Emerson VE, VH, DE, DH Circuit Board Adjustments, Steam generating humidifier capacity, Capacity

Page 70

Component Operation and Maintenance, Checks and Adjustments

Circuit Board Adjustments

! WARNING

Circuit board adjustment should be performed by qualified personnel only. Hazardous voltages are present in the equipment throughout the procedure. Use extreme caution. If desired, power may be disconnected prior to the procedure.

NOTE

Numbers and percentages within parentheses ( ) in the following paragraphs refer to circuit board settings for downflow models FH599C, 600C, 739C and 740C.

Humidifier operation is governed by the humidifier control board. This board is located in the lower right area of the panel in the control section of the unit, or in the humidifier compartment on models FH599C, 600C, 739C and 740C. There are two potentiometers mounted on the board. These pots can be used to adjust for extreme water conductivity conditions and capacity.

The “%” pot controls the amperage at which the drain will energize. The pot is clearly marked in per- centages. This adjustment is factory set, which indicates that the unit will drain when the amperage falls off of the capacity setpoint. Raising the value increases the frequency of drain cycles. Lowering the value decreases the frequency of drain cycles. The frequency should be increased for highly con- ductive water and decreased for less conductive water. If adjustment is necessary, and a change of three to four percent in either direction does not permit normal operation of the unit, consult your Liebert supplier.

The pot marked “SEC” controls the duration of the drain cycle. The pot is clearly marked in seconds. This adjustment is factory set at 60 (84) seconds and should not be readjusted without consulting your Liebert supplier.

Table 19 Steam generating humidifier capacity

 

 

Capacity

60 Hz Models

50 Hz Models

lbs/hr (kg/hr)

 

 

 

75A, 72G, 86W, 114A, 110G, 127W, 125A,

75A, 72G, 86W, 147C, 200C, 248C

11 (5)

116G, 138W, 147C, 200C, 248C

 

 

199A, 192G, 219W, 245A, 240G, 267W,

115A, 111G, 128W, 130A, 121G, 143W,

22 (10)

290A, 265G, 315W, 380A, 363G, 412W,

199A, 192G, 219W, 245A, 240G, 267W,

 

302C, 376C, 422C, 529C, 600C, 740C

290A, 265G, 315W, 380A, 363G, 412W,

 

 

302C, 376C, 422C, 529C, 599C, 739C

 

! CAUTION

The DIP switches must be set exactly as indicated in Table 20. Failure to correctly set the DIP switches may result in an electrical or water hazard.

The DIP switches are used to set the capacity of the humidifier. These are preset at the factory and should not be changed. Refer to Table 19 for the capacity of your unit. Find your unit voltage and capacity in Table 20 to determine the correct DIP switch settings for your humidifier. A potentiome- ter (R40) is used to regulate the capacity of the humidifier. This adjustment is factory set fully clock- wise to 100%. It can be used to reduce humidifier capacity, but should never be used to raise the capacity above the capacity for your model. Turn the adjustment counterclockwise to reduce your capacity. The minimum setting is approximately 50% of the DIP switch setting.

62

Image 70 Contents
Liebert Deluxe System/3 Page Table of Contents Main Menu AG-Run Diagnostics Alarm Descriptions and Solutions Temperature ControlSystem Testing Figures Page System Description IntroductionGlycool Chilled Glycol Cooling Systems Chilled Water SystemsDual Source Cooling Systems Initial START-UP Procedure Additional Considerations for Upflow UnitsBasics Advanced Microprocessor Controls SetupDisplay the Main Menu-AM Control Advanced microprocessor AM control menu Alarm History Log Main Menu AM-Status/Alarm DataActive Alarms Operating StatusDefault control and alarm setpoints Main Menu AM-Setpoints/SetupSetup System Selection Analog SensorsSetup functions and factory default values Setup OperationFunction Default Range Select Options Show DIP SwitchesDIP switch settings Calibrate SensorsSetup Alarms Select Control TypeAlarm default time delay Alarm Default Delay secondsAnalog Setup Standard Alarm MessagesHumidity Control Method Calibrate Actuator Run DiagnosticsSet Status Display Show InputsTest Outputs Change PasswordsMain Menu AM-Date and Time Test Control BoardMain Menu AM-Status Display Load Control FeaturesControl Circuit Board Nonvolatile Memory DIP SwitchesCommunications Control OutputsMonitor functions View/Change FunctionsAdvanced Microprocessor with Graphics Control Setup Advanced microprocessor with graphics control panelAdvanced microprocessor with graphics AG control menu Display the Main Menu-AG Control Main Menu AG-View/Set AlarmsMain Menu AG-Status Display Default Time Delay Alarm SecondsSetup Water Detect Floor Plan Set Up Custom AlarmsStandard Custom Alarm Messages Installation-LT750 DIP Switch SettingsMain Menu AG-Operating Status Main Menu AG-Setup SystemMain Menu AG-View/Set Control Setpoints Default Settings and Ranges Cold Start DelayAuto Restart Delay IR Flush Overfill infrared humidifiers onlyCalibrate Valve Actuator Select Control AlgorithmMain Menu AG-Run Diagnostics Select Humidity Sensing ModeShow Inputs Main Menu AG-Date and Time Dehumidification with Normal or Delayed ReheatMain Menu AG-Plot Graphs Main Menu AG-Analog/Digital Inputs Read Digital Inputs Set Up Digital InputsMain Menu AG-View Run Hours Log View 24 Hour Run Time HistoryControl Circuit Board On/Off Status Time View Only Silence Alarm Temperature Control Response by Control TYPE-ADVANCED Microprocessor ControlsChilled Water Cooling Glycool CoolingDual Cooling Source Heating Operation Electric ReheatDehumidification/Humidification Required, in Percent % Humidity ControlHot Water/Steam Heat Control Types Proportional ControlChilled Water Dehumidification Dual Cooling Source DehumidificationHumidification Operation System Activation Suggested System Tuning Procedure Intelligent Control Load Control Features Changing factory-set sensor inputs Connecting the Analog SensorsAnalog Sensors Additional connections available after unit deliveryWater Detection Display SetupPhysical Connections Calibration View/Change Functions Change Filter Standard AlarmsAlarm Descriptions and Solutions Compressor OverloadHigh Temperature and Low Temperature Simultaneously Custom Alarms Only With Advanced ControlsHigh Temperature Humidifier Problem Infrared HumidifiersLoss of Air Flow Loss of PowerLow Temperature Low HumidityOptional/Custom Alarms Environmental Control Functions System TestingComponent Operation and MAINTENANCE, Checks and Adjustments Proportional Heating/Cooling/ DehumidificationControl Transformer and Fuses Fan Safety SwitchElectric Panel FirestatFan Impellers and Bearings FiltersBlower Package BeltsElectronic Variable Speed Drive Inverter Refrigeration SystemCompressor Oil Level Suction Superheat Suction PressureDischarge Pressure Thermostatic Expansion Valve OperationAdjustment Hot Gas Bypass Valve OperationOutdoor fan/condenser configuration Air Cooled CondenserGlycol Solution Maintenance Adjustment Johnson Controls/Penn Johnson valvesTesting Function of Valve Water/Glycol Cooled Condensers Shell and Tube CondensersMechanical Failure Compressor ReplacementElectrical Failure Humidifier Compressor Replacement ProcedureInfrared Humidifier Autoflush Operation Autoflush Infrared Humidifier Cleaning System Changing Humidifier Lamps Humidifier lampsSteam Generating Humidifier Steam generating humidifierControls Replacing the CanisterHumidifier canister part numbers Faults-canister generator humidifierPriority Name LED Indication Description Capacity Circuit Board AdjustmentsSteam generating humidifier capacity Hz Models Lbs/hr kg/hrUnit Rated Rated Values Voltage Capacity Electric ReheatVoltage AMP Set Pt Chilled water troubleshooting TroubleshootingBlower troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pumps troubleshootingHumidifier-steam generator troubleshooting Adjustments onHumidifier-infrared troubleshooting Reheat troubleshootingMaintenance Inspection CHECKLIST-MONTHLY Maintenance Inspection CHECKLIST-SEMIANNUAL Ti n Ne tIti That