enabling the unit to run at low suction pressures. Entering a “0” for this time will bypass this feature. A “1”, will bypass the low-pressure switch for one minute, a “2” for two minutes, etc. The programmed value can be from 0 to 3 minutes. This delay is factory set to 0 for water-cooled, glycol cooled, and GLYCOOLunits. Typically, only air-cooled units need a “Winter Start” time.

Restart: This feature allows for the unit to restart automatically after a loss of power. The pro- grammed value is in 0.1 minute (6 seconds) intervals. A programmed value of zero (0) would require the user to manually press the ON/OFF key to start the unit, i.e. no auto restart. The purpose of this feature is to prevent several units from starting at the same time after a loss of power. The message “Restart delay -- Please wait” will be displayed when the system is in the AUTO RESTART mode. (It is suggested that multiple unit installations be programmed with different auto restart times.)

IR Fill Rate (infrared humidifiers only): An autoflush system automatically controls a water makeup valve to maintain proper level in the infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours have elapsed since the last time the humidifier was on, the humidifier is held off until the valve completes an initial fill of the humidifier pan. This pre-fill is about 35 seconds for a small pan and 60 seconds for a large pan. The valve continues to fill and flush the pan for about 4 1/2 minutes for a small pan or 7 1/2 minutes for a large pan. Pan size is selected based on unit specifications and is preset at the factory.

During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri- odically to add water to the pan (about 45 seconds every 7 minutes of humidifier operation for a small pan, or 80 seconds every 10 minutes of operation for a large pan). This adds enough water to the pan to cause about a third of the total water used to be flushed out the overflow standpipe located in the humidifier pan. This action helps to remove solids from the pan. The flush rate is adjustable from 110% to 500%. If the water quality is poor, it may be desirable to increase the water flushing action above the normal 150% rate. Also, if the supply water pressure is low, the flush rate adjustment can be increased so that sufficient water level is maintained during humidification.

Chilled Water/Hot Water/Econ-O-Coil Flush: This feature will flush the respective coil for three

(3)minutes after the programmed number of hours of non-use. For example, if the flush time is pro- grammed with 24 hours on a hot water reheat type system and heating is not required for 24 hours, the hot water valve will be open for three (3) minutes to allow the coil to be flushed. The programmed value can be from 0 (zero) (no flush) to 99 (99 hours of non-use).

F/C Degrees: The control can be selected to show readings and setpoints in either degrees Fahren- heit (°F) or Celsius (°C).

The following table lists the Setup functions, their factory default values, and the allowable ranges that can be programmed:

Table 2

Setup functions and factory default values

 

 

 

Function

Default

Range

 

 

 

Cold Start Time Delay*

3

0 to 3 min (0 = no delay)

 

 

 

Restart Time Delay

0.1

0 to 9.9 min (0 =manual restart)

 

 

 

Infrared Fill Rate

150

110 to 500%

 

 

 

Chilled/Hot Water

24

0 to 99 hrs (also Econ-o-coil)

Coil Flush

 

 

 

F/C Degrees

F

C or F

 

 

 

*Factory set to 0 for water-cooled, glycol, and GLYCOOL™ units.

 

 

 

 

8

Image 16 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Alarm Descriptions and Solutions Temperature ControlSystem Testing Figures Page System Description IntroductionGlycool Chilled Glycol Cooling Systems Chilled Water SystemsDual Source Cooling Systems Initial START-UP Procedure Additional Considerations for Upflow Units Basics Advanced Microprocessor Controls Setup Display the Main Menu-AM Control Advanced microprocessor AM control menu Main Menu AM-Status/Alarm Data Active AlarmsAlarm History Log Operating StatusMain Menu AM-Setpoints/Setup Setup System SelectionDefault control and alarm setpoints Analog SensorsSetup functions and factory default values Setup OperationFunction Default Range Show DIP Switches DIP switch settingsSelect Options Calibrate SensorsSetup Alarms Select Control TypeAlarm default time delay Alarm Default Delay secondsAnalog Setup Standard Alarm MessagesHumidity Control Method Run Diagnostics Set Status DisplayCalibrate Actuator Show InputsChange Passwords Main Menu AM-Date and TimeTest Outputs Test Control BoardMain Menu AM-Status Display Load Control FeaturesControl Circuit Board DIP Switches CommunicationsNonvolatile Memory Control OutputsMonitor functions View/Change FunctionsAdvanced Microprocessor with Graphics Control Setup Advanced microprocessor with graphics control panelAdvanced microprocessor with graphics AG control menu Display the Main Menu-AG Control Main Menu AG-View/Set AlarmsMain Menu AG-Status Display Default Time Delay Alarm SecondsSet Up Custom Alarms Standard Custom Alarm MessagesSetup Water Detect Floor Plan Installation-LT750 DIP Switch SettingsMain Menu AG-Operating Status Main Menu AG-Setup SystemMain Menu AG-View/Set Control Setpoints Cold Start Delay Auto Restart DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlyCalibrate Valve Actuator Select Control AlgorithmMain Menu AG-Run Diagnostics Select Humidity Sensing ModeShow Inputs Main Menu AG-Date and Time Dehumidification with Normal or Delayed ReheatMain Menu AG-Plot Graphs Main Menu AG-Analog/Digital Inputs Set Up Digital Inputs Main Menu AG-View Run Hours LogRead Digital Inputs View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Temperature Control Response by Control TYPE-ADVANCED Microprocessor ControlsGlycool Cooling Dual Cooling SourceChilled Water Cooling Heating Operation Electric ReheatHumidity Control Hot Water/Steam HeatDehumidification/Humidification Required, in Percent % Control Types Proportional ControlChilled Water Dehumidification Dual Cooling Source DehumidificationHumidification Operation System Activation Suggested System Tuning Procedure Intelligent Control Load Control Features Connecting the Analog Sensors Analog SensorsChanging factory-set sensor inputs Additional connections available after unit deliveryWater Detection Display SetupPhysical Connections Calibration View/Change Functions Standard Alarms Alarm Descriptions and SolutionsChange Filter Compressor OverloadCustom Alarms Only With Advanced Controls High TemperatureHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLoss of Power Low TemperatureLoss of Air Flow Low HumidityOptional/Custom Alarms System Testing Component Operation and MAINTENANCE, Checks and AdjustmentsEnvironmental Control Functions Proportional Heating/Cooling/ DehumidificationFan Safety Switch Electric PanelControl Transformer and Fuses FirestatFilters Blower PackageFan Impellers and Bearings BeltsElectronic Variable Speed Drive Inverter Refrigeration SystemCompressor Oil Level Suction Pressure Discharge PressureSuction Superheat Thermostatic Expansion Valve OperationAdjustment Hot Gas Bypass Valve OperationOutdoor fan/condenser configuration Air Cooled CondenserAdjustment Johnson Controls/Penn Johnson valves Testing Function of ValveGlycol Solution Maintenance Water/Glycol Cooled Condensers Shell and Tube CondensersMechanical Failure Compressor ReplacementElectrical Failure Humidifier Compressor Replacement ProcedureInfrared Humidifier Autoflush Infrared Humidifier Cleaning System Changing Humidifier LampsAutoflush Operation Humidifier lampsSteam Generating Humidifier Steam generating humidifierControls Replacing the CanisterHumidifier canister part numbers Faults-canister generator humidifierPriority Name LED Indication Description Circuit Board Adjustments Steam generating humidifier capacityCapacity Hz Models Lbs/hr kg/hrUnit Rated Rated Values Voltage Capacity Electric ReheatVoltage AMP Set Pt Troubleshooting Blower troubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pumps troubleshootingHumidifier-steam generator troubleshooting Adjustments onHumidifier-infrared troubleshooting Reheat troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Ne t ItiTi n That