Emerson DE, VH, VE, DH manual Compressor Replacement Procedure, Infrared Humidifier

Page 65

Component Operation and Maintenance, Checks and Adjustments

Compressor Replacement Procedure

Replacement compressors are available from your Liebert supplier. They will be shipped in a reusable crate to the job site as required by the service contractor.

Upon shipping a replacement compressor, the service contractor will be billed in full for the compres- sor until the replacement has been returned to the factory.

The compressor should be returned in the same container used for shipping to the job. The possible damage causes or conditions that were found should be recorded by marking the compressor return tag.

1.Disconnect power.

2.Attach suction and discharge gauges to access fittings.

3.Recover refrigerant using standard recovery procedures and equipment. Use a filter-drier when charging the system with recovered refrigerant.

! WARNING

Do not loosen any refrigeration or electrical connections before relieving pressure.

NOTE

Release of refrigerant to the atmosphere is harmful to the environment and is unlawful. Refrigerant must be recycled or discarded in accordance with federal, state, and local regulations.

4.Front seat service valves to isolate the compressor. Reclaim charge from compressor.

5.Remove service valves, pressure switch capillaries, and disconnect all electrical connections.

6.Remove failed compressor.

7.Follow manufacturer’s instructions for clean out kits.

8.Install replacement compressor and make all connections.

9.Pressurize and leak test the system at approximately 150 PSIG (1034 kPa) pressure.

10.Evacuate the system twice to 1500 microns, and the third time to 500 microns. Break the vacuum each time with clean, dry refrigerant to 2 PSIG (13.8 kPa).

11.Charge the system with refrigerant (R-22) based on requirements of the evaporator, condensing unit and lines. Refer to the installation manual or the unit nameplate.

12.Apply power and operate the system. Check for proper operation. Refer to Table 16 for design pressures.

7.5Humidifier

7.5.1Infrared Humidifier

During normal humidifier operation, deposits of mineral solids will collect in the humidifier pan. This should be cleaned out periodically to ensure efficient operation. Each water supply has different char- acteristics, so time interval between cleanings must be determined locally. A monthly check (and cleaning if necessary) is recommended.

The humidifier pan is easily removed by draining the pan (remove the standpipe), disconnect the drain coupling, and removing the retaining screws on each end of the pan.

! CAUTION

Before removing pan, be sure power to unit is disconnected and water in humidifier pan is no hotter than lukewarm.

Scale on the side and bottom can be loosened with a stiff brush. Flush with water and replace pan in humidifier.

An autoflush system can greatly increase the time between cleanings, but does not eliminate the need for periodic checks and maintenance.

57

Image 65 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Temperature Control Alarm Descriptions and SolutionsSystem Testing Figures Page Introduction System DescriptionDual Source Cooling Systems Chilled Water SystemsGlycool Chilled Glycol Cooling Systems Additional Considerations for Upflow Units Initial START-UP ProcedureDisplay the Main Menu-AM Control Advanced Microprocessor Controls SetupBasics Advanced microprocessor AM control menu Active Alarms Main Menu AM-Status/Alarm DataAlarm History Log Operating StatusSetup System Selection Main Menu AM-Setpoints/SetupDefault control and alarm setpoints Analog SensorsFunction Default Range Setup OperationSetup functions and factory default values DIP switch settings Show DIP SwitchesSelect Options Calibrate SensorsSelect Control Type Setup AlarmsAlarm Default Delay seconds Alarm default time delayHumidity Control Method Standard Alarm MessagesAnalog Setup Set Status Display Run DiagnosticsCalibrate Actuator Show InputsMain Menu AM-Date and Time Change PasswordsTest Outputs Test Control BoardControl Circuit Board Load Control FeaturesMain Menu AM-Status Display Communications DIP SwitchesNonvolatile Memory Control OutputsView/Change Functions Monitor functionsAdvanced microprocessor with graphics control panel Advanced Microprocessor with Graphics Control SetupAdvanced microprocessor with graphics AG control menu Main Menu AG-Status Display Main Menu AG-View/Set AlarmsDisplay the Main Menu-AG Control Alarm Seconds Default Time DelayStandard Custom Alarm Messages Set Up Custom AlarmsSetup Water Detect Floor Plan Installation-LT750 DIP Switch SettingsMain Menu AG-View/Set Control Setpoints Main Menu AG-Setup SystemMain Menu AG-Operating Status Auto Restart Delay Cold Start DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlySelect Control Algorithm Calibrate Valve ActuatorSelect Humidity Sensing Mode Main Menu AG-Run DiagnosticsShow Inputs Main Menu AG-Plot Graphs Dehumidification with Normal or Delayed ReheatMain Menu AG-Date and Time Main Menu AG-Analog/Digital Inputs Main Menu AG-View Run Hours Log Set Up Digital InputsRead Digital Inputs View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Response by Control TYPE-ADVANCED Microprocessor Controls Temperature ControlDual Cooling Source Glycool CoolingChilled Water Cooling Heating Operation Electric ReheatHot Water/Steam Heat Humidity ControlDehumidification/Humidification Required, in Percent % Control Types Proportional ControlHumidification Operation System Activation Dual Cooling Source DehumidificationChilled Water Dehumidification Suggested System Tuning Procedure Intelligent Control Load Control Features Analog Sensors Connecting the Analog SensorsChanging factory-set sensor inputs Additional connections available after unit deliveryPhysical Connections SetupWater Detection Display Calibration View/Change Functions Alarm Descriptions and Solutions Standard AlarmsChange Filter Compressor OverloadHigh Temperature Custom Alarms Only With Advanced ControlsHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLow Temperature Loss of PowerLoss of Air Flow Low HumidityOptional/Custom Alarms Component Operation and MAINTENANCE, Checks and Adjustments System TestingEnvironmental Control Functions Proportional Heating/Cooling/ DehumidificationElectric Panel Fan Safety SwitchControl Transformer and Fuses FirestatBlower Package FiltersFan Impellers and Bearings BeltsCompressor Oil Level Refrigeration SystemElectronic Variable Speed Drive Inverter Discharge Pressure Suction PressureSuction Superheat Thermostatic Expansion Valve Operation Hot Gas Bypass Valve Operation AdjustmentAir Cooled Condenser Outdoor fan/condenser configurationTesting Function of Valve Adjustment Johnson Controls/Penn Johnson valvesGlycol Solution Maintenance Water/Glycol Cooled Condensers Shell and Tube CondensersElectrical Failure Compressor ReplacementMechanical Failure Infrared Humidifier Compressor Replacement ProcedureHumidifier Changing Humidifier Lamps Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Humidifier lampsSteam generating humidifier Steam Generating HumidifierReplacing the Canister ControlsPriority Name LED Indication Description Faults-canister generator humidifierHumidifier canister part numbers Steam generating humidifier capacity Circuit Board AdjustmentsCapacity Hz Models Lbs/hr kg/hrVoltage AMP Set Pt Electric ReheatUnit Rated Rated Values Voltage Capacity Blower troubleshooting TroubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pumps troubleshooting Dehumidification troubleshootingAdjustments on Humidifier-steam generator troubleshootingReheat troubleshooting Humidifier-infrared troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Iti Ne tTi n That