Emerson DE, VH, VE, DH manual Main Menu AG-Analog/Digital Inputs

Page 37

Advanced Microprocessor with Graphics Control Setup

Six different data types are recorded for graphing: temperature, humidity, and four user defined ana- log inputs. Each data type can be viewed over three different time scales and two different resolu- tions. The three time scales are 90 minutes, 8 hours, and 24 hours. The two resolutions are minimum and maximum. With minimum resolution selected, the full scale of the sensor is displayed. In other words, the largest and smallest possible sensor readings are shown. Maximum resolution shows a range which covers two fifths of the full scale sensor range.

4.10.1Modify Plot Scales

The Modify Plot Scales menu item adjusts the layout of the graph. This setup screen selects the time scale and resolution. It also adjusts the center of the graph for a maximum resolution graph.

The time scale and resolution can also be changed while the graph is displayed. The DOWN arrow key changes the time scale from 90 minutes to 8 hours to 24 hours. The UP arrow key toggles the display between maximum and minimum resolution.

4.11Main Menu (AG)—Analog/Digital Inputs

Selecting Analog/Digital Inputs steps to the following menu:

READ ANALOG INPUTS

SETUP ANALOG INPUTS

READ DIGITAL INPUTS

SETUP DIGITAL INPUTS

4.11.1Read Analog Inputs

The four (4) analog sensor inputs can be monitored from the display. The inputs are filtered, then dis- played along with the text label assigned during setup.

4.11.2Setup Analog Inputs

For installation of analog sensors, see 4.11 - Main Menu (AG)—Analog/Digital Inputs.

After selecting a compatible sensor and properly wiring it to the terminals, setting up the control to monitor the sensor is as follows:

Slope

The slope is a multiplier used to scale the input signal. The slope can be positive (rising) or negative (falling) and can range from 0 (resulting in a horizontal line) to ±999. The slope for a 0-5 V input is per 1 V input, for 0-10 V input is per 2 V input, and for 4-20 mA is per 4 mA input. For example, assuming an intercept of 0 for a 0-10 V sensor input with a slope of 50, an input of 1 V would be displayed as 25: (1x[50/2]); 2 V would be 50: (2x[50/2]); 3 V would be 75: (3x[50/2]), etc.

Intercept

The intercept is an offset from point 0 corresponding to 0 volts or 0 mA input. The intercept can be positive or negative and can be a point from 0 to ±999. Adding an intercept of 100 to the slope example above, 1 V would be 125: 100 + (1x[50/2]); 2 V would be 150: 100 + (2x[50/2]); 3 V would be 175: 100 + (3x[50/2]); etc.

NOTE

For a 4-20 mA input sensor, if the desired reading at 4 mA input is 0, then an intercept of -1 x slope would be required. For example, assuming a slope of 50, the formula would be ([-1 x 50] + 4 x [50/4]) = 0. The intercept is -50.

Text

You may enter a custom label for each analog input. The text label can be 20 characters in length including any of the following:

ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789, or space.

29

Image 37 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Temperature Control Alarm Descriptions and SolutionsSystem Testing Figures Page Introduction System DescriptionGlycool Chilled Glycol Cooling Systems Chilled Water SystemsDual Source Cooling Systems Additional Considerations for Upflow Units Initial START-UP ProcedureBasics Advanced Microprocessor Controls SetupDisplay the Main Menu-AM Control Advanced microprocessor AM control menu Active Alarms Main Menu AM-Status/Alarm DataAlarm History Log Operating StatusSetup System Selection Main Menu AM-Setpoints/SetupDefault control and alarm setpoints Analog SensorsSetup functions and factory default values Setup OperationFunction Default Range DIP switch settings Show DIP SwitchesSelect Options Calibrate SensorsSelect Control Type Setup AlarmsAlarm Default Delay seconds Alarm default time delayAnalog Setup Standard Alarm MessagesHumidity Control Method Set Status Display Run DiagnosticsCalibrate Actuator Show InputsMain Menu AM-Date and Time Change PasswordsTest Outputs Test Control BoardMain Menu AM-Status Display Load Control FeaturesControl Circuit Board Communications DIP SwitchesNonvolatile Memory Control OutputsView/Change Functions Monitor functionsAdvanced microprocessor with graphics control panel Advanced Microprocessor with Graphics Control SetupAdvanced microprocessor with graphics AG control menu Display the Main Menu-AG Control Main Menu AG-View/Set AlarmsMain Menu AG-Status Display Alarm Seconds Default Time DelayStandard Custom Alarm Messages Set Up Custom AlarmsSetup Water Detect Floor Plan Installation-LT750 DIP Switch SettingsMain Menu AG-Operating Status Main Menu AG-Setup SystemMain Menu AG-View/Set Control Setpoints Auto Restart Delay Cold Start DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers only Select Control Algorithm Calibrate Valve ActuatorSelect Humidity Sensing Mode Main Menu AG-Run DiagnosticsShow Inputs Main Menu AG-Date and Time Dehumidification with Normal or Delayed ReheatMain Menu AG-Plot Graphs Main Menu AG-Analog/Digital Inputs Main Menu AG-View Run Hours Log Set Up Digital InputsRead Digital Inputs View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Response by Control TYPE-ADVANCED Microprocessor Controls Temperature ControlDual Cooling Source Glycool CoolingChilled Water Cooling Heating Operation Electric ReheatHot Water/Steam Heat Humidity ControlDehumidification/Humidification Required, in Percent % Control Types Proportional ControlChilled Water Dehumidification Dual Cooling Source DehumidificationHumidification Operation System Activation Suggested System Tuning Procedure Intelligent Control Load Control Features Analog Sensors Connecting the Analog SensorsChanging factory-set sensor inputs Additional connections available after unit deliveryWater Detection Display SetupPhysical Connections Calibration View/Change Functions Alarm Descriptions and Solutions Standard AlarmsChange Filter Compressor OverloadHigh Temperature Custom Alarms Only With Advanced ControlsHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLow Temperature Loss of PowerLoss of Air Flow Low HumidityOptional/Custom Alarms Component Operation and MAINTENANCE, Checks and Adjustments System TestingEnvironmental Control Functions Proportional Heating/Cooling/ DehumidificationElectric Panel Fan Safety SwitchControl Transformer and Fuses FirestatBlower Package FiltersFan Impellers and Bearings BeltsElectronic Variable Speed Drive Inverter Refrigeration SystemCompressor Oil Level Discharge Pressure Suction PressureSuction Superheat Thermostatic Expansion Valve OperationHot Gas Bypass Valve Operation AdjustmentAir Cooled Condenser Outdoor fan/condenser configurationTesting Function of Valve Adjustment Johnson Controls/Penn Johnson valvesGlycol Solution Maintenance Water/Glycol Cooled Condensers Shell and Tube CondensersMechanical Failure Compressor ReplacementElectrical Failure Humidifier Compressor Replacement ProcedureInfrared Humidifier Changing Humidifier Lamps Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Humidifier lampsSteam generating humidifier Steam Generating HumidifierReplacing the Canister ControlsHumidifier canister part numbers Faults-canister generator humidifierPriority Name LED Indication Description Steam generating humidifier capacity Circuit Board AdjustmentsCapacity Hz Models Lbs/hr kg/hrUnit Rated Rated Values Voltage Capacity Electric ReheatVoltage AMP Set Pt Blower troubleshooting TroubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pumps troubleshooting Dehumidification troubleshootingAdjustments on Humidifier-steam generator troubleshootingReheat troubleshooting Humidifier-infrared troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Iti Ne tTi n That