Emerson DH, VH, DE, VE Water/Glycol Cooled Condensers Shell and Tube Condensers, Regulating Valves

Page 63

Component Operation and Maintenance, Checks and Adjustments

7.4.8Water/Glycol Cooled Condensers Shell and Tube Condensers

Each water or glycol cooled module has a shell and tube condenser which consists of a shell, remov- able heads, gaskets and cleanable copper tubes.

It may be necessary to clean the copper tubing periodically to remove any scale or lime that should collect (periods between cleanings will vary with local water conditions). As deposits build up, a clean- ing tool, available at any refrigeration supply house, should be used to clean the heat exchanger tubes.

1.Stop the unit (using the start/stop switch) and allow the compressor to pump down.

2.Open the disconnect switch.

3.Shut off the water supply valve to the condenser.

4.Drain the water from condensers and piping.

5.Remove the bolts securing each head and slowly pry them free.

6.Remove old gaskets and inspect sealing surfaces for pits and corrosion.

7.Swab the condenser tubes with a tube cleaning tool.

8.When the tubes are clean, reinstall the heads using new factory gaskets.

9.Consult factory for specific torque requirements.

10.Reconnect the piping, open water supply valve, vent the system and check for leaks.

Regulating Valves

The water regulating valves automatically regulate the amount of fluid necessary to remove the heat from the refrigeration system, permitting more water to flow when load conditions are high and less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.

Adjustment (Johnson Controls/Penn Johnson valves)

The valves may be adjusted with a standard refrigeration service valve wrench or screwdriver. Refer to Table 16 for recommended refrigerant pressures.

To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure gauge indicates the desired setting.

To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired set- ting is obtained.

If your unit is equipped with valves from other manufacturers, please consult the factory.

Testing Function of Valve

First, turn off the refrigeration system.

When the refrigeration system has been off for approximately 10 to 15 minutes, the water flow should stop.

If the water continues to flow, the valve is either improperly adjusted (with head pressure too low) or the pressure sensing capillary is not connected properly to the condenser.

Glycol Solution Maintenance

It is difficult to establish a specific schedule of inhibitor maintenance since the rate of inhibitor deple- tion depends upon local water conditions. Analysis of water samples at time of installation and every six (6) months should help to establish a pattern of depletion. A visual inspection of the solution and filter residue is often helpful in judging whether or not active corrosion is occurring.

The complexity of water-caused problems and their correction makes it important to obtain the advice of a water treatment specialist and follow a regularly scheduled maintenance program.

Proper inhibitor maintenance must be performed in order to prevent corrosion of the glycol system. Consult glycol manufacturer for testing and maintenance of inhibitors. Do not mix products from dif- ferent manufacturers.

55

Image 63 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Temperature Control Alarm Descriptions and SolutionsSystem Testing Figures Page Introduction System DescriptionChilled Water Systems Glycool Chilled Glycol Cooling SystemsDual Source Cooling Systems Additional Considerations for Upflow Units Initial START-UP ProcedureAdvanced Microprocessor Controls Setup BasicsDisplay the Main Menu-AM Control Advanced microprocessor AM control menu Operating Status Main Menu AM-Status/Alarm DataActive Alarms Alarm History LogAnalog Sensors Main Menu AM-Setpoints/SetupSetup System Selection Default control and alarm setpointsSetup Operation Setup functions and factory default valuesFunction Default Range Calibrate Sensors Show DIP SwitchesDIP switch settings Select OptionsSelect Control Type Setup AlarmsAlarm Default Delay seconds Alarm default time delayStandard Alarm Messages Analog SetupHumidity Control Method Show Inputs Run DiagnosticsSet Status Display Calibrate ActuatorTest Control Board Change PasswordsMain Menu AM-Date and Time Test OutputsLoad Control Features Main Menu AM-Status DisplayControl Circuit Board Control Outputs DIP SwitchesCommunications Nonvolatile MemoryView/Change Functions Monitor functionsAdvanced microprocessor with graphics control panel Advanced Microprocessor with Graphics Control SetupAdvanced microprocessor with graphics AG control menu Main Menu AG-View/Set Alarms Display the Main Menu-AG ControlMain Menu AG-Status Display Alarm Seconds Default Time DelayInstallation-LT750 DIP Switch Settings Set Up Custom AlarmsStandard Custom Alarm Messages Setup Water Detect Floor PlanMain Menu AG-Setup System Main Menu AG-Operating StatusMain Menu AG-View/Set Control Setpoints IR Flush Overfill infrared humidifiers only Cold Start DelayAuto Restart Delay Default Settings and RangesSelect Control Algorithm Calibrate Valve ActuatorSelect Humidity Sensing Mode Main Menu AG-Run DiagnosticsShow Inputs Dehumidification with Normal or Delayed Reheat Main Menu AG-Date and TimeMain Menu AG-Plot Graphs Main Menu AG-Analog/Digital Inputs View 24 Hour Run Time History Set Up Digital InputsMain Menu AG-View Run Hours Log Read Digital InputsControl Circuit Board On/Off Status Time View Only Silence Alarm Response by Control TYPE-ADVANCED Microprocessor Controls Temperature ControlHeating Operation Electric Reheat Glycool CoolingDual Cooling Source Chilled Water CoolingControl Types Proportional Control Humidity ControlHot Water/Steam Heat Dehumidification/Humidification Required, in Percent %Dual Cooling Source Dehumidification Chilled Water DehumidificationHumidification Operation System Activation Suggested System Tuning Procedure Intelligent Control Load Control Features Additional connections available after unit delivery Connecting the Analog SensorsAnalog Sensors Changing factory-set sensor inputsSetup Water Detection DisplayPhysical Connections Calibration View/Change Functions Compressor Overload Standard AlarmsAlarm Descriptions and Solutions Change FilterHumidifier Problem Infrared Humidifiers Custom Alarms Only With Advanced ControlsHigh Temperature High Temperature and Low Temperature SimultaneouslyLow Humidity Loss of PowerLow Temperature Loss of Air FlowOptional/Custom Alarms Proportional Heating/Cooling/ Dehumidification System TestingComponent Operation and MAINTENANCE, Checks and Adjustments Environmental Control FunctionsFirestat Fan Safety SwitchElectric Panel Control Transformer and FusesBelts FiltersBlower Package Fan Impellers and Bearings Refrigeration System Electronic Variable Speed Drive Inverter Compressor Oil Level Thermostatic Expansion Valve Operation Suction PressureDischarge Pressure Suction SuperheatHot Gas Bypass Valve Operation AdjustmentAir Cooled Condenser Outdoor fan/condenser configurationWater/Glycol Cooled Condensers Shell and Tube Condensers Adjustment Johnson Controls/Penn Johnson valvesTesting Function of Valve Glycol Solution MaintenanceCompressor Replacement Mechanical FailureElectrical Failure Compressor Replacement Procedure HumidifierInfrared Humidifier Humidifier lamps Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Autoflush OperationSteam generating humidifier Steam Generating HumidifierReplacing the Canister ControlsFaults-canister generator humidifier Humidifier canister part numbersPriority Name LED Indication Description Hz Models Lbs/hr kg/hr Circuit Board AdjustmentsSteam generating humidifier capacity CapacityElectric Reheat Unit Rated Rated Values Voltage CapacityVoltage AMP Set Pt Symptom Possible Cause Check or Remedy TroubleshootingBlower troubleshooting Chilled water troubleshootingCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pumps troubleshooting Dehumidification troubleshootingAdjustments on Humidifier-steam generator troubleshootingReheat troubleshooting Humidifier-infrared troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL That Ne tIti Ti n